 | STUV 30 COMPACT INSTALLATION AND USER MANUAL

^

3.2  Protecting the floor

•  Any combustible floor beneath a fireplace must have a floor protector that extends 300mm at the front. 

•  If installed directly on combustible material, the floor protector must be made of a minimum 9mm thick cement 

sheet. Non-combustible finishes can be applied to the floor protector (tiles, steel sheet, light concrete, etc).

•   If the combustible floor is installed on concrete, you can replace the combustible material with non-

combustible material laid directly onto the concrete. 

Joist

Insulative board (9mm)

+ non combustible finish

Combustible 
floor (eg. timber)

FLOOR PROTECTOR LAID ON TIMBER FLOOR

3. INSTALLATION 

(CONTINUED)

Joist

Insulative board (9mm)

+ non combustible finish

Combustible 
floor (eg. timber)

FLOOR PROTECTOR LAID ON JOIST

Содержание STUV 30 COMPACT

Страница 1: ...1 TECHNICAL DATA 2 2 PRE INSTALLATION 3 3 INSTALLATION 5 4 OPERATION 9 5 TESTING 10 Keep for future use STUV 30 COMPACT MODEL SPECIFICATIONS...

Страница 2: ...CHNICAL DATA DETERMINED UNDER TEST CONDITIONS Nominal thermal output 8kW Efficiency Australian Test 80 Emissions Australian Test 1 1 g Kg 8 Flue 465 1040 WEIGHT AND DIMENSIONS Dimensions Firebox W465...

Страница 3: ...e internal flue and engage the firebox Ensure the floor has adequate protection CAUTION Using components or parts other than those provided by the manufacturer or modifying the specification of compon...

Страница 4: ...uced with the application of heat shielding to walls in accordance to the Australian Building Code For information on heat shielding please contact our office on 03 9416 0400 or email info oblica com...

Страница 5: ...Case 10 Outer Case 6 Active Flue 8 Flue 8 Flue CEILING RING RUBBER DEKTITE FLASHING 6 Active Flue Fireplace outlet 3 INSTALLATION 3 1 Installing flue kit Ensure flue is installed as per Australian sta...

Страница 6: ...roof Alternatively there must be a minimum distance of 3 meters from any higher section of roof 40 cm 40 cm 40 cm 3 m 900 cm 3 m 900 cm 900 cm The top of the flue must be 900mm above the roofline Alt...

Страница 7: ...combustiblefinishescanbeappliedtothefloorprotector tiles steelsheet lightconcrete etc If the combustible floor is installed on concrete you can replace the combustible material with non combustible m...

Страница 8: ...ALLATION AND USER MANUAL Non combustible finish eg tiles Concrete Combustible floor eg timber 300mm 167 5 167 5 747mm 800mm Combustible floor eg Timber Floor protector FLOOR PROTECTOR LAID ON CONCRETE...

Страница 9: ...s to start or rekindle the fire Do not use flammable liquids or aerosols in the vicinity of the fireplace when operating Do not store fuel within prescribed installation clearance distances The use of...

Страница 10: ...ion of Power Output and Efficiency and AS NZS 4013 2014 for Flue Gas Emission using hardwood fuel ISSUE DATE 7 10 2015 INVESTIGATING OFFICER Steve Marland RESULTS The appliance particulate emission fa...

Отзывы: