6.4 Electric Heaters

Electric heaters should be checked at regular intervals for condition

of elements, wiring and insulation.

6.5 Recuperator

The recuperator block is normally protected from dust and 

contamination by upstream pre-filters.  It is possible to clean the

unit with compressed air in the case of dust deposits or by spraying

with a mild detergent solution for grease deposits.  Solvents,

strong alkaline, acidic or any products that may be aggressive to

aluminium should not be used. Do not use cleaning water over 50

deg C.

Drain lines should be checked to ensure that they are unobstructed

and free draining.  Traps should be checked that they are fully

primed and functioning.

Drain pans should be flushed out periodically to remove 

contamination, and chemical treatments may be used to provide

protection between service visits.

Note: The unit application may require particular attention to

this item – Check with Building Management personnel for

details.

6.6 Maintenance and Cleaning of

Rotating Heat Exchangers

Maintenance of the rotor

To secure the function and performance, the face of the rotor has to

be inspected regulary for dust and dirt. Any dirt or/and dust should

be removed. For a small amount of easily removable dirt we 

recommend to use a vacuum cleaner. For heavier deposits it is 

possible to use compressed air, with caution. Finally, firm dirt in

the rotor can be removed by using hot water and a mild detergent.

Maintenace of drive unit

Tension of the V-belt must be checked after the first 100 hours of

operation to secure the rotational function of the wheel.

To adjust tension,

first check the belt tensioner and adjust it as

much as possible. Secondly, shortening of the V-belt may be

required. The V-belt is joined together by an easily removable

mechanical lock. 

Ensure adjustment of the belt tensioner after

this operation.

The round belt is self tensioned and no adjustment should be needed.

Maintenace of brush sealants

Tightness between brush sealants and casing has to be checked

during inspection. The brush sealants are easily adjusted by 

losening the screws and moving the brush sealant into the right

position.

V-belt, Round belt and brush sealants are all available as spare

parts.

Checking drive belt tension 

To check the correct tension of a drive belt, apply a force at right

angles to the centre of the belt span sufficient to deflect the belt

16mm for every metre of span length.

The force required to deflect the ‘V’ belt should be from 0.5kg to

0.8kg.

Changing a drive belt

To replace a belt, remove the two bolts from the motor mounting

furthest from the fan and slacken the remaining two bolts. Lift the

motor plate and remove the belt. Replacing the belt is the reverse

of this procedure.

Adjusting drive belt tension 

All belt drive units incorporate a belt tensioning facility.

To adjust the belt tension, slacken the pinch bolts on the sides of

the motor plate. Use the motor platform pivot adjustment to 

tighten and loosen the belt.

Clean impellers with a soft brush only, and remove dust/deposits

from all internal surfaces including the motor housing,

6.7 General

Inspect all internal and external surfaces to check for corrosion or

peeling of painted surfaces.  

Thoroughly clean affected areas with a wire brush, apply a coat of

zinc rich primer or similar, and re-touch with suitable finishing

paint.  Ensure tightness of all nuts, bolts, and fixings.  Check all

components for general condition.

7.0 Service

Service schedule (typical – will depend on site 

conditions)

6 MONTHS

12 MONTHS

FILTERS

4

or

4

DAMPERS

4

DAMPER ACTUATORS

4

BELT DRIVES

4

FILTER MANOMETER FLUID

4

VENT WATER COILS

4

COIL FINNED SURFACES

4

CHECK DRAIN LINES + DRIP TRAY

4

4

CLEAN & FLUSH DRAIN PANS

Building

Schedule ?

4

NUTS, BOLTS, FIXINGS SECURE

4

FAN BEARINGS

4

ELECTRIC HEATERS

4

ELECTRICAL WIRING

4

FAN IMPELLER

4

GENERAL

4

8.0 Warranty

Ecosmart XBOXER TWB units have a 5 year warranty. 

No control units have a 2 year warranty. The first year covers

parts and labour and the remaining period covers parts only.

This warranty is void if the equipment is modified without 

authorisation, is incorrectly applied, misused or not installed 

commissioned and maintained in accordance with the details 

contained in this manual and general good practice.

9.0 Spares

Spare parts and replacement components, and general advice are

available from the Technical Support department.

Telephone 029 2085 8400

Fax 029 2085 8444

10

17. 06. 15. Leaflet Number 671424

Installation, Operating and Maintenance Instructions

XBOXER Run Around Coil

Figure 22. 

Содержание XBOXER R4-RAC-L

Страница 1: ...f CW or DX modules are included add 600mm to overall length Nuaire Limited Western Industrial Estate Caerphilly United Kingdom CF83 1NA T 029 2085 8400 F 029 2085 8444 E info nuaire co uk W www nuaire co uk 1 17 06 15 Leaflet Number 671424 AHU with Heat Recovery section and direct drive AC motor technology Figure 2 Model shown R4 6 RAC N No heater Includes Ecosmart control Figure 1 Model shown R4 ...

Страница 2: ... unit castings Where channels and or support frames are bolted to the underside of the unit casing slings or fork lift arms should be positioned to locate in the apertures in the channels If Lifting Eyes have been supplied fitted it is recommended that they are used Figure 5 Lifting 2 3 Storage The equipment must be stored in a dry internal location Ductwork connection apertures shall be sealed ag...

Страница 3: ...d together All necessary self drilling screws and sealant are supplied with each unit and are normally bagged and located within the fan section The equipment must not be exposed to the weather in an un assembled or partially assembled state All ductwork sealing and assembly work must be completed before the unit can be considered weather proof Pipe work connections to heating and or cooling coils...

Страница 4: ... DOL STARTING 4kW and above 400V 3 phase 50Hz supply U1 V1 W1 W2 U2 V2 L1 L2 L3 Three Phase Figure 10 Note by special order Refers only to Inverters supplied by Nuaire L1 L2 L3 L1 L L2 N L3 PE W V U 400V 3 phase 50Hz supply 3 Phase only INVERTER SPEED CONTROL Connections to motor 3 Phase input Motor 3 phase Notes Total length of motor leads should not exceed 50 metres If a screened motor cable is ...

Страница 5: ... inverter are made at the factory 1 3 5 2 4 6 U V W CONTACTER A1 A2 13 14 W1 V1 U1 W2 V2 U2 Fan 1 Fan 2 W1 V1 U1 W2 V2 U2 Motors 4kW and above L3 N L2 L1 L3 N L2 L1 Mains supply connections 400V 3 phase 50 Hz Neutral FAUL RUN N L SL DP CL N RET Remove this link wire if 1 a switched live signal is connected 2 A ES PIR ES TC or BMS signal is connected Min Max SL run on Trickle Test 0 1 Pwr Standby F...

Страница 6: ...rter are made at the factory 1 3 5 2 4 6 U V W CONTACTER A1 A2 13 14 W1 V1 U1 W2 V2 U2 Fan 1 Fan 2 W1 V1 U1 W2 V2 U2 Motors 4kW and above L3 N L2 L1 L3 N L2 L1 Mains supply connections 400V 3 phase 50 Hz Neutral FAUL RUN N L SL DP CL N RET Remove this link wire if 1 a switched live signal is connected 2 A ES PIR ES TC or BMS signal is connected Min Max SL run on Trickle Test 0 1 Pwr Standby Fan 1 ...

Страница 7: ...cable installation A 4 core SELV data cable is used to connect devices Do not run data cable in the same conduit as the mains cables and ensure there is a 50mm separation between the data cable and other cables The maximum cable run between any two devices is 300m when it is installed in accordance with the instructions Please note that the total data cable length used in any system must be less t...

Страница 8: ...itted between the suction header connection and the equalising line The recommendations of the TE valve manufacturer should be referred to when locating the phial and adjusting the superheat In all cases settings should be in accordance with the recommendations of the manufacturer of the refrigeration equipment All cooling coil drains must be connected to the sloping drain with a correctly sized t...

Страница 9: ... the fan operates Note The working adjustment of the fan speed by user control and sensors ranges between the minimum and maximum set points Note Where third party controls are specified and fitted ref erence should be made to the control specification and operat ing instructions It is the installer s responsibility to ensure that such controls are suitable for operation with the Nuaire equipment ...

Страница 10: ...nd brush sealants are all available as spare parts Checking drive belt tension To check the correct tension of a drive belt apply a force at right angles to the centre of the belt span sufficient to deflect the belt 16mm for every metre of span length The force required to deflect the V belt should be from 0 5kg to 0 8kg Changing a drive belt To replace a belt remove the two bolts from the motor m...

Страница 11: ...ls or by fixed installation detail eg ducting then guarding to the appropriate standard must be fitted 5 2 The electrical installation of the equipment must comply with the requirements of the relevant local electrical safety regulations 5 3 For EMC all control and sensor cables should not be placed within 50mm or on the same metal cable tray as 230V switched live lighting or power cables and any ...

Страница 12: ... Number 671424 Installation Operating and Maintenance Instructions XBOXER Run Around Coil Western Industrial Estate Caerphilly United Kingdom CF83 1NA T 029 2085 8400 F 029 2085 8444 E info nuaire co uk W www nuaire co uk ...

Отзывы: