9

1310836-07 | Mar 02 2016

MODEL: CAREL PJEZ

 

AN ACCESS CODE IS NEEDED TO MODIFY PARAMETERS. 
PLEASE CONTACT 

MTL TECH SUPPORT

 TO RECEIVE YOUR 

ACCESS CODE

 

1.888.685.8324

DISPLAYS AND FUNCTIONS

During normal operation, the controller displays the 
temperature read by probe 1. In addition, the display has 
LEDs that indicate the activation of control functions (see 
Table 1), while the 3 buttons can be used to activate /
deactivate some of the functions (see Table 2).

LEDS AND ASSOCIATED FUNCTIONS

TABLE OF FUNCTION ACTIVATED BY THE BUTTONS
 

 

 

TURNING THE DEVICE ON/OFF

Press UP for more than 3 seconds. The control and 
defrost algorithms are now disabled and the instrument 
displays the message "OFF" alternating by tempreature 
read by the set probe. Manual 

SETTIN THE SET POINT (DESIRED TEMPERATURE)

 

ACCESSING AND SETTING THE PARAMETERS

Controller Settings

Lighting   

ON/OFF Switch

Cooler 

ON/OFF Switch

FACTORY SETTINGS CAREL

Parameter

Function

Set Range

Factory Settings

PS

Password

0 - 200

22

-

Set point

24º - 32º F

26 ºF

/5

Select °C / °F 

0 - 1

1 ºF

r1

Minimum set point allowed to the user

-50.0 - r2

24 ºF

r2

Maximum set point allowed to the user

r1 - 200

32 ºF

rd

Control differential (hysteresis)

0.0 - 19.0

3 ºF

c2

Min. compressor off time

0 - 100

4 min

d1

Interval between two defrosts

0 - 199

3 hr

dt

End defrost temperature

50.0 - 130.0

47 ºF

dP

Max. or effective defrost duration

1 - 199

40 min

DESCRIPTION 

PJEZ* represent a range of electronic microprocessor controllers with LED display developed for the manage-

ment of refrigerating units, display cabinets and showcases.

TECHNICAL SPECIFICATIONS

•  Electronic controllers for low temperature ventilated refrigeration units

•  Power supply 115 or 230Vac

•  Ambient probe NTC

•  Compressor relay 16A

•  Defrost relay 8A

•  Evaporator fan relay 8A

DISPLAY AND FUNCTIONS

During normal operation, the controller displays the temperature read by probe 1. In addition, the display has 

LEDs that indicate the activation of the control functions (see Table 1), while the 3 buttons can be used to 

activate/deactivate some of the functions (see Table 2).

LEDS AND ASSOCIATED FUNCTIONS

icon

function

normal operation

ON

OFF

blink

compressor

on

off

request

ON

fan

on

off

request

ON

defrost

on

off

request

ON

alarm

all

no alarm

-

ON

Tab. 1

TABLE OF FUNCTIONS ACTIVATED BY THE BUTTONS 

button

normal operation

start up

pressing the button alone

pressed together

up 

ON/OFF

more than 3 s: 

toggle ON/OFF

Pressed together start/stop 

continuous cycle

-

down 

defrost

more than 3 s: 

start/stop defrost

for 1 s display 

fi rmware vers. code

set mute

- 1 s.: display/set the setpoint

- more than 3 s: access parameter 

  setting menu (enter password ‘22’)

- mute audible alarm  (buzzer)

-

for 1 s RESET 

current 

EZY set

Tab. 2

SETTING THE SETPOINT (DESIRED TEMPERATURE)

g

n

i

n

a

e

M

t

c

e

ff

E

n

o

it

c

A

p

e

t

S

1

Keep  SET  button pressed for 2 s

After 1 sec currently setpoint value will 

fl ash on display

It’s regulation setpoint 

currently active

2

Press UP  or DOWN  buttons

Setpoint value will chang

3

Press SET  button

Controller will visualize temperature 

read by probes again

Setpoint is modifi ed and 

saved

Tab. 3

ACCESSING AND SETTING THE PARAMETERS

g

n

i

n

a

e

M

t

c

e

ff

E

n

o

it

c

A

p

e

t

S

1

Keep  SET  button pressed 

for 3 s

After 3 sec display will visualize “ PS”

Password is requested

2

Press SET  button again

Display will visualize “ 0” blinking

3

Press UP  or DOWN  button Visualized value on display will change

22”

4

Press SET  button

After 5 sec the fi rst parameter, “ /5”, will be 

visualized on display

It’s the name of the fi rst 

parameter

5

Press UP  or DOWN  button Parameter list will be scrolled on display 

(refer to Table of parameters)

Select desired parameter

6

Press SET  button

Display will visualize value of the selected 

parameter

It’s the currently parameter 

value

7

Press UP  or DOWN  button Parameter value visualized on display will 

change

Set desired value

8

Press SET  button

Display will visualize parameter name 

again

Attention : parameters 

updating is not yet active

9

Repeat steps  5, 6, 7  and  8 

for all desired parameters

10 Keep  SET  button 

pressed for 5 s

Controller will visualize temperature read 

by probes again

Attention:  now parame-

ters updating will be active 

Tab. 4

Insert password “

Set desired value

start up

PJEZ* easy 

electronic controller

SWITCHING THE DEVICE ON/OFF

Press UP for more than 3 s. The control and defrost algorithms are now disabled and the instrument displays the 

message “OFF” alternating with the temperature read by the set probe. 

MANUAL DEFROST

Press DOWN  for more than 3 s (the defrost starts only if the temperature conditions are valid).

CONTINUOUS CYCLE

Press UP and DOWN together for more than 3 s.

DESCRIPTION 

PJEZ* represent a range of electronic microprocessor controllers with LED display developed for the manage-

ment of refrigerating units, display cabinets and showcases.

TECHNICAL SPECIFICATIONS

•  Electronic controllers for low temperature ventilated refrigeration units

•  Power supply 115 or 230Vac

•  Ambient probe NTC

•  Compressor relay 16A

•  Defrost relay 8A

•  Evaporator fan relay 8A

DISPLAY AND FUNCTIONS

During normal operation, the controller displays the temperature read by probe 1. In addition, the display has 

LEDs that indicate the activation of the control functions (see Table 1), while the 3 buttons can be used to 

activate/deactivate some of the functions (see Table 2).

LEDS AND ASSOCIATED FUNCTIONS

icon

function

normal operation

ON

OFF

blink

compressor

on

off

request

ON

fan

on

off

request

ON

defrost

on

off

request

ON

alarm

all

no alarm

-

ON

Tab. 1

TABLE OF FUNCTIONS ACTIVATED BY THE BUTTONS 

button

normal operation

start up

pressing the button alone

pressed together

up 

ON/OFF

more than 3 s: 

toggle ON/OFF

Pressed together start/stop 

continuous cycle

-

down 

defrost

more than 3 s: 

start/stop defrost

for 1 s display 

fi rmware vers. code

set mute

- 1 s.: display/set the setpoint

- more than 3 s: access parameter 

  setting menu (enter password ‘22’)

- mute audible alarm  (buzzer)

-

for 1 s RESET 

current 

EZY set

Tab. 2

SETTING THE SETPOINT (DESIRED TEMPERATURE)

g

n

i

n

a

e

M

t

c

e

ff

E

n

o

it

c

A

p

e

t

S

1

Keep  SET  button pressed for 2 s

After 1 sec currently setpoint value will 

fl ash on display

It’s regulation setpoint 

currently active

2

Press UP  or DOWN  buttons

Setpoint value will chang

3

Press SET  button

Controller will visualize temperature 

read by probes again

Setpoint is modifi ed and 

saved

Tab. 3

ACCESSING AND SETTING THE PARAMETERS

g

n

i

n

a

e

M

t

c

e

ff

E

n

o

it

c

A

p

e

t

S

1

Keep  SET  button pressed 

for 3 s

After 3 sec display will visualize “ PS”

Password is requested

2

Press SET  button again

Display will visualize “ 0” blinking

3

Press UP  or DOWN  button Visualized value on display will change

22”

4

Press SET  button

After 5 sec the fi rst parameter, “ /5”, will be 

visualized on display

It’s the name of the fi rst 

parameter

5

Press UP  or DOWN  button Parameter list will be scrolled on display 

(refer to Table of parameters)

Select desired parameter

6

Press SET  button

Display will visualize value of the selected 

parameter

It’s the currently parameter 

value

7

Press UP  or DOWN  button Parameter value visualized on display will 

change

Set desired value

8

Press SET  button

Display will visualize parameter name 

again

Attention : parameters 

updating is not yet active

9

Repeat steps  5, 6, 7  and  8 

for all desired parameters

10 Keep  SET  button 

pressed for 5 s

Controller will visualize temperature read 

by probes again

Attention:  now parame-

ters updating will be active 

Tab. 4

Insert password “

Set desired value

start up

PJEZ* easy 

electronic controller

SWITCHING THE DEVICE ON/OFF

Press UP for more than 3 s. The control and defrost algorithms are now disabled and the instrument displays the 

message “OFF” alternating with the temperature read by the set probe. 

MANUAL DEFROST

Press DOWN  for more than 3 s (the defrost starts only if the temperature conditions are valid).

CONTINUOUS CYCLE

Press UP and DOWN together for more than 3 s.

DESCRIPTION 

PJEZ* represent a range of electronic microprocessor controllers with LED display developed for the manage-

ment of refrigerating units, display cabinets and showcases.

TECHNICAL SPECIFICATIONS

•  Electronic controllers for low temperature ventilated refrigeration units

•  Power supply 115 or 230Vac

•  Ambient probe NTC

•  Compressor relay 16A

•  Defrost relay 8A

•  Evaporator fan relay 8A

DISPLAY AND FUNCTIONS

During normal operation, the controller displays the temperature read by probe 1. In addition, the display has 

LEDs that indicate the activation of the control functions (see Table 1), while the 3 buttons can be used to 

activate/deactivate some of the functions (see Table 2).

LEDS AND ASSOCIATED FUNCTIONS

icon

function

normal operation

ON

OFF

blink

compressor

on

off

request

ON

fan

on

off

request

ON

defrost

on

off

request

ON

alarm

all

no alarm

-

ON

Tab. 1

TABLE OF FUNCTIONS ACTIVATED BY THE BUTTONS 

button

normal operation

start up

pressing the button alone

pressed together

up 

ON/OFF

more than 3 s: 

toggle ON/OFF

Pressed together start/stop 

continuous cycle

-

down 

defrost

more than 3 s: 

start/stop defrost

for 1 s display 

fi rmware vers. code

set mute

- 1 s.: display/set the setpoint

- more than 3 s: access parameter 

  setting menu (enter password ‘22’)

- mute audible alarm  (buzzer)

-

for 1 s RESET 

current 

EZY set

Tab. 2

SETTING THE SETPOINT (DESIRED TEMPERATURE)

g

n

i

n

a

e

M

t

c

e

ff

E

n

o

it

c

A

p

e

t

S

1

Keep  SET  button pressed for 2 s

After 1 sec currently setpoint value will 

fl ash on display

It’s regulation setpoint 

currently active

2

Press UP  or DOWN  buttons

Setpoint value will chang

3

Press SET  button

Controller will visualize temperature 

read by probes again

Setpoint is modifi ed and 

saved

Tab. 3

ACCESSING AND SETTING THE PARAMETERS

g

n

i

n

a

e

M

t

c

e

ff

E

n

o

it

c

A

p

e

t

S

1

Keep  SET  button pressed 

for 3 s

After 3 sec display will visualize “ PS”

Password is requested

2

Press SET  button again

Display will visualize “ 0” blinking

3

Press UP  or DOWN  button Visualized value on display will change

22”

4

Press SET  button

After 5 sec the fi rst parameter, “ /5”, will be 

visualized on display

It’s the name of the fi rst 

parameter

5

Press UP  or DOWN  button Parameter list will be scrolled on display 

(refer to Table of parameters)

Select desired parameter

6

Press SET  button

Display will visualize value of the selected 

parameter

It’s the currently parameter 

value

7

Press UP  or DOWN  button Parameter value visualized on display will 

change

Set desired value

8

Press SET  button

Display will visualize parameter name 

again

Attention : parameters 

updating is not yet active

9

Repeat steps  5, 6, 7  and  8 

for all desired parameters

10 Keep  SET  button 

pressed for 5 s

Controller will visualize temperature read 

by probes again

Attention:  now parame-

ters updating will be active 

Tab. 4

Insert password “

Set desired value

start up

PJEZ* easy 

electronic controller

SWITCHING THE DEVICE ON/OFF

Press UP for more than 3 s. The control and defrost algorithms are now disabled and the instrument displays the 

message “OFF” alternating with the temperature read by the set probe. 

MANUAL DEFROST

Press DOWN  for more than 3 s (the defrost starts only if the temperature conditions are valid).

CONTINUOUS CYCLE

Press UP and DOWN together for more than 3 s.

DESCRIPTION 

PJEZ* represent a range of electronic microprocessor controllers with LED display developed for the manage-

ment of refrigerating units, display cabinets and showcases.

TECHNICAL SPECIFICATIONS

•  Electronic controllers for low temperature ventilated refrigeration units

•  Power supply 115 or 230Vac

•  Ambient probe NTC

•  Compressor relay 16A

•  Defrost relay 8A

•  Evaporator fan relay 8A

DISPLAY AND FUNCTIONS

During normal operation, the controller displays the temperature read by probe 1. In addition, the display has 

LEDs that indicate the activation of the control functions (see Table 1), while the 3 buttons can be used to 

activate/deactivate some of the functions (see Table 2).

LEDS AND ASSOCIATED FUNCTIONS

icon

function

normal operation

ON

OFF

blink

compressor

on

off

request

ON

fan

on

off

request

ON

defrost

on

off

request

ON

alarm

all

no alarm

-

ON

Tab. 1

TABLE OF FUNCTIONS ACTIVATED BY THE BUTTONS 

button

normal operation

start up

pressing the button alone

pressed together

up 

ON/OFF

more than 3 s: 

toggle ON/OFF

Pressed together start/stop 

continuous cycle

-

down 

defrost

more than 3 s: 

start/stop defrost

for 1 s display 

fi rmware vers. code

set mute

- 1 s.: display/set the setpoint

- more than 3 s: access parameter 

  setting menu (enter password ‘22’)

- mute audible alarm  (buzzer)

-

for 1 s RESET 

current 

EZY set

Tab. 2

SETTING THE SETPOINT (DESIRED TEMPERATURE)

g

n

i

n

a

e

M

t

c

e

ff

E

n

o

it

c

A

p

e

t

S

1

Keep  SET  button pressed for 2 s

After 1 sec currently setpoint value will 

fl ash on display

It’s regulation setpoint 

currently active

2

Press UP  or DOWN  buttons

Setpoint value will chang

3

Press SET  button

Controller will visualize temperature 

read by probes again

Setpoint is modifi ed and 

saved

Tab. 3

ACCESSING AND SETTING THE PARAMETERS

g

n

i

n

a

e

M

t

c

e

ff

E

n

o

it

c

A

p

e

t

S

1

Keep  SET  button pressed 

for 3 s

After 3 sec display will visualize “ PS”

Password is requested

2

Press SET  button again

Display will visualize “ 0” blinking

3

Press UP  or DOWN  button Visualized value on display will change

22”

4

Press SET  button

After 5 sec the fi rst parameter, “ /5”, will be 

visualized on display

It’s the name of the fi rst 

parameter

5

Press UP  or DOWN  button Parameter list will be scrolled on display 

(refer to Table of parameters)

Select desired parameter

6

Press SET  button

Display will visualize value of the selected 

parameter

It’s the currently parameter 

value

7

Press UP  or DOWN  button Parameter value visualized on display will 

change

Set desired value

8

Press SET  button

Display will visualize parameter name 

again

Attention : parameters 

updating is not yet active

9

Repeat steps  5, 6, 7  and  8 

for all desired parameters

10 Keep  SET  button 

pressed for 5 s

Controller will visualize temperature read 

by probes again

Attention:  now parame-

ters updating will be active 

Tab. 4

Insert password “

Set desired value

start up

PJEZ* easy 

electronic controller

SWITCHING THE DEVICE ON/OFF

Press UP for more than 3 s. The control and defrost algorithms are now disabled and the instrument displays the 

message “OFF” alternating with the temperature read by the set probe. 

MANUAL DEFROST

Press DOWN  for more than 3 s (the defrost starts only if the temperature conditions are valid).

CONTINUOUS CYCLE

Press UP and DOWN together for more than 3 s.

SET

Содержание OASIS-30

Страница 1: ...Office 1 888 685 9959 Tech Support 1 888 685 8324 www mtlcool com 7880 Boul Industriel Chambly Quebec J3L 4X3 1310836 07 Mar 02 2016 OASIS Open Air Cooler User Manual OASIS 30 OASIS 36 Models...

Страница 2: ......

Страница 3: ...REFRIGERANT DISPOSAL 2 HOW TO CONNECT ELECTRICITY 2 SAFETY PRECAUTIONS 2 MAINTENANCE 3 INSTALLATION 4 INSTALLATION REQUIREMENTS 4 ELECTRICAL REQUIREMENTS 4 ADDING REPLACING ARTWORK IN THE HEADER 4 AP...

Страница 4: ......

Страница 5: ...age If possible please take pictures of the damage PALLET REMOVAL The Oasis Grab N Go cooler is secured to the pallet beneath it Please follow the instructions below to safely detach the cooler from t...

Страница 6: ...d prong from the power cord supplied The cord should be secured behind the refrigerator and not left exposed or dangling to prevent accidental injury SAFETY PRECAUTIONS Keep the unit upright during tr...

Страница 7: ...unless specified otherwise which has a voltage rating that matches the rating plate When removing the refrigerator from the wall be careful not to roll over or damage the power cord MAINTENANCE The co...

Страница 8: ...5 5 4 4 3 2 40 10 8 8 6 6 5 5 4 4 3 2 2 45 10 8 6 6 6 5 4 4 3 3 2 1 50 10 8 6 6 5 4 4 3 3 2 1 1 INSTALLATION INSTALLATION REQUIREMENTS 1 DO NOT place the cooler in a location with air drafts that coul...

Страница 9: ...e along the edges of the plastic sheets secure the header frame with the three screws APPLYING DECAL GRAPHICS ON GLASS 1 Wet the glass and the sticky side of the graphics with soapy water a small amou...

Страница 10: ...and are strictly the responsibility of the purchaser The term original purchaser as used herein shall be deemed to mean that person firm association of corporation for whom the Refrigeration Unit ref...

Страница 11: ...r use of products not approved by warrantor Replacement parts or repair labour costs for units operated outside the U S or Canada Repairs to parts or systems resulting from unauthorized modifications...

Страница 12: ...buttons the value will be displayed and can be modified and stored If idle for 10 seconds the unit interior temperature will be displayed FACTORY SETTINGS SF 102 Parameter Function Set Range Factory S...

Страница 13: ...dating will be active Tab 4 Insert password Set desired value start up PJEZ easy electronic controller SWITCHING THE DEVICE ON OFF Press UP for more than 3 s The control and defrost algorithms are now...

Отзывы: