![NVC KANSAS PRO Скачать руководство пользователя страница 2](http://html.mh-extra.com/html/nvc/kansas-pro/kansas-pro_instructions_1720589002.webp)
Annual Duration Test
After 11 monthly function tests, the luminaire will carry out a full rated duration test.
The test will last 3 hours. During this time the lamp heads will illuminate & the LED status indicator will rapidly flash red.
FAULT INDICATORS
If during a self-test a fault is detected, it will be indicated as follows by the RED LED indicator:
1 flash every 3 seconds –
Fault with battery. Maybe a battery failure & requires changing, or not connected properly.
2 flashes every 3 seconds
– Fault with LED module.
3 flashes every 3 seconds –
Duration time not being met so batteries will need to be replaced.
NOTES
1. After completion of the tests listed above the luminaire will repeat the process of 11 monthly function tests & 1 annual
duration test.
2. If there is a power outage before any of the tests, the luminaire will delay the test appropriately to ensure a minimum
24-hour charge is received.
3. A fault indicator will continue until the fault is rectified.
4. A reset of the mains supply will be required to clear the fault code once it has been rectified.
MANUAL TESTING
As this is a self-test product this is NOT recommended.