Unit must not be switched off, product is 

designed to run continuously.

For good EMC engineering practice, any sensor cables 

or switched live cables should not be 

placed within 50mm of other cables or on the same 

metal cable tray as other cables.

Isolation - Before commencing work make sure that the unit,

switched live and Nuaire control are electrically isolated 

from the mains supply. Note this product must be earthed.

Carry out all required electrical connections before fitting 

the front section.

3

Leaflet Number 671365 October 2009

Installation and Maintenance

mrXbox70 Mechanical Ventilation with Heat Recovery

4.0 Electrical Wiring 

The unit is designed to be wired directly to the mains supply

through a fused spur isolator (by others). With the rear

section only fixed in position bring the mains wiring through

the supplied cable gland (this gland can be moved to the

side position if required).

Additional grommeted holes are provided to allow additional

wiring to each blower.

The two fans are pre-wired into an internal wiring block for

ease of connection. (see figure 9 for connection details). 

All incoming mains connections must be routed through a

suitable local isolator for maintenance purposes.

L

N

Fuse 3A max.

230V ac
signal  
must be  
routed
through  
isolator

2

1

L

N

E

Signal to  
activate  
supply fan

Signal to  
activate  
extract fan

230V  
50Hz  
mains  
supply

Isolator (by others)

Figure 9.  Terminal Block Connections.

5.0 Setting to Work

Each fan is factory set to operate at trickle airflow when

power is applied and switch over to the boost flow rate

when a switched live signal is present. The pot marked ‘MIN

Airflow’ adjusts the trickle flow rate and the boost flow rate

by the pot marked ‘MAX Airflow’. These flow rates for the

supply and extract fan are adjusted separately. When the

switched live signal is removed, the fan will continue to run

at boost flow rate for a preset period as dictated by the pot

marked ‘RUN-on’.

6.0 Run-on Timer

The Run-on timer adjustment is from 0 - 60 mins.

Run-on is

only available from the switched live (SL) signal.

7.0 Maintenance

It is inevitable that even with filtered extract grilles as 

recommended in BRE digest 398 some dust, fluff etc. will

pass through the filter, and which, if allowed, will build up

internally on motors and impellers, shortening the life of 

the unit and, in severe cases, leading to overheating of the

motors. Consequently, it is strongly recommended that all

units are inspected and cleaned every 18 months.  

8.0 Cleaning 

Remove covers and carefully clean out interiors as 

necessary. To clean the filters, remove from the unit and

vacuum clean or wash in tepid water to which a little  

detergent has been added.  Shake out excess water and

allow to dry naturally.  Replace when dry. The heat exchanger

core can be safely cleaned in a domestic dish washer. 

Check for damage and security of components. Refit covers.

9.0 Replacement of Parts

Should any component need replacing Nuaire keep extensive

stocks for quick delivery. Ensure that the unit is electrically

isolated, before carrying out any work. 

When ordering spare parts, please quote the serial number

of the unit and the ARC number of the purchase if possible.

(This information will be available on the fan label).

10.0 Warranty

The 5 year warranty starts from the day of delivery and

includes parts and labour for the first year and parts only

for the remaining 4 years. This warranty is conditional on

planned maintenance being undertaken.

11.0 Service Enquiries

Nuaire can assist you in all aspects of service. Our service 

department will be happy to provide any assistance required,

initially by telephone and If necessary arrange for an 

engineer to call.

Customer Services Department 

on 08705 002 555

N

L

SL

Do not use

To OPUS-SPD
speed control

Internal
humidity adj.

To remote 
fail indicator
ES-MEV-AVI

TEST

Status

30

0

60

Run-on

(mins)

25

100

Max 

Airflow

(%)

25

100

Min 

Airflow

(%)

      

 

 LVT  

 

 

   

NET 

    TR

240V 1ph 
supply 
pre-wired 
to terminal 
box

Switch live
input 
pre-wired
to terminal
block

(Terminal 1 for extract fan)
(Terminal 2 for supply fan)

4.1 Additional Control Wiring Option 

Other control wirings are available on each fan. Open the

cover of the unit to gain access to these connections on

each fan (see figure 10).