8

18. 10. 17. Leaflet Number 671508

Installation, Operating and Maintenance Instructions

XBOXER 55

5.0 Wiring (Units with Ecosmart

Control)

The electrical wiring must be carried out by competent persons, in

 

accordance with good industry practice and should conform to all

 

governing and statutory bodies i.e. IEE, CIBSE, COHSE etc.

Connections 

a)

 

Control Connections

Net

 

- the 4 IDC plug-in connectors are provided for the connection

 

of compatible sensors, manual controls and for linking the fans

 

together under a common control. If more than 4 connections are

 

required, the junction box (product code ES-JB) should be used

(see data cable installation).

Switch Live (SL) terminal

 

- A signal of 100-230V a.c. will activate

 

the fan (required at each control). 

Note that a signal from an isolating transformer will produce

 

an unpredictable result and is not recommended.

b)

 

Damper Connections

OP

 

230V 50Hz 1A max supply to open the damper

CL

 

230V 50Hz 1A max supply to close the damper

N

 

Neutral supply to damper

RET 

-

 

230V ac return signal from the damper limit switch 

indicates

 

the damper has reached its operating position. 

If the return signal is not present, the fan will wait for 1 minute

 

before starting. 

Note: If a damper is not fitted, connect a link wire from OP to

 

RET. This will cancel the delay.

Where units are supplied in modular sections, it will be necessary to 

install and connect mains wiring between controls and devices

such as motorised dampers, it may also be necessary to install and 

connect mains wiring between sensors and actuators.

Depending on final damper location, extension of the cable looms 

may be required.

c) Volt Free Relay Contacts

Note that the volt free contacts are not fused.  If these are used to

power any external equipment, the installer must provide adequate

fusing or other protections. 

These contacts are rated at 5A resistive, 0.5A inductive.

Run connections

- These contacts are closed when the fan is 

running.

Fault connections

- No fault = the contacts are closed.

Fault

= the contacts are opened.

Heat demand - 

contacts closed when heating is selected.

d) Data Cable Installation

A 4-core SELV data cable is used to connect devices. 

Do not run data cable in the same conduit as the mains cables and

ensure there is a 50mm separation between the data cable and

other cables. The maximum cable run between any two devices is

300m when it is installed in accordance with the instructions.

Please note that the total data cable length used in any system

must be less than 1000m. Keep the number of cable joints to a

minimum to ensure the best data transmission efficiency

between devices.

e) Maximum Number of Devices

The maximum number of devices (including fans) that can be 

connected together via the cable is 32, irrespective of their functions.

f) Other Low Voltage Cables

Follow the basic principle (as d). Keep the cable run as short as

possible, less than 50 metres. Use screened cable if cable length is

more than 2m.

Electrical Details

Wiring with Ecosmart fan only control. Figure 14.

230V -  50Hz Supply

Local isolator (by others)

L

N

N

L

All inter-connections between circuit boards, blowers and 

sensors are made at the factory. This diagram only shows the 

essential field wiring points for clarity.

Damper Connections

Heat Demand 

Signal

Run 

Signal

Fault 

Signal

Damper Connections

Run 

Signal

Fault 

Signal

NET 

connections 

for Ecosmart 

devices

Min     Max    SL run 

  on

Trickle  

  Test

0  

  1

Link wire see note*

ES-CO2

Connection

BMS

Input

Signal

0-1

0V

0V

Ecosmart

Pwr

Standby

Fan 1

Fan 2

Heating

Cooling

Fault

Frost

TX

RX

Extract

N

E

L

SL

DP

CL

N

RET

Heat

Demand   Run 

  Fault

NET 

connections 

for Ecosmart 

devices

Min  

  Max    SL run 

  on

Trickle  

  Test

0  

  1

Link wire see note*

ES-CO2

Connection

BMS

Input

Signal

0-1

0V

0V

Ecosmart

Pwr

Standby

Fan 1

Fan 2

Heating

Cooling

Fault

Frost

TX

RX

Supply

N

E

L

SL

DP

CL

N

RET

Heat

Demand   Run 

  Fault

*Remove link wire if switched live signal, an enabler or BMS

signal is connected.

Wiring diagrams for units with Ecosmart Control

Fans without 

Fans with 

Electric Heater

Electric Heater

Unit

flc 

Unit

flc 

Code

(amps)

Code

(amps)

XB55-*N/L

2 X 3.5

XB55-*E

18.7

Содержание XBOXER 55 Series

Страница 1: ...014 3 U Nuaire A Trading Division of Polypipe Limited Western Industrial Estate Caerphilly United Kingdom CF83 1NA T 029 2088 5911 F 029 2088 7033 E info nuaire co uk W www nuaire co uk 1 18 10 17 Lea...

Страница 2: ...sphere 153 240 Side Silencer With Mixing Box 165 252 XBOXER 55 141 267 Roomside Silencer XBOXER 55 391 516 Ventilation Unit 1 3 Storage The equipment must be stored in a dry internal location Ductwork...

Страница 3: ...to be available adjacent to the units for future inspection maintenance repair and replacement Mark positions for mounting the ceiling brackets for each of the three units ensuring that the fixed bra...

Страница 4: ...g mounted brackets the units should be joined together using the supplied extrusion joining strips and screws see figure 8 When installing ceiling brackets ensure each one matches the specific units t...

Страница 5: ...the commissioned system operation 4 2 Heating Cooling Coils Water Water coils should be connected to ensure that full counter flow exists i e the entering airflow meets the return connection All water...

Страница 6: ...must not be operated unless control interlocks are in place damage to equipment may result Test run motor for condition and correct rotation Check that the correct current overloads are fitted and tha...

Страница 7: ...Atmospheric Silencer and Mixing Box Remove access panel pod and frame by sliding out to reveal terminal box for Mixing Box actuators Access panel Pod and insulation inside pod Figure 13b View of dampe...

Страница 8: ...nnections No fault the contacts are closed Fault the contacts are opened Heat demand contacts closed when heating is selected d Data Cable Installation A 4 core SELV data cable is used to connect devi...

Страница 9: ...factory This diagram only shows the essential field wiring points for clarity Remove link wire if switched live signal an enabler or BMS signal is connected Wiring with Ecosmart fan and LPHW coil cont...

Страница 10: ...ntrol connected in the system The voltage tolerance is _ 125mV and is measured at the fans terminal Ventilation Cooling Heating mode mode mode Local control 0 00 OFF trickle 0 25 Speed 1 0 50 0 75 1 0...

Страница 11: ...lectric Heater Electric Heater Unit flc sc kW flc Code amps amps watts amps XB55 2 X 3 5 2 X 3 5 4 5 18 7 Isolator by others N L N L 230V 50Hz 230V 50Hz Isolator by others Bypass Damper Power to open...

Страница 12: ...bypass L1 L N Supply Damper L N Switch or relay on to open bypass L1 L N Extract Damper L N Switch or relay on to open bypass L1 L N Mixing Damper Isolators and switches by others Wiring for 240V AC...

Страница 13: ...y be aggressive to aluminium should not be used Do not use cleaning water over 50 C Drain lines should be checked to ensure that they are unobstructed and free draining Traps should be checked that th...

Страница 14: ...prevented by the equipment panels or by fixed installation detail eg ducting then guarding to the appropriate standard must be fitted 5 2 The electrical installation of the equipment must comply with...

Отзывы: