Wiring for Com 1 & Com 2 must be terminated on a panel 

mounted terminal block. No ground wires should be 

terminated on terminals 9 & 11. Terminate Com shields at 

the panel mounted field terminal block chassis ground.

Wiring for Com 1 & Com 2 must be terminated on a panel 

mounted terminal block. No ground wires should be 

terminated on terminals 10 & 12. Terminate Com shields and 

120 Ω termination resistors (included) at the panel mounted 

field terminal block as shown.

1

2

1

2

Each NGC-40-BRIDGE mounts on a DIN 35 rail. 
MOUNTING: Insert the rear bottom of the module into the DIN rail, then push up 

and inwards to engage the clip.

REMOVAL: Push the module upwards to 

disengage the clip, then rotate the module 

toward you.

Mounting the NGC-40-BRIDGE

RS-485 Connection Diagrams – North American Installation Technique

COM 1&2 Connections (In)

COM 1&2 Connections (Out) and  

RS-485 Termination Resistor 

Содержание Raychem NGC-40-BRIDGE

Страница 1: ...D 1 NGC 40 BRIDGE serial cable TTC 10332 005 This component is an electrical device that must be installed correctly to ensure proper operation and to prevent shock or fire For technical support call...

Страница 2: ...50 ft maximum Data rate 9600 19 2K 38 4K 57 6K 115 2K baud Data bits 7 or 8 Parity None even odd Stop bits 0 1 2 Tx delay 0 5 sec Protocol Modbus RTU or ASCII Connection terminals RJ 11 CAN NETWORKING...

Страница 3: ...s CAN network activity Off No link detected Green Link OK receive data packets Yellow Transmit data packets Red flashing Network error COM Indicates COM1 2 RS 485 activity Off No activity Green flashi...

Страница 4: ...e terminated on terminals 9 11 Terminate Com shields at the panel mounted field terminal block chassis ground Wiring for Com 1 Com 2 must be terminated on a panel mounted terminal block No ground wire...

Страница 5: ...device RESET NGC 40 BRIDGE MODULE COM 1 Out COM 1 Out 2 2 6 6 10 10 COM 2 Out COM 2 Out 4 4 8 8 12 12 120 ohm termination resistor 120 ohm termination resistor 120 ohm termination resistor 120 ohm ter...

Страница 6: ...11 11 Earth grounding bar located at the bridge module Earth grounding bar located at the bridge module Panel Terminal Block Panel Terminal Block Panel Panel To next RMM2 To next RMM2 Field Field Whe...

Страница 7: ...n Module CAN 24 Vdc Primary Supply 24 Vdc Primary Supply 24 Vdc Power supply shall have a means for disconnect from line voltage Power supply shall have a means for disconnect from line voltage Redund...

Страница 8: ...emperature is outside this range a space heater and or cooling fan will be required in the panel 2 Determine locations for the NGC 40 BRIDGE assembly in the electrical panel The NGC 40 BRIDGE should b...

Страница 9: ...23 IN IN OUT OUT CAN 24 Vdc HTC HTC3 or I O Module 22 IN IN OUT OUT CAN 24 Vdc HTC HTC3 or I O Module 21 20 Modules per Power Supply 20 Modules per Power Supply 100 240 Vac In 100 240 Vac In 20 Modul...

Страница 10: ...426 3167 cn thermal info nvent com Latin America Tel 1 713 868 4800 Fax 1 713 868 2333 thermal info nvent com 2018 nVent All nVent marks and logos are owned or licensed by nVent Services GmbH or its a...