PIR-PEC SENSOR OPTION (…/PIR-PEC/…)

 

With the passive infra-red and photocell (PIR-PEC) sensor version, the following information is applicable. 

 

PIR RATINGS 

Power supply  

 

 

220-240VAC 50Hz 

Power Consumption  

 

0.8W work, 0.2W static 

Handset Battery Type 

 

CR2025 (Instructions on how to change on handset) 

Recommended mounting height 

1.8m – 2.5m 

Detection range 

 

 

See diagram below, 8m max. 

Photocell   

 

 

70 Lux OFF / 35 Lux ON 

Ambient light level setting 

 

Day mode = Always work, Dusk mode = Work at low light levels (60 Lux or less) 

Time out settings    

 

15 sec, 30 sec, 1 min, 3 min, 5 min, 10 min, 15 min, 30 min 

Default settings 

 

 

PIR = On, Lux = Dusk mode, Sensitivity = Near distance, Time out = 30 sec

 

 

TO CHANGE PIR SETTINGS 

The unit comes with a remote control handset, which is used to change settings of the PIR. If the default settings (listed above) are not 
suitable, then the use the handset as follows: 

 
 
 

 

 

PIR TESTING 

It may be possible to test the PIR using your required settings, but if it is daylight then you can test it by: 

1. 

Using the remote control handset, set sensor to: 

o

 

DAY MODE by pressing the green “Day mode” button 

o

 

FAR DISTANCE (max sensitivity) by pressing blue “Far distance” button 

o

 

TIME DELAY to 15 Seconds by pressing the orange “15 sec” button 

2. 

Avoid sensor detection to allow fitting to go off. 

3. 

Create movement in front of the sensor & the luminaire will switch on. 

4. 

Cease movement & the luminaire will switch off after 15 seconds. 

5. 

Once satisfied it is working, adjust to required settings as listed above. 

PE CELL TESTING  

 

Using the remote control set the fitting to Photocell only operation by pressing the blue button marked PE cell.

 

 

To test cover the sensor and the fitting will come on, once uncovered the fitting will go off.

 

FAULT FINDING 

If you experiencing a problem please check through the following before making contact with NVC: 

 

Fault - Load does not come on 

 

Check to see if the live supply to the circuit is good. 

 

Check that the “Lux Sensing” setting matches the user requirements. If the 60 lux threshold of “Dusk Mode” is too low for switch 
on, then change to “Day Mode” setting to always come on. 

 

Check that the photocell mode of operation has not been selected. 

Fault - Light does not go off 

 

Ensure that the area is left unoccupied for longer than the selected timer setting. 

 

Avoid direct sunlight entering the sensor. 

 

Do not site within 1m of forced air heating or ventilation. 

 

Do not fix to a vibrating surface.

 

 

Lux sensing (green buttons): 
Day mode = Always come on 
Dusk mode = Only come on when 
ambient light level < 60 lux (Default) 

Time out setting (orange buttons): 
15 seconds to 30 mins 
(Default = 30 secs) 

Sensitivity setting (blue buttons): 
Near distance = Picks up in shorter range 
(Default) 
Far distance = senses in longest range 

Override fitting OFF 

ON/Manual Override = Turn the 
luminaire on, but with no PIR 
function 
ON/PIR sensor = Turn on PIR mode 
(Default) 

Note: Press button to select setting. A 
successful setting is shown by the 
fitting switching off & then back on. 

DETECTION RANGE 

8m maximum. Most sensitive on 

direct perpendicular to front of 

fitting/sensor, so fitting should be 

tilted/angled to suit

NOTE! The luminaire will flash 

off & on to show a handset 

command has been received. 

Photocell mode only 