Error
No.
Warning
message
Possible causes
Corrective actions
Cannot access
programming
Mode and
parameter
settings
Controller is
password protected
Enter password (
3000
) to
unlock the controller.
See key lock.
No reaction
on screen by
touching
Screen is frozen
Press
1
finger
simultaneously for
30
seconds; screen will go in
screen calibration mode.
Touch the circles on the
screen, screen will go back
in main screen.
Seeing
3
dots,
one by one,
on the screen
Pushing the screen for
30
seconds causes
controller to enter screen
calibration mode (it can
be triggered also from
the service menu)
All
3
dots have to be
pressed one by one for
calibration before jumping
back to the main screen
7
. APPENDIX
Sensor position
Note
: For plastic pipes
position sensor on metal
boiler coupling
Sensor positioning
on metal pipes
Sensor positioning
on plastic pipes
Min. 7.87 in
Min. 7.87 in
Insulation
HWAT-ECO-GF sensor
Aluminium tape
Pipe/boiler coupling
Boiler
Boiler
ATE-180