CONDENSER AND EVAPORATOR AIR MOVERS

Fan motors require no maintenance. All bearings, shafts, etc. are lubricated during manufacturing for the life of 
the fan. 

Operation of the air conditioner in areas containing airborne 

caustics or chemicals can rapidly deteriorate filters, condenser 

coils, blowers and motors, etc. Contact nVent Equipment 

Protection for special recommendations.

CAUTION

REFRIGERANT LOSS

Each air conditioner is thoroughly tested prior to leaving the factory to insure against refrigeration leaks. Shipping 
damage or microscopic leaks not found with sensitive electronic refrigerant leak detection equipment during 

manufacture may require repair or recharging of the system. This work should only be performed by qualified 
professionals, generally available through a local, reputable air conditioning repair or service company.

Refer to the data on the nameplate which specifies the type of refrigerant and the charge size in ounces.

Before recharging, make sure there are no leaks and that the system has been properly evacuated into a 
deep vacuum.

C-NET INDUSTRIAL LTD. | +44(0)121 544 8608 | [email protected] | WWW.CNET-IS.CO.UK

Содержание T 15

Страница 1: ...T15 Instruction Manual ...

Страница 2: ... 2019 nVent 89059119 Rev I P N 10 1008 194 T SERIES Air Conditioner t15 Model INSTRUCTION MANUAL ...

Страница 3: ...STING THE AIR CONDITIONER 3 INSTALLATION INSTRUCTIONS 4 Design Data 4 Dimensional Drawing 4 Mounting Cutout Dimensions 5 Components List 5 Wire Diagrams 6 Without Heat 6 With Heat 7 Schematics 8 TEMPERATURE CONTROL 9 Units With heat 9 PRINCIPLES OF OPERATION 9 MAINTENANCE 10 Compressor 10 Inlet Air Filter 10 How To Remove Clean or Install a New Inlet Air Filter 10 Condenser and Evaporator Air Move...

Страница 4: ...efer to the nameplate for proper electrical current requirements and then connect the power cord to a properly grounded power supply Minimum circuit ampacity should be at least 125 of the amperage shown in the design data section for the appropriate model No other equipment should be connected to this circuit to prevent overloading Operate the air conditioner for five 5 to ten 10 minutes No excessi...

Страница 5: ...be taken to keep it from kinking or being elevated above the exit point of the air conditioner The drain tube must be on a continuous downward slope A slight elevation of the tube could result in secondary trap FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN OVERFLOWING OF THE CONDENSATE DRAIN PAN 7 Refer to top of nameplate for electrical requirements Connect the power cord to a properly gro...

Страница 6: ...02 15 1001 02 Coil Condenser Coated 15 1001 01 15 1001 01 Coil Evaporator 15 1001 03 15 1001 03 Compressor 10 1016 82 10 1026 101 Filter Air Reusable 89057626 89057626 Filter Dryer 52 6028 03 52 6028 03 Freeze stat 10 1033 26 10 1033 26 Service Cord 52 6035 140 52 6035 141 Terminal Block 10 1003 03 10 1003 03 Thermal Overload Compressor 10 1007 67 10 1007 68 Thermostat SPST 55 100F 10 1061 16 10 1...

Страница 7: ...89059119 6 WIRE DIAGRAMS WITHOUT HEAT C NET INDUSTRIAL LTD 44 0 121 544 8608 INFO CNET IS CO UK WWW CNET IS CO UK ...

Страница 8: ...89059119 7 WITH HEAT C NET INDUSTRIAL LTD 44 0 121 544 8608 INFO CNET IS CO UK WWW CNET IS CO UK ...

Страница 9: ...89059119 8 SCHEMATICS With Heat Without Heat C NET INDUSTRIAL LTD 44 0 121 544 8608 INFO CNET IS CO UK WWW CNET IS CO UK ...

Страница 10: ...ut down for the compressor suction and discharge pressures to equalize in order for the air conditioner to restart Operating the air conditioner below the minimum ambient temperature or above the maximum ambient temperatures indicated on the nameplate voids all warranties It is recommended that the warranty section of this manual be read in order to familiarize yourself with parameters of restrict...

Страница 11: ...ut down of the unit The above described shutdown is symptomatic of a clogged or dirty filter thus causing a reduction in cooling air flow across the surface of the compressor and condenser coil Do not run the air conditioner for extended periods of time with the filter removed Particles of dust lint etc can plug the fins of the condenser coil which will give the same reaction as a plugged filter The co...

Страница 12: ...the factory to insure against refrigeration leaks Shipping damage or microscopic leaks not found with sensitive electronic refrigerant leak detection equipment during manufacture may require repair or recharging of the system This work should only be performed by qualified professionals generally available through a local reputable air conditioning repair or service company Refer to the data on the...

Страница 13: ...tive thermostat Open motor winding Stuck fan motor Obstructed blades Repair or Replace defective part 6 Carefully check the compressor for operation motor should cause slight vibration and the outer case of the compressor should be warm Is the compressor showing signs of this YES wait 5 minutes then proceed to step 7 NO possible problem Defective thermostat Defective capacitor Defective overload D...

Страница 14: ...stem Getting water in enclosure Drain plugged Drain tube kinked Enclosure not sealed allowing humidity in Mounting gasket damaged For additional technical information i e amp draw pressures temperatures contact nVent Equipment Protection at 800 896 2665 F GAS INFORMATION T150116GXXX T150126GXXX Refrigerant Kühlmittel Chłodziwo R134a R134a GWP 1430 1430 Factory Charge Füllmenge durch Hersteller Opł...

Страница 15: ...89059119 14 NOTES C NET INDUSTRIAL LTD 44 0 121 544 8608 INFO CNET IS CO UK WWW CNET IS CO UK ...

Страница 16: ...89059119 15 NOTES C NET INDUSTRIAL LTD 44 0 121 544 8608 INFO CNET IS CO UK WWW CNET IS CO UK ...

Страница 17: ...89059119 Rev I P N 10 1008 194 nVent com nVent 2100 Hoffman Way Anoka MN 55303 USA 1 763 422 2211 1 763 576 3200 C NET INDUSTRIAL LTD 44 0 121 544 8608 INFO CNET IS CO UK WWW CNET IS CO UK ...

Страница 18: ...C NET Industrial Solutions Limited Suite 12 Sandwell Business Centre Oldbury Road Smethwick B66 1NN United Kingdom 44 0 121 544 6808 info cnet is co uk ...

Отзывы: