General Information
1
2 | nVent.com
Space and Surface Heating), govern the installation of
electrical heat-tracing systems. All heat-tracing-system
installations must be in compliance with these and any
other applicable national or local codes.
1.4 Warranty and Approvals
RAYCHEM heating cables and components are
approved for use in hazardous and nonhazardous
locations. Refer to the specific product data sheets for
details.
1.5 General Installation Notes
These notes are provided to assist the installer
throughout the installation process and should be
reviewed before the installation begins.
• Read all instruction sheets to familiarize yourself with
the products.
• Select the heating cable type and rating in accordance
with the Industrial Product Selection and Design
Guide (nVent literature #H56550), or TraceCalc Pro
software, or the website design software.
• Ensure all pipes, tanks, etc., have been released
by the client for tracing prior to installation of the
heating cables.
• Typically, heating cables are installed at the 4 and
8 o’clock positions on a pipe.
• All heat-traced pipes, tanks, vessels, and equipment
must be thermally insulated.
• Do not install heating cables on equipment
operating above the heating cable’s maximum rated
temperature.
• The minimum bending radius for VPL Power-Limiting
cables is 3/4 inch (19 mm). The minimum bending
radius for Self-Regulating cables is 1/2 inch (13 mm).
• Never install heating cables over expansion joints
without leaving slack in the cable.
• Do not energize cable when it is coiled or on the reel.
• Never use tie wire or pipe straps to secure heating
cables.
• The minimum installation temperature for heating
cables is –40°F (–40°C).