To insert a power supply unit:
Make sure the mating connector of the new unit is free of any dirt and/or obstacles.
Insert the power supply unit by sliding it into the opening, until a slight resistance is felt.
Continue pressing the power supply unit until it seats completely. The latch will snap into
place, confirming the proper installation.
Insert the power cord into the supply connector.
Insert the other end of the power cord into an outlet of the correct voltage.
Fans
The system can fully operate if one fan FRU is dysfunctional. Failure of more than one fan is not
supported.
To extract a fan unit:
Grasping the handle with your right hand, push the latch release with your thumb while
pulling the handle outward. As the fan unit unseats, the fan unit status LEDs will turn off.
Remove the fan unit.
Fan Module Latches
To remove or replace a fan unit, gently pull out its black handle while pushing the latch release
with your thumb.
To insert a fan unit:
Make sure the mating connector of the new unit is free of any dirt and/or obstacles.
Do not attempt to insert a power supply unit with a power cord connected to it.
The green power supply unit indicator should light. If it does not, repeat the whole
procedure to extract the power supply unit and re-insert it.
Make sure that the fans have the air flow that matches the model number. An air flow
opposite to the system design will cause the system to operate at a higher (less than
optimal) temperature. For power supply unit air flow direction, refer to