English
LOCATION AND MOUNTING
1. Hoffman electric heaters should be centered as low as possible in
the enclosure for optimum heat distribution.
2. It is recommended that the heater be installed on a non-
combustible metal panel for optimum performance. It may,
however, be mounted on any metal surface.
WARNING: Heaters must not be installed on wood or other
combustible surfaces.
3. The heater should be mounted in a vertical position with the
terminal block at the bottom and the air outlet openings at the top
as shown.
4. The recommended clearances shown by the shadowed area
indicates the space that should be kept free of components for safe
operation of the heater.
WARNING: Heat sensitive components must not be placed above the
heater discharge area.
5. Four 10−32 UNF, self−tapping screws are included for installation.
Vertical Surface Mounting
Optional Horizontal Surface Mounting
Watts
X
D
E
DAH1001A, DAH1002A
100
4
5.00 (127 mm)
3.25 (83 mm)
DAH2001A, DAH2002A
200
6
DAH4001B, DAH4002B
400
6
7.00 (178 mm)
3.50 (89 mm)
DAH8001B, DAH8002B
800
8
DAH13001C, DAH13002C
1300
8
© 2018 Hoffman Enclosures Inc.
- 3 -
PH 763 422 2211 • nVent.com/HOFFMAN
87565511