background image

INST
ALLA
TION MANUAL

INST
ALLA

TION

11

BKSA2 and NKSA2 Series

(1) G

REASE

 F

ILTER

(1) 3¼” 

X

 10”

D

AMPER

 

ASSEMBLY

F

IND

 

INSIDE

 

OF

 

HOOD

)

(1) P

ARTS

 B

AG

* C

ONTAINING

:

(1) B

ULB

 S

UCTION

C

UP

 T

OOL

(5) N

O

. 8 

X

 5/8”

RD. HD.

W

OOD

 S

CREWS

* F

IND

 

PARTS

 

BAG

 

BEHIND

THE

 

DAMPER

 

ASSEMBLY

INSIDE

 

OF

 

HOOD

Содержание CAPTUR BKDD1 Series

Страница 1: ...Serial number 99045655 001G RANGE HOOD Series BKDD1 BKDF1 BKSA2 BKSF1 BKSM1 CKSL1 NKDF1 NKSA2 and NKSH1 INSTALLATION USE AND CARE MANUAL WWW BROAN CA WWW NUTONE CA ...

Страница 2: ...ols and Accessories for Installation 8 Install Ductwork Ducted Installations Only 8 Contents 9 11 Prepare the Hood 12 14 Prepare the Hood Location 15 EZ1 Person Installation 15 17 Install the Hood EZ1 Bracket 18 19 Standard Installation 20 Install the Hood Standard Installation 21 Connect the Wiring 22 Light Bulbs BKSA2 BKSM1 CKSL1 NKSA2 and NKSH1 Series only 23 Install the Filters 23 Wiring Diagr...

Страница 3: ...d standards including fire rated construction Sufficient air is needed for proper combustion and exhausting of gases through the flue chimney of fuel burning equipment to prevent backdrafting Follow the heating equipment manufacturer s guidelines and safety standards such as those published by the National Fire Protection Association NFPA and the American Society for Heating Refrigeration and Air ...

Страница 4: ...and you know how to operate it B The fire is small and contained in the area where it started C The fire department has been called D You can fight the fire with your back to an exit Based on Kitchen Fire Safety Tips published by NFPA CAUTION For indoor use only For general ventilating use only Do not use to exhaust hazardous or explosive materials and vapors To avoid motor bearing damage and nois...

Страница 5: ...UTTON When blower is OFF push this button to turn ON the blower at the last selected speed Push this button again to turn OFF the blower NOTE If there is no speed selected all blower speed push buttons up the blower will not turn ON In that case press on the desired speed level push button to activate the blower BLOWER SPEED LEVEL PUSH BUTTONS When blower is ON change the blower speed by pressing ...

Страница 6: ...e beep sound ends this will turn off the blower and save this blower speed to memory LIGHT BUTTON When lights are OFF press once on this button to turn ON the lights at the last saved setting If there was no light setting saved the lights will be set on LOW intensity Press another time to set the lights on HIGH intensity Pressing another time after the HIGH setting will turn OFF the lights Each ti...

Страница 7: ...d frequently Use a clean cloth soaked with warm detergent solution STAINLESS STEEL CLEANING Do Regularly wash with clean cloth or rag soaked with warm water and mild soap or liquid dish detergent Always clean in the direction of original polish lines Always rinse well with clear water 2 or 3 times after cleaning Wipe dry completely You may also use a specialized household stainless steel cleaner D...

Страница 8: ... SURFACE CABINET 3 X 10 DUCT FOR HORIZONTAL DISCHARGE WALL CAP ROOF CAP 3 X 10 OR 7 ROUND DUCT FOR VERTICAL DISCHARGE HOUSE WIRING TOP OR BACK OF HOOD HOOD NOTE Distances over 24 are at the installer and user discretion 1 Determine whether hood will discharge vertically 3 x 10 or 7 round or horizontally 3 x 10 only 2 Decide where the ductwork will run between the hood and the outdoors 3 Choose a s...

Страница 9: ...framed cabinet Pour une installation sous une armoire à fond en retrait utiliser les lignes pour mesurer l épaisseur du décalage causé par le mur de l armoire et plier le gabarit en conséquence To be translated in Spanish 2 SHIELDED HALOGEN BULBS 50W GU10 INSTALLED ON HOOD 2 GREASE FILTERS 1 3 X 10 DAMPER ASSEMBLY FIND INSIDE OF HOOD 1 PARTS BAG CONTAINING 6 NO 8 X 5 8 RD HD WOOD SCREWS 2 INSTALLA...

Страница 10: ...anslated in Spanish FIND EZ1 BRACKETS ATTACHED INSIDE OF HOOD FIND PARTS BAG BEHIND THE DAMPER ASSEMBLY INSIDE OF HOOD BKDD1 Series 1 3 X 10 DAMPER ASSEMBLY 1 PARTS BAG CONTAINING 6 NO 8 X 5 8 RD HD WOOD SCREWS FIND INSIDE OF HOOD FIND PARTS BAG BEHIND THE DAMPER ASSEMBLY INSIDE OF HOOD 2 INSTALLATION BRACKETS FOR FRAMED CABINET 2 INSTALLATION BRACKETS FOR FRAMELESS CABINET 1 TEMPLATE FOR DUCTING ...

Страница 11: ...LATION 11 BKSA2 and NKSA2 Series 1 GREASE FILTER 1 3 X 10 DAMPER ASSEMBLY FIND INSIDE OF HOOD 1 PARTS BAG CONTAINING 1 BULB SUCTION CUP TOOL 5 NO 8 X 5 8 RD HD WOOD SCREWS FIND PARTS BAG BEHIND THE DAMPER ASSEMBLY INSIDE OF HOOD ...

Страница 12: ...p no EZ1 brackets in BKSA2 and NKSA2 Series Remove both screws holding damper assembly to hood Remove parts bag captured behind the damper assembly Remove damper assembly from inside the hood and keep the screws for further use 4 Remove the wiring cover shaded part on illustration below by sliding it out from the hood and set it aside B C DAMPER ASSEMBLY SCREWS EZ1 BRACKETS NOTE Since this manual ...

Страница 13: ...EWS 6 Remove Electrical Power Cable Knockout from top vertical wiring or back horizontal wiring of hood Install an appropriate strain relief 1 2 diameter not included NON DUCTED INSTALLATION ONLY 7 Remove 3 screws retaining the recirculation cover plate shaded part in illustration below to the hood Discard this plate with its screws ELECTRICAL POWER CABLE KNOCKOUT ...

Страница 14: ... plate can be installed up to 1 2 on either side of the hood center 7 ROUND KNOCKOUT PLATE ALSO REMOVE VERTICAL KNOCKOUT PLATE 3 X 10 VERTICAL KNOCKOUT PLATE 3 X 10 HORIZONTAL KNOCKOUT PLATE FIGURE 1 A 7 ROUND DUCT PLATE SCREWS FIGURE 3 3 X 10 DAMPER ASSEMBLY TOP BACK EDGE OF HOOD DAMPER FLAP PIVOT SCREWS FIGURE 2 A FIGURE 2 B 9 Attach 3 x 10 Damper Assembly on top OR back of hood if using 3 x 10 ...

Страница 15: ...when installing to framed cabinet Pour une installation sous une armoire à fond en retrait utiliser les lignes pour mesurer l épaisseur du décalage causé par le mur de l armoire et plier le gabarit en conséquence To be translated in Spanish P C CABINET FRONT C L A B VERTICAL EXHAUST A S A A V RTICAL EX 3 x 10 3 x 14 RECTANGULAR DUCTING 7 ROUND DUCTING OR Use this template for marking do not attemp...

Страница 16: ...crews Repeat for the other side frame 7 Install the proper installation brackets according to the type of cabinet framed or frameless See below 4 Drill a 1 8 dia pilot hole for house wiring at A location on template 5 Use a sharp pencil or 1 8 drill bit to mark the locations for the appropriate duct access holes 16 locations for 7 round duct or 4 corner locations for rectangular duct Remove the te...

Страница 17: ...raw a line on the outer edge of the bracket as shown Slide the bracket towards the center of cabinet and align side edge to marked line keeping the rear end edge leaning on the wall Use a pencil to mark 3 holes Remove the bracket Using a 7 64 drill bit drill 3 holes where marked Assemble the bracket to the cabinet bottom using a Phillips screwdriver and 3 provided countersunk wood screws Repeat fo...

Страница 18: ...ts 2 recessed FRONT HOLES C and D While holding the hood attach the power cable to the hood using the strain relief 5 Hang the hood on the brackets using the 2 recessed FRONT HOLES C and D While holding the hood run the house power cable into the hood through the strain relief previously installed in step 6 on page 13 Attach power cable to the hood NOTE See final installation steps on next page HO...

Страница 19: ...arts bag Insert 2 screws per side in the slots as shown in insets on illustration below 8 For frameless cabinet secure the hood to the cabinet using 4 no 8 x 5 8 round head wood screws included in parts bag Insert 2 screws per side in the slots as shown in insets on illustration below FRAMED CABINET FRAMELESS CABINET WOOD SCREWS METAL SCREWS ...

Страница 20: ...ncluded VERTICAL DUCT ACCESS HOLE 1015 16 5 5 CENTER LINE HOOD MOUNTING SCREWS 4 ELECTRICAL ACCESS HOLE IN CABINET BOTTOM WOOD SHIMS RECESSED BOTTOM CABINETS ONLY CABINET FRONT 3 4 1Ǫ 1 7 16 12Ǭ 47 16 CABINET BOTTOM 12Ǭ 3 X 10 VERTICAL DUCTING CABINET BOTTOM CABINET FRONT HORIZONTAL DUCT ACCESS HOLE HOOD MOUNTING SCREWS 4 ELECTRICAL ACCESS HOLE IN WALL 3Ǭ CENTER LINE WOOD SHIMS RECESSED BOTTOM CAB...

Страница 21: ...m 4 mounting screws previously installed Slide hood back towards wall until mounting screw heads are engaged in narrow end of keyhole slots in top of hood Tighten screws securely Attach power cable to the hood using the strain relief DUCTED INSTALLATION ONLY 3 Connect ductwork to hood and use metal foil duct tape to make joints secure and air tight Make sure the damper assembly or round duct plate...

Страница 22: ...tandards Before connecting wires switch power off at service panel and lock service disconnecting means to prevent power from being switched on accidentally CAUTION Ensure both tabs on inner top of hood are engaged in their corresponding slots in wiring cover Also take care not to pinch wires while reinstalling wiring cover SCREW 2 Reinstall wiring cover and attach it to the hood using its retaini...

Страница 23: ...TOOL WARNING Do not touch lamps during or soon after operation Burns may occur In order to prevent the risk of personal injury only install shielded halogen lamps Also never install a cool beam a dichroic lamp a lamp not suitable for use in recessed luminaires or identified for use in enclosed fixtures Install the Filter s Ducted Installation Only Re install grease filter s removed in step 2 on pa...

Страница 24: ...gh Motor On Off Motor Speeds Lights On Off Lights High Low 1 2 3 BKSM1 AND CKSL1 SERIES 1 2 3 4 5 6 1 2 3 4 J6 Override J4 LED J10 Interface 1 2 3 4 5 6 7 8 User interface mounted to J10 on back of control board J1 Transformer J2 Power Motor 5 4 3 2 1 5 4 3 2 1 6 7 Control Board R R BL BL BK W BK BK W G Y R Low O Medium BK High W 120 V AC Line Neutral Ground G Y W BK O R FAN MOTOR BN BN W R BK LED...

Страница 25: ... WHITE G Y O R W GREEN YELLOW ORANGE RED WHITE R W LED driver input output 1 2 3 4 5 6 2 2 1 1 BK R W LED LED BKSF1 SERIES G Y W BK O R FAN MOTOR BN BN W G Y R Low BK High W 120 V AC Line Neutral Ground BK BK Motor Switch Light Switch Y Low BL High W W BK BK COLOR CODE BK BL BN BLACK BLUE BROWN R W Y RED WHITE YELLOW BN W G Y O BROWN WHITE GREEN YELLOW ORANGE W 1 2 3 4 5 6 1 1 2 2 BKSA2 NKSA2 AND ...

Страница 26: ...AG INCLUDING 4 METAL SCREWS NO 8 18 X 1 2 6 ROUND HEAD NO 8 X 5 8 WOOD SCREWS 6 NO 8 X 1 2 COUNTERSUNK SCREWS 1 1 S97020466 NON DUCTED FILTER TYPE XC SET OF 2 NON DUCTED INSTALLATION ONLY 1 1 S99527587 NON DUCTED FILTER CLIP KIT INCLUDES 4 CLIPS 1 1 S97020470 EASY INSTALL KIT INCLUDING HARDWARE 1 1 BKDD1 SERIES ITEM NOT SHOWN REPLACEMENT PARTS AND REPAIRS In order to ensure your unit remains in go...

Страница 27: ...INCLUDING 4 METAL SCREWS NO 8 18 X 1 2 6 ROUND HEAD NO 8 X 5 8 WOOD SCREWS 6 NO 8 X 1 2 COUNTERSUNK SCREWS 1 1 S97020466 NON DUCTED FILTER TYPE XC SET OF 2 NON DUCTED INSTALLATION ONLY 1 1 S99527587 NON DUCTED FILTER CLIP KIT INCLUDES 4 CLIPS 1 1 S97020470 EASY INSTALL KIT INCLUDING HARDWARE 1 1 BKDF1 SERIES ITEM NOT SHOWN REPLACEMENT PARTS AND REPAIRS In order to ensure your unit remains in good ...

Страница 28: ...INCLUDING 4 METAL SCREWS NO 8 18 X 1 2 6 ROUND HEAD NO 8 X 5 8 WOOD SCREWS 6 NO 8 X 1 2 COUNTERSUNK SCREWS 1 1 S97020466 NON DUCTED FILTER TYPE XC SET OF 2 NON DUCTED INSTALLATION ONLY 1 1 S99527587 NON DUCTED FILTER CLIP KIT INCLUDES 4 CLIPS 1 1 S97020470 EASY INSTALL KIT INCLUDING HARDWARE 1 1 NKDF1 SERIES ITEM NOT SHOWN REPLACEMENT PARTS AND REPAIRS In order to ensure your unit remains in good ...

Страница 29: ...K SCREWS 1 SUCTION CUP TOOL 1 1 S97020466 NON DUCTED FILTER TYPE XC SET OF 2 NON DUCTED INSTALLATION ONLY 1 1 S99527587 NON DUCTED FILTER CLIP KIT INCLUDES 4 CLIPS 1 1 S97020470 EASY INSTALL KIT INCLUDING HARDWARE 1 1 SV05921 SHIELDED HALOGEN BULB 50 W GU10 2 2 BKSM1 SERIES REPLACEMENT PARTS AND REPAIRS In order to ensure your unit remains in good working condition you must use Venmar Ventilation ...

Страница 30: ...d repairs KEY NO PART NO DESCRIPTION QUANTITY 30 STAINLESS 1 S97020031 RECIRCULATION COVER PLATE STAINLESS STEEL INCLUDING SCREWS 1 2 S97020534 3 X 10 DAMPER ASSEMBLY INCLUDING SCREWS 1 3 S97020408 BLOWER MOTOR INCLUDING 4 SCREWS AND 1 CAPACITOR 1 4 S97020407 FANPELLER INCLUDING ITEM 5 1 5 SR99420635 CLIP FOR FANPELLER 1 6 S99010434 002 GREASE FILTER MICRO MESH TYPE C2 SET OF 2 1 7 S97020427 MECHA...

Страница 31: ...INCLUDING 4 METAL SCREWS NO 8 18 X 1 2 6 ROUND HEAD NO 8 X 5 8 WOOD SCREWS 6 NO 8 X 1 2 COUNTERSUNK SCREWS 1 SUCTION CUP TOOL 1 1 1 S97020466 NON DUCTED FILTER TYPE XC SET OF 2 NON DUCTED INSTALLATION ONLY 1 1 1 S99527587 NON DUCTED FILTER CLIP KIT INCLUDES 4 CLIPS 1 1 1 S97020470 EASY INSTALL KIT INCLUDING HARDWARE 1 1 1 SV05921 SHIELDED HALOGEN BULB 50 W GU10 2 2 2 NKSH1 SERIES REPLACEMENT PARTS...

Страница 32: ...30 RECIRCULATION COVER PLATE WHITE INCLUDING SCREWS 1 S97020031 RECIRCULATION COVER PLATE STAINLESS STEEL INCLUDING SCREWS 1 2 S97020534 3 X 10 DAMPER ASSEMBLY INCLUDING SCREWS 1 1 3 S97020408 BLOWER MOTOR INCLUDING 4 SCREWS AND 1 CAPACITOR 1 1 4 S97020407 FANPELLER INCLUDING ITEM 5 1 1 5 SR99420635 CLIP FOR FANPELLER 1 1 6 S99010430 002 GREASE FILTER OPEN MESH TYPE C1 SET OF 2 1 1 7 S99030375 ROC...

Страница 33: ... certified service depot for all replacement parts and repairs KEY NO PART NO DESCRIPTION QUANTITY 30 STAINLESS 1 S97020031 RECIRCULATION COVER PLATE STAINLESS STEEL INCLUDING SCREWS 1 2 S97020534 3 X 10 DAMPER ASSEMBLY INCLUDING SCREWS 1 3 S97020408 BLOWER MOTOR INCLUDING 4 SCREWS AND 1 CAPACITOR 1 4 S97020407 FANPELLER INCLUDING ITEM 5 1 5 SR99420635 CLIP FOR FANPELLER 1 6 S99010436 GREASE FILTE...

Страница 34: ...ent parts to you at no charge You are responsible for all costs for removal reinstallation and shipping insurance or other freight charges incurred in the shipment of the Product or part to the Company If you must send the Product or part to the Company as instructed by the Company you must properly pack the Product or part the Company is not responsible for damage in transit The Company reserves ...

Отзывы: