background image

Broan-NuTone LLC    Hartford, Wisconsin    www.nutone.com    888-336-3948

PERFORMANCE RATINGS

MODEL QTXEN110S 
VENTILATOR

AMPS

 

Model 

Amps*

  QTXEN110S 

0.3

WEIGHT

 

Model 

 Shipping

    Weight

   QTXEN110S   12.2 lbs.

*

 Total connected load

AIR FLOW PERFORMANCE

MODEL QTXEN110S

TYPICAL SPECIFICATION

Ceiling Ventilator shall be NuTone Model QTXEN110S.
The unit will have a control that will automatically turn fan ON 

when humidity increase is rapid to moderate (user adjustable), or 

when humidity is higher than user-adjustable set-point (50%-80% 

Relative Humidity), or when supply power is cycled from ON (for 

more than a second) to OFF (for less than a second) and back 

ON. It shall be user-adjustable to turn OFF 5 to 60 minutes after 

humidity has stabilized and is below user-adjustable set-point,

or after manually initiated by supply power cycling.
Ceiling Ventilator shall have corrosion resistant galvanized steel 

housing with four-point mounting capability. It shall be ducted to 

a roof or wall cap using 6” round ductwork.

Blower assembly shall be removable, have a centrifugal-type blower 

wheel and a permanently lubricated motor designed for continuous 

operation.
Non-metallic damper/duct connector shall be included.
Air delivery shall be no less than 110 CFM and sound level no greater 

than 0.7 Sones. All air and sound ratings shall be certified by HVI.
Ceiling Ventilator shall be Energy Star® qualified and have an energy 

efficient permanent split capacitor motor.
Ceiling  Ventilator  shall  be  U.L.  Listed  for  use  over  bathtubs  and 

showers when connected to a GFCI protected branch circuit.

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0

10

20

30

40

50

60

70

80

90 100 110 120 130

Air flo w  (cfm )

P

s

 (

in

w

.g

.)

HVI-2100 CERTIFIED RATINGS comply with new 

testing  technologies  and  procedures  prescribed 

by the Home Ventilating Institute, for off-the-shelf 

products,  as  they  are  available  to  consumers. 

Product  performance  is  rated  at  0.1  in.  static 

pressure, based on tests conducted in a state-of-

the-art  test  laboratory.  Sones  are  a  measure  of 

humanly-perceived loudness, based on laboratory 

measurements.

HVI PERFORMANCE

  

Static   

Fan

 

Model 

Pressure (Ps)  CFM  Sones  Watts

 

QTREN110S

 

0.10 

110 

0.7 

33.5

  

0.25 

90

Отзывы: