Installation and Maintenance

The MRXBOXAB-ECO4-1Z Range of Units

2.2 Optional Wall Mounting

The MVHR unit fixed to a solid wall construction using a suitable 

mounting structure (supplied by others).

Ducting in the 

ceiling void.

Side view of unit 

mounted on the

solid wall in a 

cupboard using 

MVHR-DRAIN

suitable mounting 
structure.

Condensate drain,

uninsulated drain 

pipe with min 5

o

 fall 

running to SVP.

Valve in ceiling.

Unit weight 

= 115kG

Mounting frame 
not supplied

Figure 4. Typical example of a cupboard mounted unit (Standard 

unit) fixed to a block work wall.

2.4 Condensate Drain

An additional straight multi-fit connector is included with the ancillary 

items supplied to extend the condensate drain connection of the MVHR 

unit outside the enclosure. The threaded connector should be coupled 

to the corresponding connection of the MVHR unit through the square 

cut out in the base panel of the enclosure.  Care should be taken to not 

over tighten this joint as this may result in the inner drain connection 

coming loose making removal difficult if required in the future.
The threaded nut can then be removed from the multi-fit connector 

and the adhesive backed cover plate passed over the multi-fit 

connector and affixed to the enclosure base panel, see Figure 6.

2.3 Transportation Fixings

To prevent damage during transit and installation, the product is 

shipped with two transportation brackets, these are attached to the 

upper screws of the MVHR front pa

nel (Figure 5)

.  These brackets must 

be removed before use, failure to do so will result in excessive vibration 

and noise. The screws securing the bracket to the side panel of the 

enclosure can be removed and discarded, the remaining screws securing 

the bracket to the MVHR unit can be loosened allowing the bracket to 

be removed before fully tightened to secure the panel in place.

2.1 Mounting the MVHR Unit

Due to the size and weight of the unit, floor mounting is the preferred 

mounting method. If this is not possible a solid wall is required, 

however, a structural engineer should be consulted. A gypsum block/

plasterboard wall will not suffice.

 

The unit is not supplied with any mounting brackets; a suitable 

mounting structure with means of securing the unit in place is 

required.  

Four female M8 fixing points are available in the base panel 

of the enclosure to be used to secure the unit in place, for details of 

these along with compulsory support areas and features that should be 

accommodated within the mounting structure, see Figure 3.
No part of the enclosure should be in contact with the building 

structure, the only components that should be in contact are those 

used to provide the mounting structure.

Note: Care must be taken to ensure the unit is installed true in 

all 3 dimensions. Failure to do so may result in overflow from the 

internal condensation drip tray.

IMPORTANT

The unit must remain switched on at all times to maintain 

ventilation within the dwelling. Turning the unit off will cause long 

term damage to the unit and building fabric.

This appliance is not intended for use by persons (including children) 

with reduced physical, sensory or mental capabilities, or lack of 

experience and knowledge, unless they have been given supervision 

or instruction concerning the use of the appliance by a person for their 

safety. Children should be supervised so that they do not play with 

the appliance.

A

A

Transportation 
bracket

B

B

Multi-fit 

Connector

Cover Plate

Enclosure 
Base Panel

Figure 5. Transportation fixings

Figure 6. Condensate connections

Содержание MRXBOXAB-ECO4-1Z

Страница 1: ... appropriate standards Ensure that the mains supply Voltage Frequency and Phase complies with the rating label Please note a clear working space is required around the installed unit to allow the cover to be removed and provide sufficient access for maintenance such as filter change A minimum of 480mm is required in front of the unit The fan must be installed indoors on a suitable structure away f...

Страница 2: ...of the enclosure can be removed and discarded the remaining screws securing the bracket to the MVHR unit can be loosened allowing the bracket to be removed before fully tightened to secure the panel in place 2 1 Mounting the MVHR Unit Due to the size and weight of the unit floor mounting is the preferred mounting method If this is not possible a solid wall is required however a structural engineer...

Страница 3: ...ation 6 l s Number of bedrooms in dwelling 1 2 3 4 5 Whole dwelling ventilation rate l s 1 2 13 17 21 25 29 1 The condensate must be discharged under a water level in a U trap drainpipe or an alternative drain method which acts as an airlock 2 The condensate discharge drain is a 32mm male threaded connection 3 If using a U trap please ensure the U trap has been filled to a suitable level of water ...

Страница 4: ...ons given in ADF 2010 can be used where security is not an issue In this case minimum high extract rate for the sanitary accommodation should be omitted from the step 2 calculation Step 3 The required airflow rates are as follows The maximum whole dwelling extract ventilation rate e g boost should be at least the greater of step 1 and step 2 Note that the maximum individual room extract rate shoul...

Страница 5: ...ms in ceilings via AirValve Insulated extract duct Insulated extract duct MVHR unit Nuaire MVHR DRAIN Condensate drain uninsulated drain pipe with min 5 o fall running to SVP MVHR unit Nuaire MVHR DRAIN Condensate drain uninsulated drain pipe with min 5 o fall running to SVP Exhaust air from kitchen bathroom to outside via air brick Minimum distance as specified in building regulations Intake air ...

Страница 6: ...ples Of Typical Wiring Layouts MAINS 230V 50Hz N L 3 Position Switch Ancillary code MRXBOX95 3SWITCH Blue Green yellow Brown Black Supply cord from unit Grey L 1 2 Fuse 5A MAINS 230V 50Hz N L 3 Pole Isolator 3 Position Switch Ancillary code MRXBOX95 3SWITCH Blue Green yellow Brown Black Supply cord from unit Grey L 1 2 Fuse 5A 2 Pole Isolator light Room Light switch Double Pole MAINS 230V 50Hz N L...

Страница 7: ...emoving front cover C C Ecosmart Connector Removable Plate 1 For required air flow rates please refer to the design specification for the property follow 2 4 or refer to building regulations ADF 2010 2 The unit should be run for a minimum of 10 minutes to reach steady state before commencing commissioning 3 The humidity sensor is initially set to its least sensitive position this should be adjuste...

Страница 8: ...as standard the supply fan will reduce to minimum speed Once the temperature rises above the set point the fan will return to its commissioned speed Please note this mode will only activate after ten days of continuous run time If commissioning of the unit is outside of this timeframe please notify the after sales department prior to site visit Nuaire recommend that filters are inspected every 6 m...

Отзывы: