NuAire MRXBOXAB-ECO-LP2OHSW Скачать руководство пользователя страница 3

3

18. 02. 21. Document Number  671876

Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk

MRXBOXAB-ECO-LP2SW

Installation Manual

3.3 Ducting Installation

Before commencing ducting installation reference should be made 
to building regulations document “Domestic ventilation compliance 
guide”. This document supports ADF2010 and details installation, 
testing and commissioning of all ventilation systems.

It is recommended that rigid ducting must be used it all times. Flexible 
ducting has a very high resistance and it is impossible to calculate 
how much resistance will be on a system if used. If used the flexible 
ducting must be kept to a minimum and should always be pulled taut. 
A maximum of 300mm should be used on each leg.

To prevent condensation on the outside of the outside air inlet duct and 
the air outlet duct from the MRXBOXAB-ECO-LP2, these ducts should 
be insulated.

Ducting must be installed in such a way that resistance to airflow is 
minimised. Bends should be kept to a minimum.

A minimum distance of 300mm between the appliance and any bends 
in ductwork is recommended.

204 x 60mm rectangular ducting should be used (refer to dwelling 
ducting design drawing, Figures 8 & 10 for further information).

Ducting joints must be sealed with silicone type sealant and needs 
to be taped. Ducting shall be adequately and reliably fixed to the 
appliance.

3.4 Ventilation Flow Rates

Any air intake terminal MUST be installed in accordance with the 
appropriate regulation.

As a guide, the BS5440 series of British Standards deals with this 
issue and currently states that an air intake must be at a minimum 
distance of 300mm from a gas boiler balanced flue.

Installers are advised to be aware of the requirements of this 
standard when installing ‘through the wall’ supply air ducting.

3.4.1 ADF 2010 - Extract Ventilation Rates

 

Room

Min high rate

Min low rate

Kitchen

13 l/s

Total extract rate 

should be at least 

the whole dwelling 

ventilation rate given 

in table 2.

Utility Room

8 l/s

Bathroom

8 l/s

Sanitary 

Accommodation

6 l/s

3.4.2 Whole Dwelling Ventilation Rates

 
 

Number of bedrooms in dwelling

1

2

3

4

5

Whole dwelling 
ventilation rate 
(l/s)

1,2

13

17

21

25

29

1. In addition, the minimum ventilation rate should be no less than 
0.3 l/s per m2 of internal floor area.  (This includes all floors, e.g. 
for a two-story building add the ground and first floor areas).

2. This is based on two occupants in the main bedroom and a single 
occupant in all other bedrooms. This should be used as the default 
value. If a greater level of occupancy is expected add 4 l/s per 
occupant.

Typical Condensate Pipe Connection Using MVHR-DRAIN 
Ancillary

 

CORRECT

INCORRECT

Flow

Side elevation

When installed horizontally the ribs must be at the bottom to 
ensure  correct operation. 

MVHR-DRAIN Installation

3.1.1 MVHR-DRAIN Installation

Offer up the MVHR-DRAIN inlet to the threaded tail of the appliance 
waste outlet or MVHR-DRAIN knuckle or running adaptor, and tighten 
the threaded cap sufficiently hand-tight to provide a water-tight seal 
(check that the cap screws on square and does not ‘cross-thread’). 
When the screwed cap is tight, the MVHR-DRAIN body is secure.

Cut the pipe to length, allowing for the full compression socket 
depth (using an appropriate pipe cutter, such as a Hepworth 
ratchet pipe cutter).

Remove any ‘swarf’ from the end of the plastic pipe. Ream the 
copper pipe end to remove any ‘burr’, and file if necessary to 
remove any external sharp edges. Mark the socket depth on the 
pipe, and check that the pipe section to be jointed is free of any 
surface damage which may affect the joint seal.

Unscrew the cap from the MVHR-DRAIN outlet, and slide the cap 
and rubber seal onto the pipe.

Insert the pipe end fully into the socket.

Slide the rubber seal and screwed cap up against the face of the 
socket, and tighten the cap sufficiently hand-tight (check that the 
cap is square to the body and does not ‘cross thread’). Hand tight 
should be adequate to form a proper seal.

3.2 Extract & Supply Areas

The unit is designed to extract air from all wet rooms e.g. bathroom, 
kitchen, en-suite, utility room (with sink).

WC’s do not need to be ventilated if openable windows are fitted.

Supply air should be to all habitable rooms e.g. bedrooms and lounge. 
Extract & Supply grilles should be adjustable valve types (not supplied).

External grilles must have a minimum free area of 12,250 mm

2

.

Содержание MRXBOXAB-ECO-LP2OHSW

Страница 1: ...ven supervision or instruction concerning the safe use of the appliance by a person responsible for their safety Children shall not play with the appliance Cleaning and user maintenance shall not be c...

Страница 2: ...is required around the installed unit to allow the cover to be removed and provide sufficient access for maintenance such as filter change The fan must be installed indoors in a suitable ceiling void...

Страница 3: ...r of bedrooms in dwelling 1 2 3 4 5 Whole dwelling ventilation rate l s 1 2 13 17 21 25 29 1 In addition the minimum ventilation rate should be no less than 0 3 l s per m2 of internal floor area This...

Страница 4: ...be at least those given in table 1 for minimum high rate The minimum air supply rate should be at least the whole building ventilation rate found in step 1 For Scotland refer to BRE Digest 398 For fu...

Страница 5: ...k Supply and extract ducts from external air bricks to the unit needs to be insulated Top of ceiling void Minimum distance as specified in Building Regulations Intake air from outside via air brick 3...

Страница 6: ...to the mains supply 4 1 Electrical Information Electrical details Voltage 240V 1ph 50Hz Consumption 1 3 Amp This unit must be earthed The cable from the mains power supply should be connected to a fix...

Страница 7: ...ontrol has an adhesive panel which should be removed post commissioning to prevent tampering Control module Speed 1 Speed 2 Speed 1 Speed 2 15 Commissioning Controls 6 0 CONTROLS 6 1 Integral Automati...

Страница 8: ...nd general good practice The product warranty applies to the UK mainland and in accordance with Clause 14 of our Conditions of Sale Customers purchasing from outside of the UK should contact Nuaire In...

Отзывы: