WARNING - Before commencing work, electrically 

isolate the fan unit from the mains supply.

3

Leaflet Number 671281 March 2007

Installation and Maintenance

MVHR-LP Mechanical Ventilation with Heat Recovery

4.0 Setting to Work

Each fan is factory set to operate at trickle airflow when

power is applied and switch over to the boost flow rate

when a switched live signal is present. The pot marked ‘MIN

Airflow’ adjusts the trickle flow rate and the boost flow

rate by the pot marked ‘MAX Airflow’. These flow rates for

the supply and extract fan are adjusted separately. When

the switched live signal is removed, the fan will continue to

run at boost flow rate for a preset period as dictated by the

pot marked ‘RUN-on’.

Work out the required flow rate for the supply and extract

fans (these are usually supplied by the design consultant)

and adjust the approprate pots. If these figures are not

available, please refer to the typical settings below.

No. of 

Typical volume of

Trickle/normal

Boost

Bedrooms

ventilated space

flow rate l/s*

flow rate l/s*

1

140m

3

19

24

2

200m

3

28

35

3

260m

3

36

45

4

320m

3

44

56

*These figures are given as a general guide. They should only

be used if actual design figures are not available.

5.0 Run-on Timer

The Run-on timer adjustment is from 0 - 60 mins.

Run-on

is only available from the switched live (SL) signal.

5.1 Start-up Routine

On power up or and after power failure the unit goes

through a 2 minute set-up period. 

During this period the unit:

1.Starts at full speed

2.Ramps down to off

3.Restarts at 25% speed

4.Resumes normal operation

5.2 Status Light

Green light - Fan running

Red light - Fan failure

Flashing green light - Set-up period

Flashing red light - Electronics failure

5.3 Calibration

By pressing the calibration button the unit re-sets itself by

switching off for 30 seconds then re-starts at full speed

before ramping down to the desired duty. Whilst running at

full speed the status light flashes to indicate if the duty set

on the adjustment dials can be achieved (green for yes,

amber for no). Checks can be carried out in both the trickle

and boost modes. If the light flashes amber check the 

resistance of the ducting, grilles etc. or turn down the

adjustment dial.

6.0 Maintenance

It is inevitable that even with filtered extract grilles as 

recommended in BRE digest 398 some dust, fluff etc. will

pass through the filter, and which, if allowed, will build up

internally on motors and impellers, shortening the life of 

the unit and, in severe cases, leading to overheating of the

motors. Consequently, it is strongly recommended that all

units are inspected and cleaned every six months.  

7.0 Cleaning 

Remove covers and carefully clean out interiors as 

necessary. To clean the filter, remove from the unit and

wash in tepid water to which a little mild detergent has

been added.  Shake out excess water and allow to dry 

naturally.  Replace when dry. Check for damage and 

security of components. Refit covers.

8.0 Replacement of Parts

Should any component need replacing Nuaire keep extensive

stocks for quick delivery. Ensure that the unit is electrically

isolated, before carrying out any work. 

When ordering spare parts, please quote the serial number

of the unit and the ARC number of the purchase if possible.

(This information will be available on the fan label).

9.0 Warranty

The 5 year warranty starts from the day of delivery and

includes parts and labour. This warranty is conditional on

planned maintenance being undertaken.

10.0 Service Enquiries

Nuaire can assist you in all aspects of service. Our service 

department will be happy to provide any assistance required,

initially by telephone and If necessary arrange for an 

engineer to call.

Customer Services Department 

on 08705 002 555

Содержание MVHR-LP

Страница 1: ...ust be carried out by competent personnel in accordance with the appropriate authority and conforming to all statutory and governing regulations The fan must be fitted indoors away from any direct sources of heat water spray or moisture generation Temperature range 5OC to 40OC The integral mounting bracket supplied can be offered up to position the fixing points marked through and the bracket inst...

Страница 2: ...live input pre wired to terminal box Terminal 1 for extract fan Terminal 2 for supply fan 3 0 Electrical Wiring 3 1 Additional Control Wiring Option Other control wirings are available on each fan Open the cover of the unit to gain access to these connections on each fan see figure 7 N L 2 1 L N E 230V 50Hz Factory fitted links N L 1 2 3A fuse Isolator by others N L 2 1 L N E 230V 50Hz Remove fact...

Страница 3: ...nit re sets itself by switching off for 30 seconds then re starts at full speed before ramping down to the desired duty Whilst running at full speed the status light flashes to indicate if the duty set on the adjustment dials can be achieved green for yes amber for no Checks can be carried out in both the trickle and boost modes If the light flashes amber check the resistance of the ducting grille...

Страница 4: ...nit is considered Lifting gear such as slings or ropes must be arranged so as not to bear on the casing 3 3 Equipment stored on site prior to installation should be protected from the weather and steps taken to prevent ingress of contaminants 4 0 OPERATIONAL LIMITS 4 1 It is important that the specified operational limits for the equipment are adhered to e g operational air temperature air borne c...

Отзывы: