MRXBOXAB-ECO4-1Z (Standard Unit) 
MRXBOXAB-ECO4-1Z-OH (Opposite hand Unit) 

Mechanical Ventilation Units with Heat Recovery

 

Installation and Maintenance

The EMC Directive

 

2014/30/EU

The Low Voltage 
Directive

2014/35/EU

1.0 INTRODUCTION

The ECO4-1Z range of units are designed to offer improved sound 

levels and an aesthetically pleasing installation by housing a 

Mechanical Ventilation with Heat Recovery (MVHR) unit and 

attenuator inside an acoustically lined enclosure. 

The MVHR unit is fitted with two independent fans to provide 

mechanical supply and extract ventilation, each fan has full speed 

control for background and boost ventilation rates. To recover heat 

from the extract air, the heat exchanger block is utilised. The heat 

exchanger can recover up to 95% of the normally wasted heat.

The units also incorporate an integral humidistat and frost protection, 

see sections 7.1 & 9.1 for details.

The unit is not supplied with any mounting brackets; a suitable 

mounting structure with means of securing the unit in place is 

required.

2.0 INSTALLATION

Installation must be carried out by competent personnel in accordance 

with the appropriate authority and conforming to all statutory 

governing regulations. All mains wiring must be in accordance with the 

current I.E.E. Regulations, or the appropriate standards. Ensure that the 

mains supply (Voltage, Frequency and Phase) complies with the rating 

label. 
Please note a clear working space is required around the installed unit 

to allow the cover to be removed and provide sufficient access for 

maintenance such as filter change. A minimum of 480mm is required in 

front of the unit.
The fan must be installed indoors, on a suitable structure away from 

direct sources of frost, heat and water spray or moisture generation. For 

a vibration-free result the unit must be mounted to a solid structure.

Intake air 

from outside

Extract air 

from house

to house

Supply air 

Exhaust air 

from house

to outside

Extract air 

from house

Intake air 

Exhaust air 

from outside

from house

to outside

Supply air 

to house

Figure 1. Airflow through unit (Standard unit).

Figure 2. Airflow through OH unit (Opposite hand unit).

=

=

=

726

=

41

0

10

143

48

48

38

70

60

Summer / Winter Cable entry point.

Mains Cable Connection

Note: 
Any Items being accomodated in structure design should 
include sufficient clearance to allow for assembly tolerances 
and for ease of installation when positioning on site.

43

43

21

Condensate drain connection

(standard hand configuration). 

For opposite hand configuration position 

will be mirrored to the other side.

4x M10 Flanged head bolts 
protruding from base to be 

accomodated in structure design.

2x Rivet Heads

4x M8 Mounting Points

2x Hatched regions details 
compulsory support areas, 
further support may be required 
depending on structure design 
(supplied by others).

Figure 3. Mounting point locations.

Содержание MRXBOXAB-ECO4-1Z

Страница 1: ... appropriate standards Ensure that the mains supply Voltage Frequency and Phase complies with the rating label Please note a clear working space is required around the installed unit to allow the cover to be removed and provide sufficient access for maintenance such as filter change A minimum of 480mm is required in front of the unit The fan must be installed indoors on a suitable structure away f...

Страница 2: ...of the enclosure can be removed and discarded the remaining screws securing the bracket to the MVHR unit can be loosened allowing the bracket to be removed before fully tightened to secure the panel in place 2 1 Mounting the MVHR Unit Due to the size and weight of the unit floor mounting is the preferred mounting method If this is not possible a solid wall is required however a structural engineer...

Страница 3: ...ation 6 l s Number of bedrooms in dwelling 1 2 3 4 5 Whole dwelling ventilation rate l s 1 2 13 17 21 25 29 1 The condensate must be discharged under a water level in a U trap drainpipe or an alternative drain method which acts as an airlock 2 The condensate discharge drain is a 32mm male threaded connection 3 If using a U trap please ensure the U trap has been filled to a suitable level of water ...

Страница 4: ...ons given in ADF 2010 can be used where security is not an issue In this case minimum high extract rate for the sanitary accommodation should be omitted from the step 2 calculation Step 3 The required airflow rates are as follows The maximum whole dwelling extract ventilation rate e g boost should be at least the greater of step 1 and step 2 Note that the maximum individual room extract rate shoul...

Страница 5: ...ms in ceilings via AirValve Insulated extract duct Insulated extract duct MVHR unit Nuaire MVHR DRAIN Condensate drain uninsulated drain pipe with min 5 o fall running to SVP MVHR unit Nuaire MVHR DRAIN Condensate drain uninsulated drain pipe with min 5 o fall running to SVP Exhaust air from kitchen bathroom to outside via air brick Minimum distance as specified in building regulations Intake air ...

Страница 6: ...ples Of Typical Wiring Layouts MAINS 230V 50Hz N L 3 Position Switch Ancillary code MRXBOX95 3SWITCH Blue Green yellow Brown Black Supply cord from unit Grey L 1 2 Fuse 5A MAINS 230V 50Hz N L 3 Pole Isolator 3 Position Switch Ancillary code MRXBOX95 3SWITCH Blue Green yellow Brown Black Supply cord from unit Grey L 1 2 Fuse 5A 2 Pole Isolator light Room Light switch Double Pole MAINS 230V 50Hz N L...

Страница 7: ...emoving front cover C C Ecosmart Connector Removable Plate 1 For required air flow rates please refer to the design specification for the property follow 2 4 or refer to building regulations ADF 2010 2 The unit should be run for a minimum of 10 minutes to reach steady state before commencing commissioning 3 The humidity sensor is initially set to its least sensitive position this should be adjuste...

Страница 8: ...as standard the supply fan will reduce to minimum speed Once the temperature rises above the set point the fan will return to its commissioned speed Please note this mode will only activate after ten days of continuous run time If commissioning of the unit is outside of this timeframe please notify the after sales department prior to site visit Nuaire recommend that filters are inspected every 6 m...

Отзывы: