Numens HNC-310 Скачать руководство пользователя страница 2

 

 

 

 

 

 2 

32-0029-r02_2015-05 

Numens 
46-2 MoGao Road, Dong Qian Lake, Ningbo, Zhejiang, China 315121 

© 2015 Ambest Electronics (Ningbo) Co Ltd. All rights reserved. All specifications and other information shown were current at the date of publication 
and subject to change without notice. 

 

3. 

Subject the detector to a flow of warm air at a temperature of 
between 65 ˚C and 80 ˚C as follows (this requirement can be 
met by some domestic hair dryers). 

a. 

Start the warm airflow and check that temperature is 
correct and stable. 

b. 

From a distance of approximately 5 cm, direct the 
airflow at the guard protecting the thermistor for up to 
30 s. The detector will signal an alarm by continuous 
illumination of the LED. 

c. 

Upon alarm, immediately remove the heat source. 

4. 

Reset the detector from the control and indicating equipment. 

5. 

Check that the detector LEDs are off and the control and 
indicating equipment returns to the quiescent condition. 

Remote Indicator (where fitted)

 

Check that the indicator illuminates at the same time as the 
detector LEDs. 

Output Relay (where fitted)

 

1. 

Follow Heat Detector procedure step 3. 

2. 

Monitor the output relay for activation. 

3. 

Reset the detector from the control and indicating equipment. 

4. 

Monitor the output relay for reset to its quiescent setting. 

Auto-Reset (where fitted)

 

1. 

Follow Heat Detector procedure step 3. 

2. 

Monitor that the detector automatically resets. 

The auto-reset will typically reset the detector within 30 s of the 
removal of the heat source.  

Final Conditions 

Ensure all the alarm signal services, releasing devices and 
extinguisher systems disabled for the commissioning are returned 
to their previous condition. 

References 

Document Description 

31-0041 

HNC-310 non-addressable heat detector datasheet 

 

View the complete range of products at 

www.numens.net

 

 

 

Отзывы: