3.4 Spa Heat Pumps Plumbing 

Location: Connect the unit in the pool pump discharge (return) line downstream of all filter 
and pool pumps, and upstream of any chlorinators, ozonators or chemical pumps.

Standard model have slip glue fittings which accept  40mm NB PVC pipe for connection to 
the pool or spa filtration piping. By using a 50 NB to 40NB you can plumb 50NB PVC piping 
straight into the unit. 

Give serious consideration to adding a quick coupler fitting at the unit inlet and outlet to allow 
easy draining of unit for winterizing and to provide easier access should servicing be 
required. 

Condensation: Since the Heat pump cools down the air about 4 -5 , water may condense on 
the fins of the horseshoe shaped evaporator. If the relative humidity is very high, this could 
be as much as several litres an hour. The water will run down the fins into the basepan and 
drain out through the barbed plastic condensation drain fitting on the side of the basepan. 
This fitting is designed to accept 3/4" clear vinyl tubing which can be pushed on by hand and 
run to a suitable drain. It is easy to mistake the condensation for a water leak inside the unit. 

NB: A quick way to verify that the water is condensation is to shut off the unit  and keep the 
pool pump running. If the water stops running out of the basepan, it is condensation. AN 
EVEN QUICKER WAY IS to TEST THE DRAIN WATER FOR CHLORINE - if the is no chlorine 
present, then it's condensation. 

3.INSTALLATION AND CONNECTION

To  Spa

From pump

PVC COUPLER
RECOMMENDED(Provided)

The Spa Heat Pumps exclusive rated flow titanium heat exchanger requires no special 
plumbing arrangements except bypass(please set the flow rate according to the nameplate). 
The water pressure drop is less than 10kPa  at max. Flow rate. Since there is no residual 
heat or flame Temperatures, The unit does not need copper heat sink piping. PVC  pipe can 
be run straight into the unit.

8

Horizontal vision

Содержание C13b

Страница 1: ...SWIMMING POOL HEAT PUMP UNIT Installation Instruction Manual ...

Страница 2: ......

Страница 3: ... Unit 4 Usage and Operation 4 1 4 2 4 3 5 Maintenance and Inspection 5 1 5 2 Malfunction table 6 Appendix Spa Heat Pumps Location Spa Heat Pumps Plumbing Spa Heat Pumps Electrical Wiring Function of wire controller The controller usage Parameter table Maintenance 6 4 Cable specification 6 1 Connection of PCB Illustration 6 2 Connections Explanation 6 3 Caution Warning 6 5 Explosive view of the uni...

Страница 4: ...t comprises an efficient rotary scroll compressor and a low noise fan motor which guarantees its quiet operation 4 Advanced controlling The unit includes micro computer controlling allowing all operation parameters to be set Operation status can be displayed on the wire controller 1 In order to provide our customers with quality reliability and versatility this product has been made to strict prod...

Страница 5: ...Quantity Compressor Fan Quantity Fan Power Input Fan Rotate Speed Fan Direction Noise Water Connection Water Flow Volume Water Pressure Drop max Unit Net Dimensions L W H Unit Shipping Dimensions L W H Net Weight Shipping Weight Model kW BTU h kW A W RPM dB A inch 3 m h kPa mm mm kg kg Oasis C17b 17 5 60000 3 5 15 9 230V 50Hz 1 Scroll 1 120 850 Horizontal 54 1 5 6 0 10 1120 470 850 1200 480 1010 1...

Страница 6: ...Scroll 2 120 2 850 Horizontal 56 1 5 9 0 12 1120 470 1240 1200 490 1380 130 140 REFRIGERANT R410A Unit Heating Capacity Heating Power Input Running Current Power Supply Compressor Quantity Compressor Fan Quantity Fan Power Input Fan Rotate Speed Fan Direction Noise Water Connection Water Flow Volume Water Pressure Drop max Unit Net Dimensions L W H Unit Shipping Dimensions L W H Net Weight Shippin...

Страница 7: ...sis C25Tb Water Inlet Water Outlet A E D C B TYPE B A C D SIZE E unit mm Oasis C8b C13b H13b 650 1000 700 420 400 255 101 Horizontal vision Vertical vision Oasis C17b H17b 850 1120 720 470 440 400 97 TYPE B A C D SIZE 1240 1120 720 470 440 475 95 E Unit mm Oasis C21b C25b C25Tb A E D C B Horizontal vision Water Inlet Water Outlet Vertical vision F G F G F G G F ...

Страница 8: ...Oasis C35T Vb Oasis C50T Vb Models EH9b 1002 658 430 455 630 Water Inlet Water Outlet Horizontal vision Vertical vision 1130 1490 1464 480 735 Water inlet Water outlet Drainage Horizontal vision Vertical vision 255 102 5 88 120 ...

Страница 9: ...s or the installer 3 1 Installation illustration 3 INSTALLATION AND CONNECTION Chlorinator cell Water outlet Pool Valve Water supply Water inlet Water pump Sand filter or other type filter By pass valve Special Notes If the heat pump is used to heat the spa then the parts will not strictly like what shown as above please make sure the water loop is clear and enough ...

Страница 10: ...DO NOT place the unit to shrubs which can block air inlet These locations deny the unit of a continuous source of fresh air which reduces it efficiency and may prevent adequate heat delivery 3 2 Spa Heat Pumps Location 3 3 How Close To Your spa 3 INSTALLATION AND CONNECTION Air inlet Air outlet 2500m m 700mm 300mm 500mm 700mm Normally the longer the distance from the spa the greater the heat loss ...

Страница 11: ...an and drain out through the barbed plastic condensation drain fitting on the side of the basepan This fitting is designed to accept 3 4 clear vinyl tubing which can be pushed on by hand and run to a suitable drain It is easy to mistake the condensation for a water leak inside the unit NB Aquick way to verify that the water is condensation is to shut off the unit and keep the pool pump running If ...

Страница 12: ...me type used in all gas pool heaters and is factory adjusted for normal pool installations If the pool water level is more than a few feet above or below the thermostat knob of the unit your dealer may need to adjust it at initial startup Time Delay The unit is equipped with a 3 minute built in solid state restart delay included to protect control circuit components and to eliminate restart cyclin...

Страница 13: ...ion NO Symbol Name Function On off Mode Up Press this button can start up or shut down the unit cancel the current operation or back to the upper interface Press this button can switch modes or save parameter setting Press this button can move up or increase parameter value Press this button can move down or decrease the parameter value Down 5 Press this button can set the clock and timer ...

Страница 14: ...ain display area gives the inlet water temperature measured value Outlet water It is showed when the AUX display area gives the outlet water temperature measured value Minute It is showed when the main display area gives minute value Centigrade It is showed when the main AUX display area gives centigrade value Parameter setting It is showed when the parameter can be setted Lock It is showed when t...

Страница 15: ...pressing Attention The modes switching is useless if the unit you buy is single cold single heat unit For example Press Press Press Press TEMP OUT MODE SET TEMP IN C TEMP OUT MODE SET TEMP OUT MODE SET TEMP OUT MODE SET TEMP OUT MODE SET A TEMP OUT MODE SET TEMP OUT MODE SET MODE SET MODE SET MODE SET MODE SET MODE SET In the off interface press for 0 5s can start up the unit and aux display area ...

Страница 16: ...ing press to increase value or press to decrease value and press to save setting Press can not save setting parameter and back to main interface Attention If there is no operation for 5s system will remember parameter setting and back to the main interface For example In the main interface press or and the current mode target temperature flashes then press to increase the temp value or press to de...

Страница 17: ...Hour minute Flashing TEMP IN C TEMP OUT MODE SET Flashing Press TEMP IN C TEMP OUT MODE SET Press or TEMP IN C TEMP OUT MODE SET Press to save hour value setting TEMP IN C TEMP OUT MODE SET Press or TEMP IN C TEMP OUT MODE SET Press to save minute value setting Flashing Flashing Flashing ...

Страница 18: ...terface press to cancel Attention 1 If there is no operation for 5s system will remember clock setting and back to the main interface 2 By pressing till the off flashing you can set the timer off without timer on TEMP IN C TEMP OUT MODE SET TEMP IN C TEMP OUT MODE SET ON Press for 2 second TEMP IN C TEMP OUT MODE SET Press ON Flashing Flashing TEMP IN C TEMP OUT MODE SET ON Flashing press or TEMP ...

Страница 19: ... OFF TEMP IN C TEMP OUT MODE SET ON OFF TEMP IN C TEMP OUT MODE SET ON OFF Press Press or TEMP IN C TEMP OUT MODE SET ON OFF TEMP IN C TEMP OUT MODE SET Press ON OFF The timer on and off has been set Flashing Flashing Flashing Flashing Flashing Flashing Flashing Flashing 4 USAGE AND OPERATION ...

Страница 20: ...xample TEMP IN C TEMP OUT MODE SET ON OFF The timer on off has been set Press for 2s TEMP IN C TEMP OUT MODE SET ON OFF ON is flashing TEMP IN C TEMP OUT MODE SET OFF The setting of timer on has been cancelled Press TEMP IN C TEMP OUT MODE SET OFF Press for 4s OFF is flashing TEMP IN C TEMP OUT MODE SET The setting of timer off has been cancelled Press 4 USAGE AND OPERATION ...

Страница 21: ...nlocked NOTES When the unit is in alarming state the key lock can be removed automaticly TEMP IN C TEMP OUT MODE SET Hold on Locked TEMP IN C TEMP OUT MODE SET MODE SET 8 Malfunction display There will be malfunction code showing on the controller screen when relative malfunction occurs You can refer to the malfunction table to find out the failure cause and solution For example Water inlet temp S...

Страница 22: ...19 28 28 27 Meaning Heating inlet target temp Adjustable Adjustable Adjustable 4 3 Parameter table Cooling inlet target temp Auto inlet target temp Remark Default 4 USAGE AND OPERATION ...

Страница 23: ... pressure of the refrigerant system should only be serviced by a certified technician Discharge all water in the water pump and water system so that freezing of the water in the pump or water system does not occur You should discharge the water at the bottom of water pump if the unit will not be used for an extended period of time You should check the unit thoroughly and fill the system with water...

Страница 24: ...side antifreezing protection The secondary anti freezing protection Discharge Temp Of system 2 is too high The temp Sensor is brokenor short circuit The temp Sensor is brokenor short circuit The temp Sensor is brokenor short circuit The temp Sensor is brokenor short circuit The temp Sensor is brokenor short circuit The temp Sensor is brokenor short circuit The temp Sensor is brokenor short circuit...

Страница 25: ...4 25 26 27 28 29 30 31 32 Electric heater overload protection input Compressor 1 overload protection input Water flow switchprotection input Compressor 2 overload protection input System protection input Emergency switch input 33 34 35 17 18 19 36 37 Water input temperatureinput Water output temperatureoutput System 1 fan coil temperature input System 2 fan coil temperature input Ambient temperatu...

Страница 26: ...be handled separately from domestic waste must be taken to a recycling centre for electric and electronic devices or handed back to the dealer when purchasing an equivalent appliance 6 Directive 2002 95 EC RoHs This product is compliant with directive 2002 95 EC RoHs concerning restrictions for the use of harmful substances in electric and electronic devices 7 The unit CANNOT be installed near the...

Страница 27: ...n 0 1 sec 30mA less than 0 1 sec 13 25A 25 30A 30 40A 40 55A 55 70A Phase line 2 3 1 5mm 2 3 4mm 2 3 6mm 2 3 10mm 2 3 16mm 2 3 25mm 2 1 5mm 2 1 5mm 2 4mm 2 6mm 2 10mm 2 16mm MCB 20A 40A 40A 63A 80A 100A Creepage protector Signal line 2 n 0 5mm Nameplate maximum current Earth line No more than 13A 30mA less than 0 1 sec 30mA less than 0 1 sec 30mA less than 0 1 sec 30mA less than 0 1 sec 30mA less ...

Страница 28: ...anel 50 connector PVC elbow wire fixer Thermostatic expansion valve wire fixer water proof cover wire controller pressure meter chassis filter Drainage pipe fittings compressor 4 way valve Note Code 3512 2158 4000 3901 2000 3909 3512 2152 3512 2175 3500 2701 2000 3501 3404 3301 3508 2178 2000 3510 3512 2126 3512 2155 2000 3115 2000 3619 95005 310114 32008 210009 2000 3603 3512 2121 20000 140003 Pa...

Страница 29: ...r capacitor soft start PCB plastic cover pressure switch 4 way valve needle valve pressure switch chassis wire controller water proof cover Note Code 2001 1116 32012 210080 3500 2701 32008 220040 3404 3301 32008 210069 32012 210077 32012 210079 32012 210075 32012 210076 32012 220031 3400 2203 2000 3505 95005 310114 20000 360005 32008 210101 4000 3901 Part name Compressor protect net fan blade fron...

Страница 30: ...08 2178 2000 3502 3512 2126 3512 2155 2000 3116 2000 3619 95005 310114 32008 210009 2000 3603 3512 2121 20000 140003 Part name female branch tee condenser water flow switch heat exchanger right panel 50 connector PVC elbow wire fixer Thermostatic expansion valve wire fixer water proof cover wire controller pressure meter chassis filter Drainage pipe fittings compressor 4 way valve AC contactor Par...

Страница 31: ...at exchanger right panel 50 connector PVC elbow wire fixer wire fixer water proof cover wire controller chassis filter Drainage pipe fittings compressor AC contactor Note Code 3512 2158 4000 3901 2000 3909 3512 2152 3512 2175 3500 2701 2000 3501 3404 3301 3508 2178 2000 3502 3512 2126 3512 2155 2000 3116 2000 3619 95005 310114 32008 210009 2000 3603 3512 2121 Part name front right panel 5 Terminal...

Страница 32: ...ndle right panel chassis wire fixer compressor wire fixer wire controller water proof cover 4 way valve pressure meter thermostatic expansion valve needle valve pressure switch filter Note Code 2000 3602 3509 2156 3512 2152 3509 2194 2000 3909 3500 2701 3400 2203 2000 3510 2000 3501 3404 3301 3509 2164 3509 2117 2000 3524 2000 3619 20000 360007 5512 2123 3509 2155 2000 3920 95005 310114 Part name ...

Страница 33: ...er 3 terminal Gas Liquid Separators handle right panel chassis wire fixer compressor wire fixer wire controller water proof cover needle valve pressure switch filter Note Code 2000 3602 3509 2156 3512 2152 3509 2194 2000 3909 3500 2701 3400 2203 2000 3510 2000 3501 3404 3301 3509 2164 3509 2117 2000 3524 2000 3619 20000 360007 5512 2123 3509 2155 2000 3920 Part name pressure switch front right pan...

Страница 34: ...e fixer wire fixer filter drainage pipe fittings pressure switch 4 way valve needle valve pressure switch Thermostatic expansion valve wire controller water prrof cover Gas Liquid Separators Code 32018 210012 3512 2152 20000 110112 3518 2155 3518 2173 2000 3676 3500 2701 2000 3619 3404 3301 3536 2120 2000 3933 3518 2152 3404 3301 3536 2120 3518 2152 2000 3909 2000 3501 2000 3524 95005 310114 32018...

Страница 35: ...essure gage 3 way valve right panel water proof sheath water proof sheath filter 4 way valve pressure gage needle valve TX valve pressure switch LCD wire controller water proof box Code 2000 1440 32018 210012 3518 2155 2000 3920 3512 2152 3518 2173 20000 110119 3500 2701 3536 2120 3404 3301 2000 3676 2000 3619 2000 3933 2000 3909 3518 2152 2000 3501 2000 3524 32018 210025 3518 2153 95005 310114 20...

Страница 36: ...re gage 3 way valve right panel water proof sheath water proof sheath filter 4 way valve pressure switch needle valve TX valve pressure switch LCD wire controller water proof box Code 2000 1440 32018 210012 3518 2155 3512 2152 3518 2173 2000 1135 3500 2701 3536 2120 3404 3301 2000 3619 2000 3902 2000 3909 3518 2152 2000 3501 32018 210025 3518 2153 95005 310114 2000 3653 35018 120003 Part name liqu...

Страница 37: ...tor compressor 4 way valve left condenser Part Code 32006 210047 35005 210012 35005 210017 35005 210002 35005 210006 4000 7707 35005 210010 20000 220068 95005 310156 95005 310114 20000 360023 2001 3602 2000 3619 2000 3653 2000 3680 2000 3902 2000 3909 2000 1406 2002 1417 2000 3603 2000 1404 2000 3602 2005 1360 2001 1359 20000 360005 Part Name electrical box cover scale board left panel left post l...

Страница 38: ...6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 NO 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 PartName pipe connector PVC 3 way valve PVC elbow PVC pipe PVC fixed plate PVC adapter bonnet PVC 3 way valve front down panel front beam right post front up panel right condenser chassis right panel right beam water collector pressure gage support beam fan motor he...

Страница 39: ......

Страница 40: ...Code 20120807 0001 Code 20120807 0001 ...

Отзывы: