NGC-UIT2-EX

User Interface Terminal for nVent RAYCHEM NGC Systems 

Installation Instructions

NGC-UIT2-EX 

installed in a panel

DESCRIPTION

The nVent RAYCHEM NGC-UIT2-EX is a panel mounted display used 

in conjunction with other RAYCHEM control and monitoring devices. 

The NGC-UIT2-EX is rated IP 65 (Type 4X), and can be mounted 

indoors or outdoors. The NGC-UIT2-EX kit includes all hardware 

required for mounting in a suitable electrical panel. Additional 

materials are required for electrical connections and are detailed 

below. These instructions describe how to mount the NGC-UIT2-EX 

in an electrical panel and are intended only for qualified personnel 

experienced in panel construction.

TOOLS REQUIRED

•  Masking tape 

•  #16 (3/16) drill bit

•  Metal file
•  In-line torque wrench with 8 mm (5/16 in) socket

•  Jig saw (recommend using carbon steel blade with 24TPI)

ADDITIONAL MATERIALS (TO BE ORDERED SEPARATELY)

Qty Description

Manufacturer

Manufacturer  

Part Number

2

9 pin D-SUB to 10 pin  

terminal block PCB

Phoenix Contacts 2315162

2

Serial communication cable L-COM

CSMN9MF-xx 

xx = Length in ft

3

Alarm relays – 12 Vdc, 12 

A, SPDT

TE Connectivity

RTB14012F

3

Alarm relay sockets

TE Connectivity

RT78724

1

Push to test alarm light 120 or 230 Vac

Note: Equivalent parts may be used.

CERTIFICATIONS / APPROVALS 

•  NEMA 4X, IP65 protection on front panel

•  FCC Part15 Subpart B/ICES 003 Class A

•  ETL 4000758

Conforms to ANSI/UL Std. 60950-1 2

nd

 Ed.; CAN/CSA Std. C22.2 No. 

60950-1-07; ANSI/ISA Std. 12.12.01-2013 & CAN/CSA Std. C22.2 No. 

213-M1987 (R2013)

•  CE marking

  Low Voltage Directive (2006/95/EC) EN 60950-1

  EMC Directive (2004/108/EC) EN 55022, EN 55024

  ATEX Directive (94/9/EC) EN 60079-0, EN 60079-15

  Certificate Number: ITS15ATEX18221X

•  IECEx

  Certificate Number: IECEx ETL 15.0015X

ITS15ATEX18221X

IECEx ETL 15.0015X

|| 3G

Ex nA IIC T5 Gc

Class | Div.2 Groups A,B,C,D T5

–40°C 

 Ta 

 60°C

General

Area of Use

Ordinary (nonhazardous) and Hazardous locations, indoors or outdoors (IP65, Type 4X)

Supply Voltage

9 – 30 Vdc, 15 W Max, AWG 18-22 (0.9 mm

2

 - 0.52 mm

2

)

Operating Temperature

–40°C to 60°C (–40°F to 140°F)

Min. Storage Temperature

–40°C to 80°C (–40°F to 176°F)

Dimensions

279 mm W X 229 mm H X 70 mm D (11 in. W X 9 in. H X 2.75 in. D)

Humidity Range

10 to 90% Non-Condensing

Alarm Outputs

Transistor open collector outputs Three open collector outputs, with a range of 5 – 30 Vdc with a max. sink current of 500 mA
Use to drive external relays

Relays may be assigned for alarm outputs.

LCD Display 

Display

LCD is a 8.4 in. XGA, color TFT transflective device with integral LED backlight

Touch Screen

5-wire resistive touch screen interface for user entry

4000758

RoHS

Содержание Raychem NGC-UIT2-EX

Страница 1: ...t alarm light 120 or 230 Vac Note Equivalent parts may be used CERTIFICATIONS APPROVALS NEMA 4X IP65 protection on front panel FCC Part15 Subpart B ICES 003 Class A ETL 4000758 Conforms to ANSI UL Std...

Страница 2: ...it will be exposed to strong magnetic fields or excessive vibration Conditions of Safe Use This equipment must be installed in a hazardous location classified cabinet or panel rated as follows Intern...

Страница 3: ...izontal surface 5 Mount the user interface assembly onto the panel door Place the NGC UIT2 EX assembly in position the twelve studs go through the twelve holes on the NGC UIT2 EX assembly mounting pla...

Страница 4: ...n 88 39 mm 3 480 in 4 8 3 m m 0 1 9 0 i n X 1 2 71 48 mm 2 814 in 71 48 mm 2 814 in 71 48 mm 2 814 in Panel Cut Out Area Top of Display Drawing NOT TO SCALE Drawing NOT TO SCALE 11 1 mm 0 437 in 88 39...

Страница 5: ...5 2 Debug Port not used Ethernet USB device port not used Open Collector Outputs RS 485 1 Side view RS 232 RS 485 1 Termination RS 485 2 Termination Side view RS 485 not used CAN not used Power Reset...

Страница 6: ...Vdc we have used this voltage to also power the NGC UIT2 EX As a result the recommend alarm relays and lights detailed in the Additional Materials are rated for 12 Vdc Provision shall be made externa...

Страница 7: ...l the two 9 pin D SUB to 10 pin terminal block on a DIN rail inside the panel enclosure Note These should be placed were the Serial cable from the bottom of the NGC UIT2 EX mounted on the panel door c...

Страница 8: ...Comments Pull down As shipped default RS 485 network signal is forced to a determinate state when idle RS 485 network signal is not forced to a determinate state when idle One device typically this N...

Отзывы: