Installation and Maintenance

MRXBOX95B-WM2 Mechanical Ventilation with Heat Recovery & Summer Bypass

The filters fitted inside the unit are protected with a 

plastic film. Prior to commissioning remove the covers

(fig 13), take off the film and replace.

Figure 11. Detail of unit control
on front panel.  

Filter covers

Figure 12. Removing
the two filter covers
on the front panel of
the unit.

Filter being 
removed

Filter cover

Figure 13.The filters
can be removed by
pulling on the black
tab on the visible end
of the filters.

Technical or commercial considerations may, from time to time, make it necessary to alter the design, performance and 

dimensions of equipment and the right is reserved to make such changes without prior notice.

Isolation - Before commencing work make sure that the 

unit, switched live and Nuaire control are electrically 

isolated from the mains supply and switched live supply. 

6.0 Commissioning

1. For the required air flow rates please refer to the design 

specification for the property, follow 2.4, or refer to building 

regulations ADF 2006/2010.

2. The unit is supplied with independent control for both normal 

and boost airflows. (see fig. 11). 

3. Correct commissioning is essential to ensure the ventilation 

air flowrates are met. It also ensures the unit is not over 

ventilating and causing excessive power consumption. 

4. Commissioning should be carried out in accordance with 

building regulations document “Domestic ventilation 

compliance guide”. A calibrated moving vane anemometer 

and hood will be required to carry out commissioning.

5. Adjustment valves should be locked in place to prevent 

further adjustment. 

6. Once commissioned the home owner / tenant should be 

informed that the unit should not be adjusted as it will have 

a detrimental effect on the indoor air quality and could result 

in condensation and mould growth. The label covering the 

control has an adhesive panel which should be removed post 

commissioning to prevent tampering.

6.1 Summertime boost facility

The unit has to ability to override both the trickle and boost

speeds to operate the fan to maximum airflow. See wiring 

diagram for details of operating this facility.

7.0 Maintenance/Cleaning

We recommend that the two G3 fiters are inspected after 

6 months, and replaced every 12 to 18 months.

The filters can be removed from the unit by removing the two

filter covers on the front panel of the unit. Take hold of the two

circular tabs either end of the filter covers and pull out.

The filter can now be extracted by pulling the removal loop on

the front edge of the filter. Once the filters have been inspected

return or replace them as necessary.

Inspect the heat exchanger every 5 years. Generally check 

for damage and security of components. Refit cover.

8.0 Replacement of Parts

Should any component need replacing Nuaire keep extensive

stocks for quick delivery. Ensure that the unit is electrically 

isolated, before carrying out any work.

Note: The supply cable must be replaced by an electrically 

competent person. 

When ordering spare parts, please quote the serial number 

of the unit and the ARC number of the purchase if possible.

(This information will be available on the fan label).

9.0 Warranty

The 5 year warranty starts from the day of delivery and

includes parts and labour for the first year and parts only for

the remaining 4 years. This warranty is conditional on planned

maintenance being undertaken

.

10.0 Service Enquiries

Nuaire can assist you in all aspects of service. Our service 

department will be happy to provide any assistance required, 

initially by telephone and If necessary arrange for an 

engineer to call.

Technical Support

on 029 2085 8400

Содержание MRXBOX95B-WM2

Страница 1: ...the installed unit to allow the cover to be removed and provide sufficient access for maintenance such as filter change Please allow a minimum of 350mm in front of the unit The fan must be installed...

Страница 2: ...le valve types not supplied External grilles to have a minimum free area of 12 250 sq mm 2 3 Ducting Before commencing ducting installation reference should be made to building regulations document Do...

Страница 3: ...boost should be at least the greater of step 1 and step 2 Note that the maximum individual room extract rate should be at least those given in table 1 for minimum high rate the minimum air supply rate...

Страница 4: ...ated supply duct Insulated supply duct Minimum 300mm Air supply to lounge via Air Valve Part no V125S in ceilings Extract air from kitchen bathroom via Air Valve Part no V125S in ceilings Air supply t...

Страница 5: ...Pole isolator 3 Pole isolator Kitchen switch Kitchen switch Blue Brown Black Optional summer boost switch Supply cord from unit Green yellow Blue Brown Black Supply cord from unit Optional summer boos...

Страница 6: ...ot be adjusted as it will have a detrimental effect on the indoor air quality and could result in condensation and mould growth The label covering the control has an adhesive panel which should be rem...

Страница 7: ...nge speed This is normal and will have no adverse effect on the fan The speed will return to normal once the interference has subsided 5 0 INSTALLATION REQUIREMENTS In addition to the particular requi...

Страница 8: ...ings assessed under The Building Regulations 2010 specifically SAP 2009 and Approved Documents L and F Completion of this document is therefore only required for dwellings assessed by SAP 2005 Custome...

Страница 9: ...r to overcome particular obstructions If flexible ducting has been used has it been pulled taut to minimise system resistance Has the number of duct bends been minimised to ensure adequate air flow an...

Страница 10: ...y unit been fixed to a stable element of the building fabric e g wall or floor using manufacturer recommended supplied fixing brackets Has the condensation drain been fitted and the pipe insulated Hav...

Страница 11: ...or N A Has the rating label been verified to establish suitability for the installation strategy and whether an earth is required e g voltage class I or II product status Has a local isolator been pro...

Страница 12: ...tion grilles been locked where possible to minimise unapproved occupant adjustment Figure 3 Ensure all external and internal windows and doors are closed Set fan speed using manufacturer data table Se...

Страница 13: ...e customer been advised that opening windows is not recommended during normal use in order to ensure the energy efficient operation and performance of the balanced system Has the customer been advised...

Отзывы: