30
1.
2.
To mount the system into the rack:
Attach the left and right rack mount rails (A) to the switch, and secure the chassis in the rails
by screwing 2 flat head Phillips screws (D) in the designated points on each side (a total of 4
screws). To tighten the screws, use a torque of 1.5±0.2 Nm.
Attaching the Rails to the Chassis
Install 8 cage nuts (C) in the desired slots of the rack: 4 cage nuts in the non-extractable side
and 4 cage nuts in the extractable side. Note that while each rack U (unit) consists of three
holes, the cage nut should be installed vertically with its ears engaging the top and bottom
holes only.
Installing the Cage Nuts
At least two people are required to safely mount the system in the rack.