NuAire MRXBOXAB-ECO2-AESW Скачать руководство пользователя страница 2

2

nuaire.co.uk 

029 2085 8400

04. 11. 19. Leaflet Number  671859

Installation and Maintenance

MRXBOXAB-ECO2-AESW Mechanical Ventilation Unit with Heat Recovery

2.3 Option 1: Wall Mounting

The MVHR unit fixed to a solid wall construction using the 

mounting bracket provided.

2.4 Option 2: Wall Mounting

If it is not practical to use a solid wall, the unit should be fixed to a 

stud partition with a 25mm minimum thickness MDF panel solidly 

fixed behind the plasterboard.

If fixing to a stud wall the MDF panel should extend, width wise, over 

a minimum of 3 vertical studs with centres of no more than 400mm. 

A vertical stud should be located to correspond with the position each 

mounting bracket is to be fixed to provide additional support.
Add additional vertical supports if necessary. Height wise, the MDF 

panel should extend from floor to ceiling.
Fix the mounting bracket to the wall (as fig. 4) and use the wall 

mounted bracket to mount the unit on (as shown in fig. 6).

Ducting in the 
ceiling void.

Side view of unit 
mounted on the
block wall in a 
cupboard using 

MVHR-DRAIN

the wall brackets.

Condensate drain,
uninsulated drain 
pipe with min 5

o

 fall 

running to SVP.

Valve in ceiling.

Unit weight 

= 45kG

Figure 5. Typical example of a cupboard mounted unit (Standard 

unit) fixed to a block work wall.

Ducting in the 
ceiling void.

Side view of unit 
mounted in a 

with the 25mm 

cupboard fixed to 
a stud partition

MDF fixed behind 
the plasterboard
using the wall 

MVHR-DRAIN

brackets. 

Condensate drain,
uninsulated drain 
pipe with min 5

o

 fall 

running to SVP.

Valve in ceiling.

Unit weight 

= 45kG

Figure 6. Typical example of a cupboard mounted unit (Standard 

unit) fixed to a stud partition with the MDF panel fixed behind the 

plasterboard.

2.5 Condensate Drain

The MVHR unit inside the enclosure is fitted with a straight coupling to 

allow 21.5mm overflow pipe (not supplied) to be attached using solvent 

cement, the pipe should be passed through the flexible adhesive backed 

cover plate before the solvent cement is applied.
The pipe can then be inserted into the coupling of the MVHR unit and 

the cover plate slid along the length to bond against the base panel of 

the enclosure preventing noise breakout (fig. 7).

1. The condensate must be discharged under a water level in a U-trap 

drainpipe or an alternative drain method which acts as an airlock. 

2. This condensate discharge connection is suitable for 21.5mm dia. 

overflow pipe. Solvent cement should be used to make the joint. 

3. If using a U-trap please ensure the U-trap has been filled to a 

suitable level of water to avoid any air locks.

4. If the condensation pipe is fitted in an unheated space the pipe 

should be in insulated to prevent freezing.

Nuaire recommend MVHR-DRAIN be used as the primary 

condensate take-off. (see figure 9 and 10).

Min 5

Drop

Collar

To SVP 

“T” piece 

MVHR Drain 

To unit 

To CONTRAP 

Solvent cement to be applied

Flexible adhesive backed 
cover plate

Overflow pipe

Figure 7.  

Figure 8. Wet option: 

Condensate pipe connection 

to unit and a typical 

example of a “U” trap 

drainpipe 

(Standard 

configuration only).

Figure 9. MVHR-DRAIN option: Condensate 

drain, uninsulated drain pipe with min 5° fall 

running to SVP.

Figure 10. IMPORTANT: When using a “T” Piece to connect the 

CONTRAP drainage and the MVHR drain pipework the MVHR 

drain must always be fitted before the “T” Piece to prevent 

condensate from feeding back into the MVHR system.

Содержание MRXBOXAB-ECO2-AESW

Страница 1: ...n with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning the use of the appliance by a person for their safety Children should be supervised so that they do not play with the appliance 2 1 Transportation fixings To prevent damage during transportation the product is shipped with securing fixings the...

Страница 2: ...ical example of a cupboard mounted unit Standard unit fixed to a stud partition with the MDF panel fixed behind the plasterboard 2 5 Condensate Drain The MVHR unit inside the enclosure is fitted with a straight coupling to allow 21 5mm overflow pipe not supplied to be attached using solvent cement the pipe should be passed through the flexible adhesive backed cover plate before the solvent cement ...

Страница 3: ...outside of the outside air inlet duct and the air outlet duct from the unit these ducts should be insulated Ducting must be installed in such a way that resistance to airflow is minimised Bends should be kept to a minimum A minimum distance of 300mm between the appliance and any bends in ductwork is recommended Ideally 125mm diameter or 220 x 90mm rectangular ducting should be used Refer to dwelli...

Страница 4: ...step 1 and step 2 Note that the maximum individual room extract rate should be at least those given in table 1 The minimum air supply rate should be at least the whole building ventilation rate found in step 1 For Scotland refer to BRE Digest 398 For further information refer to Domestic Ventilation Compliance Guide www planningportal gov uk buildingregulations approved documents partl compliance ...

Страница 5: ... duct 4 0 DUCTING ARRANGEMENTS STANDARD CONFIGURATION Figure 12 Typical ducted arrangement for a wall mounted unit using circular ducting Figure 13 Typical ducted arrangement for a wall mounted unit using rectangular ducting Air supply to lounge in ceilings via AirValve Extract air from kitchen bathroom in ceilings via AirValve Exhaust air from kitchen bathroom to outside via louvre grille Minimum...

Страница 6: ...ions in fig 14 are factory fitted The unit is pre wired with a 2 metre fly lead Fuse 2A MAINS 230V 50Hz light Room Light switch Double Pole N L 3 Pole isolator Kitchen switch Blue Brown Black Optional 3 speed switch Supply cord from unit Grey Green yellow Fuse 2A MAINS 230V 50Hz Room lights Light Double switches Pole N L 3 Pole isolator Kitchen switch Blue Green yellow Brown Black Supply cord from...

Страница 7: ...or is measuring humidity from all the wet rooms at the same time and should not be relied on to solely boost the unit Additional switch should be used local to the wet rooms see wiring diagrams Nuaire recommend that filters are inspected every 6 months and replaced every 12 months A flashing LED section 7 0 will indicate that a filter change is required This indication repeats every 12 months and ...

Страница 8: ...our for the first year and parts only for the remaining 4 years This warranty is void if the equipment is modified without authorisation is incorrectly applied misused disassembled or not installed commissioned and maintained in accordance with the details contained in this manual and general good practice The product warranty applies to the UK mainland and in accordance with Clause 14 of our Cond...

Отзывы: