Work Order #
Orifice # (Main)
BTU Rating
Orifice # (OTHER)
Serial #
Leak Test
Model #
Burn Test
Air Shutter
Gas Type
Inspector:
COM0595B
X
Follow steps 1 – 5 shown above.
THE CONVERSION SHALL BE CARRIED OUT BY
A MANUFACTURER’S AUTHORIZED
REPRESENTATIVE, IN ACCORDANCE WITH
THE REQUIREMENTS OF THE
MANUFACTURER, PROVENCIAL OR
TERRITORIAL AUTHORITIES HAVING
JURISDICTION AND IN ACCORDANCE WITH
THE REQUIREMENTS OF THE
CAN/CGA-B149.1 OR CAN/CGA-B149.2
INSTALLATION CODES.
After conversion follow Operating Instructions
found on Page 11.
Casual Fireside Fire Pits Are
Suitable For Installation from
0 - 4,500 ft. Without Modification.
Carefully detach the flex line connector hose attached to the orifice holder (Figure # 1) and unscrew the orifice holder from
the burner pipe (Figures #1 and # 2).
#45
LP 48,000 / NG 52,000
If you are converting from propane (LP) gas to natural gas, install the air shutter sleeve so that the air intake holes are
closed (Figure #2). For Propane gas, remove the air shutter so that the air intake holes are open (Figure #1).
After the
unit is assembled for use, it is requires a "leak check" test on all connections are before placing the unit in
operation.
Page 12
FIGURE 2
CONVERTING YOUR FIRE PIT TO A DIFFERENT GAS TYPE
1.
MAKE SURE THAT THE GAS SUPPLY TO THE FIRE PIT (AND ANY NEARBY ELECTRICAL
SOURCES/APPLIANCES) ARE SHUT OFF.
2.
#29 / COM0595BCK
3.
Remove the orifice from the holder (Figure # 2 ) and replace it with the proper sized one for your gas requirement.
Propane requires the smaller orifice.
LP - NAT
MANUFACTURER’S USE ONLY - QUALITY CHECK
Date:
4.
5.
IT IS NECESSARY TO ATTACH THE LABEL OR RATING PLATE INCLUDED WITH THE CONVERSION KIT TO
CLEARLY INDICATE THE FIELD CONVERSION.
FIGURE 1
After The Unit Is Converted, it Must Be Tested
to Verify the Inlet and Manifold pressures are
as specified on Page 3. Additionally, the
authorized representative must verify that the
input rate of the converted appliance match the
rate listed below.
Orifice
Orifice Holder
Burner
When converting to natural gas, the air shutter
sleeve MUST be installed over the burner pipe.
Flex Line
Connector Hose
Burner
Orifice Holder
Flex Line
Connector Hose
Orifice
Air Intake hole open for LP Gas