nVent.com
|
16
Parameter
Meaning
Value range
from...factory-set...to
OF.r
Lead compensation resistance
This value is used for compensating the resistance of the probe lead for
resistance sensors and is dependent on the lead length.
For best temperature measurement results, the resistance value of the
probe lead has to be entered here.
If the total resistance at the measurement input (sensor resistance
+ selected value for OF.r) exceeds 320 Ω with Pt100 or 3200 Ω with
Pt1000/KTY2x-6, a measurement error will occur !
0.0 ... 0�0 ... 99.9 in Ω
Un
Unit
for the indicated process value
For settings in °F, the process value will be converted correspondingly.
All other setting, such as for SP, will retain their values.
°C, °F or
no (= no unit)