Installation Manual

5.0 COMMISSIONING

The filters fitted inside the unit are protected with a plastic film. 
Prior to commissioning remove the covers (Figures 20 & 21), take 
off the film and replace.

1. For the required air flow rates please refer to the design specification 

for the property, follow 2.4, or refer to building regulations ADF 
2010.

2. The unit is supplied with independent control for both normal and 

boost airflows (Figure 18). 

3. Correct commissioning is essential to ensure the ventilation air flow 

rates are met. It also ensures the unit is not over ventilating and 
causing excessive power consumption. 

4. Commissioning should be carried out in accordance with building 

regulations document “Domestic ventilation compliance guide”. 

www.planningportal.gov.uk/building regulations/approved 
documents/partf/associated. 

A calibrated moving vane 

anemometer and hood will be required to carry out commissioning.

5. Adjustment valves should be locked in place to prevent further 

adjustment. 

6. Once commissioned the home owner / tenant should be informed 

that the unit should not be adjusted as it will have a detrimental 
effect on the indoor air quality and could result in condensation and 
mould growth. The clear panel covering the control has an adhesive 
panel which should be exposed and sealed post commissioning to 
prevent tampering.

7. Speed 1 is limited to never exceed speed 2, when commissioning 

speed 2 should always be set first.

5.1 Humidity Adjustment (AB unit only).

This product contains an internal humidity sensor fitted into the air-
flow extracting from the wet rooms. When the unit senses that the 
humidity exceeds the set point the unit will boost to that set by the 
commissioned boost speed. The set point can be found on the front 
of the unit (Figure 19) and is at its least sensitive when turned fully 
clockwise. Note that the sensor is measuring humidity from all the wet 
rooms at the same time and should not be relied on to solely boost the 
unit. Additional switch should be used local to the wet rooms (Section 
4.3.3).

5.2 Status Indication

The status of the unit is indicated by a series of LED’s on the front cover. 

The variants are listed below.

The display on the unit control panel will not indicate when a 

higher speed setting has been triggered by an external source, such 

as an ES-PIR2 etc.

19 

20 

Unit Control On Front Panel

 (Standard Configuration Only)

Unit Control On Front Panel

 (Standard Configuration Only)

HX Bypass

(AB units only)

Speed 1

Speed 2

Speed 3

Supply Fan Fault

Extract Fan Fault

Frost Protection

Filter Change

5.3 Integral Automatic HX Bypass

Intake and extract temperatures are monitored at the point the 

airflows enter the unit, if the range falls within the set parameters the 

bypass damper is opened automatically to target an indoor comfort 

temperature all year round.

5.4 Summer / Winter Switch

When the switch position is set to Summer the integral automatic 
summer bypass is fully operational, in the alternative Winter position 
the HX bypass is disabled to ensure the unit is constantly in heat 
recovery mode.

5.5 Frost Protection

In the event of the intake air temperature at the unit dropping below 

the predetermined set point (-5°C as standard) the supply fan will 

reduce to minimum speed, once the temperature rises above the set 

point the fan will return to its commissioned speed.
Frost protection will only activate after ten days of continuous run 

time. If commissioning of the unit is outside of this time frame please 

notify the after sales department prior to site visit.

6.0 MAINTENANCE

It is important that maintenance checks are recorded and that the 
schedule is always adhered to, in all cases, the previous report should 
be referred to.

6.1 Filters

Filters are to be inspected every 6 months and replaced every 12 
months (or sooner if required). 

Failure to do so may impair the 

performance and energy efficiency of this unit.

 A flashing LED 

(Section 5.2) will indicate that a filter change is required. This indication 
repeats every 12 months and will turn off automatically after 5 Days.

Remove the filter covers on the front panel of the unit by gripping the 
two circular tabs either end of the filter covers and pulling away from 
the unit. The filter can now be extracted by pulling the black removal 
loop on the front edge of the filter. Once the filters have been inspected 
return or replace them as necessary. 

+

-

Post commissioning remove
adhesive backing and seal 

Power Fan

Failure

+

-

Ventilation Controls

- +

+

- +

-

Speed 1 

- +

Speed 2 

Speed 3

Supply  Extract  Supply  Extract  Supply  Extract

Humidity adjustment

Содержание MRXBOX-ECO3

Страница 1: ...corporated within the fixed wiring and shall have a minimum contact separation of 3mm in accordance with latest edition of the wiring regulations This unit must be earthed Ducting must be securely fix...

Страница 2: ...e appropriate authority and conforming to all statutory governing regulations All mains wiring must be in accordance with the current I E E Regulations or the appropriate standards Ensure that the mai...

Страница 3: ...th centres of no more than 400mm Add additional vertical supports if necessary Height wise ideally the MDF panel should extend from floor to ceiling but as a minimum should be a least 2m high Fix the...

Страница 4: ...mmodation 6 l s Whole Dwelling Ventilation Rates Number Of Bedrooms In Dwelling 1 2 3 4 5 Whole dwelling ventilation rate l s 1 2 13 17 21 25 29 Notes 1 In addition the minimum ventilation rate should...

Страница 5: ...as follows The maximum whole dwelling extract ventilation rate e g boost should be at least the greater of step 1 and step 2 Note that the maximum individual room extract rate should be at least those...

Страница 6: ...insulated Insulated supply duct Top of ceiling void Air supply to bedrooms in ceilings via Air Valve mounted unit Nuaire wall MVHR DRAIN Condensate drain uninsulated drain pipe with min 5o fall runnin...

Страница 7: ...he two screws the Ecosmart cable can then be connected to the underside of the MVHR unit within The cable should be fed through rubber blanking plug to provide a seal when the cover is re fitted 4 3 W...

Страница 8: ...s on the front cover The variants are listed below The display on the unit control panel will not indicate when a higher speed setting has been triggered by an external source such as an ES PIR2 etc 1...

Страница 9: ...orrectly applied misused disassembled or not installed commissioned and maintained in accordance with the details contained in this manual and general good practice The product warranty applies to the...

Страница 10: ...10 23 07 20 Document Number 671856 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO 3 5 OH SW Installation Manual NOTES...

Страница 11: ...11 23 07 20 Document Number 671856 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO 3 5 OH SW Installation Manual NOTES...

Страница 12: ...12 23 07 20 Document Number 671856 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO 3 5 OH SW Installation Manual NOTES...

Отзывы: