background image

SOLO

      400-632-000-A                    2008-09-19                    6/7

NOTE: The Select button flashes during the error display when there
is corrective action to be taken. Also, the appropriate wording flashes
on the screen to pinpoint the source of the problem.

All programmed settings (time and temperature) are not erased
during a power outage. However, if a power outage exceeds 4 hours,
only the thermostat’s clock must be set (refer to section 3.1). When
power returns, the thermostat returns to the operating mode
preceding the power outage.

If you have multiple SOLO thermostats, you can connect them to
form a network. This allows you to:

Use the “Send to Network” feature. This feature allows you to
program only one thermostat in the network and be able to send
its settings to the other thermostats. This reduces programming
time during installation and is useful when you are leaving for
vacation or returning home from a vacation.

Display the outdoor temperature or humidity from any thermostat
(requires outdoor sensor AC629 - refer to section 10).

To connect thermostats in a network:

n

Insert a pair of 18-gauge wires (not supplied) through one of the 
two openings on the thermostat base and connect them to 
terminals 2 and 3. 

NOTE: Pay close attention to the polarity of the connections. 
Link all terminals “2” together and all terminals “3” together.

o

Configure any one of the thermostats in the network as “Master” 
using DIP Switch 2 and leave the rest as “Slave”. Refer to step 5 
in section 2.

The following will appear on the “master” thermostat and “slave”
thermostat(s) when the thermostats are powered up:

Send to Network

The Send to Network function is available on the “master” thermostat
only. It is used to send the settings of the “Master” thermostat to all
“slave” thermostats in the network.

NOTE: Send to Network is not available if the “Master” thermostat is
not connected to other SOLO thermostats in a network.

To send the settings from the “master” thermostat to the “slave”
thermostat(s):

n

Press and hold the 

Select

 button for 2 seconds to enter the 

Programming Menu.

o

Using the 

Up

 or 

Down

 button, go to 

Send to Network

 and press 

the 

Select

 button.

p

Using the 

Up

 or 

Down

 button, choose Yes and press the 

Select

 

button. All settings are now transmitted to the “slave” 
thermostat(s). You will automatically be returned to the 
Programming Menu.

t

Error Displays

7.

The GFCI has tripped. Reset the thermostat (refer to
section 6). If the GFCI trips again, cut power to the
heating system from the main electrical panel and have
the installation verified by an electrician.

It is normal that this briefly appears at power-up. Wait
for the thermostat to obtain its reading. No corrective
action is necessary.

The temperature reading is higher than 158 °F (70 °C).
Although the thermostat does not display temperatures
above that value, it continues to operate and control the
temperature. No corrective action is necessary.

The ambient or floor temperature reading is lower than
32 °F (0 °C) or the outdoor temperature reading is lower
than -40 °F (-40 °C). Although the thermostat does not
display temperatures below that value, it continues to
operate and control the temperature. No corrective
action is necessary.

Two or more thermostats have been configured as
“master” in the same network (refer to section 9). Only
one thermostat per network must be configured as
“master”. This error code will appear only on all
thermostats configured as “master” thermostats.

There is a short in the network wires. This can indicate
the terminal polarity was not observed during the
network cable connections (refer to section 9). Although
the error code appears only on the master thermostat,
the short or bad connection can be anywhere in the
network.

The floor sensor circuit is open. This can be caused by
a cut in the sensor wires. Replace the floor sensor. The
thermostat is automatically set to use the “Ambient”
setpoint temperatures (refer to section 5.2). The
maximum heating power is 100% if the thermostat has
been configured for a tile floor and 70% for a wood
floor.

The floor sensor is shorted. This can happen, for
example, if a nail or screw has been driven through the
wires. Replace the floor sensor. The thermostat is
automatically set to use the “Ambient” setpoint
temperatures (refer to section 5.2). The maximum
heating power is 100% if the thermostat has been
configured for a tile floor and 70% for a wood floor.

The ambient temperature sensor circuit is open.
Replace the thermostat.

The ambient temperature sensor is shorted. Replace
the thermostat.

u

Power Outage

8.

v

Network Connection

9.

Appears on 
a “master” 
thermostat

Appears on 
a “slave” 
thermostat

400-632-000-A (Nuheat OEM632) ENG.fm  Page 6  Friday, September 19, 2008  4:35 PM

Содержание Solo

Страница 1: ...code This thermostat has tinned copper wires for line and load connections Special CO ALR solderless connectors must be used if these wires are to be connected to aluminium conductors p Pull the temperature sensor wires through one of the openings on the thermostat base and connect the wires to terminals 1 and 2 no polarity The sensor cable must not come in contact with the electrical wires and mu...

Страница 2: ...our and press the Select button r Set the minutes and press the Select button s Set the year and press the Select button t Set the month and press the Select button u Set the day and press the Select button You will automatically be returned to the Programming Menu 3 2 Setting the Week Schedule Set the week schedule by assigning a Day Type workday home day away day for each day of the week The def...

Страница 3: ...d when you go on vacation or during warmer months refer to section 4 4 To modify the Away temperature n Press and hold the Select button for 2 seconds to enter the Programming Menu o Using the Up or Down button go to Away and press the Select button p Using the Up or Down button set the desired temperature and press the Select button You will automatically be returned to the Programming Menu 4 1 M...

Страница 4: ...utomatically be returned to the Programming Menu 4 5 Temporarily Bypassing the Programmed Temperature The thermostat uses a programmed temperature when it is in Automatic mode Workday mode Home day mode or Away mode To temporarily bypass the programmed temperature press the Up or Down button until the desired temperature is displayed The mode indicator will flash indicating that you are temporaril...

Страница 5: ...Programming Menu o Using the Up or Down button go to Floor Limit and press the Select button p Using the Up or Down button choose the Floor Limit Min Max that you wish to modify and press the Select button q Set the temperature and press the Select button to return to the Floor Limit submenu r Repeat steps 3 and 4 if you wish to modify the other Floor Limit temperature s When done press the Up or ...

Страница 6: ...lave thermostat s You will automatically be returned to the Programming Menu t Error Displays 7 The GFCI has tripped Reset the thermostat refer to section 6 If the GFCI trips again cut power to the heating system from the main electrical panel and have the installation verified by an electrician It is normal that this briefly appears at power up Wait for the thermostat to obtain its reading No cor...

Страница 7: ...d NUHEAT will repair or replace at our option and without charge any defective product which has been used under normal conditions The warranty does not cover delivery costs and does not apply to products poorly installed or randomly damaged before during or after installation This warranty cancels and replaces any other manufacturer s express or implied warranty as well as any other company commi...

Отзывы: