9.3  Vernier Output - Master/Slave Configuration 

In  a  Master-

Slave  Configuration,  the  master  unit’s  Vernier  output  should  be 

used for driving the SSR or SCR Power Control. 
 

10.  Electrical Specifications 

Power Input 

24VAC -15/+15% 50/60Hz < 10VA. 

24V Thermostat Power 

-  

Aux Output Rated at

 

24VAC @ 500mA max. 

Brown Out Protection 

Stages restart from zero upon loss of power.

 

Command Inputs 

0-5V,  1-5V,  0-10V,  2-10V,  0-20mA,  4-20mA,  0-135Ohm.  
Selectable via dipswitch. 

Stages 

Selectable  from  1  to  16  stages  via  dipswitch.    More  than  8 
stages requires an additional NWVS setup for slave operation.

 

Stage Outputs 

30  VAC  @  1.0A  SPST  Mechanical  Relays  w/MOV  protection, 
up to a max of 5A total for all of the stages.   Up to 8 stages per 
board.  Use a Class 1 ( properly fused ) or Class 2, CSA or UL 
recognized transformer for power supply & relay outputs. 

Vernier Output 

Selectable via dipswitch # S1-6:   

 

 

Time  Proportioning  (S1-6  OFF): 

Current  limited  ~24VDC 

nominal.  Time Proportioned 4 second cycle time for driving an 
SSR. 

 

 

Analog  (S1-6  ON): 

0-10VDC  output  for  driving  an  SCR  power 

control.    10VDC  output  tolerance  is  +5/-8%  at  24VAC  power.  
10VDC output tolerance is +5/-25% at 20VAC power.           

Slave Output 

0-5V

 

output for expanding beyond 8 stages.

  

Stage Output Modes 

-

  LIFO or FIFO Selectable via dipswitch.

 

Содержание NWVS-4

Страница 1: ...Rev 7 4 06 22 Rev7 4 NUWAVE TECHNOLOGIES INC NWVS 4 NWVS 8 INSTALLATION AND USER MANUAL LOW VOLTAGE STEP CONTROL WITH VERNIER STAGE...

Страница 2: ...aster Slave Selection 8 5 5 Vernier Output Type Selection 8 6 Adjustment Potentiometers 8 6 1 Stage Delay Adjustment 8 6 2 Vernier Ratio 9 7 Test Button 9 8 Indicator LEDs 9 9 Outputs 9 9 1 Relay Outp...

Страница 3: ...termining suitability for use in any application equipment lies solely on the purchaser OEM and end user Suitability for use in your application is determined by applicable standards such as UL cUL an...

Страница 4: ...other misuse misapplication 3 Components which wear or damage with misuse are excluded e g relays 4 NuWave Technologies Inc shall not be responsible for any damage or losses however caused which may b...

Страница 5: ...a common ground with the 24VAC power input ground The diagram below details the internal wiring of the NWVS WARNING EXCEEDING 30MA OR 15V ON THE COMMAND INPUT CAN PERMANENTLY DAMAGE THE NWVS CAUSING...

Страница 6: ...R Input 0 5V OFF OFF OFF OFF OFF 1 5V OFF ON OFF OFF OFF 0 10V OFF OFF ON OFF OFF 2 10V OFF ON ON OFF OFF 0 20mA ON OFF OFF OFF OFF 4 20mA ON ON OFF OFF OFF 0 135 OHM OFF OFF OFF ON ON If the 0 10V ra...

Страница 7: ...OFF 14 ON ON OFF ON 15 ON ON ON OFF 16 ON ON ON ON 5 3 Output Mode Selection LIFO last in first out and FIFO first in first out modes are both available by setting of S2 position 6 Switch S2 Position...

Страница 8: ...cycle time PWM signal The SSR used to control the Vernier heater is driven from terminals TP and TP When Analog is selected the Vernier output is a 0 10V analog signal for driving a phase angle contr...

Страница 9: ...creases in intensity when power is increasing and Analog is selected When Time Proportioning is selected turns on when the output is energized Slave Output LED Increases in intensity when power is inc...

Страница 10: ...Selectable via dipswitch Stages Selectable from 1 to 16 stages via dipswitch More than 8 stages requires an additional NWVS setup for slave operation Stage Outputs 30 VAC 1 0A SPST Mechanical Relays w...

Страница 11: ...if the relay is operating correctly the contacts should be closed when the Red LED is energized Vernier Output Indication Green LED that varies in intensity when analog mode is selected or blinks whe...

Страница 12: ...Page 12 of 15 Rev7 4 NUWAVE TECHNOLOGIES INC 11 Wiring Diagrams 11 1 Command Input Wiring...

Страница 13: ...ICE to switch the power off if safe temperatures are exceeded WARNING HIGH VOLTAGE This control is wired to a transformer Solid State Relay and contactors with high voltage on them This control must b...

Страница 14: ...switch the power off if safe temperatures are exceeded WARNING HIGH VOLTAGE This control is wired to a transformer Solid State Relay and contactors with high voltage on them This control must be inst...

Страница 15: ...ch the power off if safe temperatures are exceeded WARNING HIGH VOLTAGE This control is wired to a transformer Solid State Relay and contactors with high voltage on them This control must be installed...

Отзывы: