background image

 

 

Press the ON/OFF button for 5~8 seconds to turn the unit on. 

 

The UPS should charge the battery for at least 6 hours to ensure sufficient runtime. 

 

Press ON/OFF button in 5~8 seconds. The alarm sounds to confirms that the UPS is on and provide 
power to outlets. 

 

3.  Cold start the UPS 

 

Use cold start feature to supply power to connected equipment from the UPS batteries when there is no 
utility power.    To turn on the UPS see step 2 above.   

 
4.  Connect and install management software 

 

UPS is provided with management software for unattended system shutdown, UPS monitoring, and UPS 
configuration. 

7. Audible Indicators and Status Icons 

If the UPS… 

Possible cause... 

In Battery Mode: Alarm sounds every 2 seconds.   
(alarm for 0.5 second and stops for 1.5 seconds) 

UPS is running on battery. You should consider saving any work in 
progress. 

a.  Low Battery: alarm sounds every 0.2 seconds 
b.  Low Battery power off: Continuous alarm 

Low battery condition and battery run-time is very low. Promptly save 
any work in progress, exit all open applications, and shut down the 
operating system. 

Continuous tone with 

  flashing. 

UPS is overloaded. 

Continuous tone with 

  illuminated. 

a.  Press ON/OFF button one time to mute the alarm. 
b.  Continuous tone will persist until battery LOW. 

(<11Vdc each battery) 

: Inverter short   

: Inverter over voltage 

: Transformer over temperature 

: DC power output short circuit 

Battery Replacement Alarm: alarms every 4 seconds (alarms 
for 1 second and stops for 3 seconds) 

The battery is near the end of useful life or damaged and should be 
replaced. 

 

8. Specifications 

Model 

NPTU250-GL-N 

NPTU400-GL-N 

Input 

Voltage range 

120V

AC 

Voltage range 

96-144Vac (

±

5Vac) 

Connection 

NEMA5-15P 

Frequency 

60 Hz 

Output 

UPS Capacity (total) 

250VA / 200W 

400VA / 320W 

Rated Voltage 

120V

AC

 

Transfer time 

Typical 2 - 6 ms 

Waveform 

Pure sine wave 

DC 

Power 

Output Voltage 

24V

DC

 

Output Current 

3A (max) 

Physical 

Dimension 
(D x W x H) 

12 x 5.9 x 10.5 inch 

304.8 x 149.9 x 266.7 mm 

Net Weight   

38.6 lb 

17.5 kg 

Packaging 
Dimension 
(D x W x H) 

16.1 x 9.8 x 15.5 inch 

408.9 x 248.92 x 393.7 mm 

Gross Weight 

41.9 lb 

19 kg 

Environm

ent 

Operating     
temperature   

32 - 104 °F (0 - 40 °C) 

Humidity 

Operating Humidity: 5% to 90% 

Noise level 

<40dB, convection cooling 

 
 

 

Отзывы: