NuAire MRXBOX95B-450 WC Скачать руководство пользователя страница 6

6

27. 11. 17. Leaflet number 671617

Installation and Maintenance

MRXBOX95B-450 WC and MRXBOX95B-450

5.0 Wireless control

Note:  This process should only be carried out by a competent and
qualified person. 

The wireless control comes pre-set, if for any reason this needs to be
repeated e.g. a replacement switch required the following steps
should be followed.  The unit needs to be powered to carry this out,
care should be taken of live electrics while carrying out the task.

Step 1.

Remove the cover from the wireless receiver on top of the 
unit using a terminal screwdriver.

Step 2.

Press and hold push button M4 so that the buzzer sounds 
continually, while it sounds press one of the buttons on the
switch that is to be paired.  Repeat this process for any 
additional switches that are to be paired.

Step 3.

The system should now be fully functional and the cover 
can be re-fitted.

The duration of the timed boost may be adjusted between 
5 - 30 mins using the trimmer as shown in fig 13. below.

A diagram of the wireless receiver is shown below, this is for reference
only as the unit comes pre-wired.

Figure 13. Wireless receiver.

5.2 Ecosmart controls

A maximum of two Ecosmart sensors can be connected directly to the 
main circuit board, this can be done by cutting a small slit in the

 

20mm grommets situated on the top of the unit, the cable can then

 

be threaded through to gain access to the connections on the PCB.  If 
more than 2 connections are required an Ecosmart junction box will

 

be required.

When a sensor is activated the unit will switch to speed 3 and run-on

 

for 15 minutes after the signal is lost. Some sensors may also have

 

additional optional run-on features.

M1 

Antenna input
(wire 8.5cm)

FUSE 10A

L2

FUSE 10A

L3

FUSE 10A

L4

M4

MT 

5.1 Switches

The wireless switch is supplied with a battery but this is not fitted, to

 

fit the battery pull out the carrier at the base of the switch and insert

 

the battery with the text facing you.

To fix either switch to a wall or back box remove the front fascia by 
inserting a terminal screwdriver into the two openings along the 
bottom edge and prize open gently.  The fixing points on the back

 

plate can then be accessed, once the switch has been secured the

 

front fascia can then be re-fitted.

Note:  The wireless switch will typically operate up to a distance of

 

30m inside a building, however, this is dependent on the layout

 

and 

construction of the building. This distance will be reduced 
depending on obstructions e.g. walls.  If the switch will not operate

 

an additional wire aerial is supplied attached to the outside of the

 

receiver cover, if required this can be fitted under the dome nut of

 

the receiver and should point vertically skywards.

The filters fitted inside the unit are protected with a 

plastic film. Prior to commissioning remove the covers (fig 13), take off

the film and replace.

6.0 Commissioning

1. 

The unit should be run for a minimum of 10 minutes to reach

steady state before commencing commissioning.

2.

The humidity sensor is initially set to its least sensitive position, this

should be adjusted during commissioning.  Depending on storage
and site conditions the unit may boost due to high relative
humidity levels, this will continue until the level drops below the
specified set point.

3.

The unit is supplied with independent control for both normal and
boost airflows. (see fig. 14). 

4.

Correct commissioning is essential to ensure the ventilation air
flow rates are met. It also ensures the unit is not over ventilating
and causing excessive power consumption. 

5.

Adjustment valves should be locked in place to prevent further
adjustment. 

6.

Once commissioned the home owner / tenant should be informed
that the unit should not be adjusted as it will have a detrimental
effect on the indoor air quality and could result in condensation
and mould growth. The label covering the control has an adhesive
panel which should be removed post commissioning to prevent
tampering.

Figure 14. Detail of unit control on front panel.

+

-

+

+

-

-

+

-

+

-

Post commissioning remove
adhesive backing under
this section 

Power

060905

For commissioning:
refer to user manual

Ventilation Controls

+

-

Содержание MRXBOX95B-450 WC

Страница 1: ...g to all statutory governing regulations All mains wiring must be in accordance with the current I E E Regulations or the appropriate standards Ensure that the mains supply Voltage Frequency and Phase complies with the rating label Please note a clear working space is required around the installed unit to allow the cover to be removed and provide sufficient access for maintenance such as filter ch...

Страница 2: ...tested 2 5 Handing The unit may be handed to switch the supply and extract spigot positions this can be done by following the steps below and are shown in fig 6 Note This process should only be carried out by a competent and qualified person Step 1 Remove the front cover and inner panel followed by the rear panel to gain access to the inside of the unit Step 2 Partially pull out the metal tray to ...

Страница 3: ...0 69 58 53 46 43 67 45 Open Outlet 63 57 57 64 51 46 39 36 62 30 Open Outlet 60 54 51 56 40 35 28 25 54 Supply Full Speed Open Outlet 59 62 65 71 65 63 57 53 71 90 Open Outlet 59 61 64 70 63 61 55 51 70 80 Open Outlet 58 61 63 68 61 59 53 49 68 65 Open Outlet 57 59 60 65 55 53 47 43 64 45 Open Outlet 55 56 57 60 48 46 40 36 59 30 Open Outlet 52 53 51 52 37 35 29 25 51 Breakout Sound Pressure Level...

Страница 4: ...ensions for unit wall mounting bracket position on 450WC 450 units 200 176 534 67 492 CRS 67 40 0 CRS 5 Fixing Points Bracket to be fitted to the wall 40 0 CRS 86 0 Front view Side view 86 0 15 0 23 0 Flush mounting face to wall or back box View from back 86 0 Front view Side view 86 0 11 0 Figure 8a Dimensions 450WC unit switch Figure 9a Dimensions MRXBOX95 3SWITCH 4 x Spigots 180mm Internal Diam...

Страница 5: ...connections Humidistat connections Fuse 5A MAINS 230V 50Hz N L MAINS 230V 50Hz N L 2 Pole Isolator 3 Position Switch Ancillary code MRXBOX95 3SWITCH Blue Brown Supply cord from unit Green yellow Blue Brown Black Supply cord from unit Grey Green yellow L 1 2 Fuse 5A MAINS 230V 50Hz N L 3 Pole Isolator 3 Position Switch Ancillary code MRXBOX95 3SWITCH Green yellow Blue Brown Black Supply cord from u...

Страница 6: ... to a wall or back box remove the front fascia by inserting a terminal screwdriver into the two openings along the bottom edge and prize open gently The fixing points on the back plate can then be accessed once the switch has been secured the front fascia can then be re fitted Note The wireless switch will typically operate up to a distance of 30m inside a building however this is dependent on the...

Страница 7: ...check for damage and security of components The heat exchanger should be fitted in the same orientation as originally assembled e g front label facing removable cover and top label nearest PCB Figure 15 Removing the two filter covers on the front panel of the unit Figure 16 The filters can be removed by pulling on the black tab on the visible end of the filters Telephone 02920 858 400 7 27 11 17 L...

Отзывы: