MRXBOX(AB)-ECO3-AE

Installation Manual

1.2 Important Information

This manual contains important information on the safe and 
appropriate assembly, transport, commissioning, operation, 
maintenance, disassembly and simple troubleshooting of the product.

While the product has been manufactured according to the accepted 
rules of current technology, there is still a danger of personal injury or 
damage to equipment if the following general safety instructions and 
the warnings contained in these instructions are not complied with.

Read these instructions completely and thoroughly before 
working with the product.

Keep these instructions in a location where they are accessible 
to all users at all times.

Always include the operating instructions when you pass the 
product on to third parties.

1.3 Personal Protective Equipment

The following minimum Personal Protective Equipment (PPE) is 
recommended when interacting with Nuaire product:

Protective Steel Toed Shoes - 

when handling heavy objects.

 

Full Finger Gloves (Marigold PU800 or equivalent) - 

when 

handling sheet metal components. 

Semi Fingerless Gloves (Marigold PU3000 3DO or equivalent) 

- when conducting light work on the unit requiring tactile 
dexterity. 

Safety Glasses

 - when conducting any cleaning/cutting operation 

or exchanging filters. 

Reusable Half Mask Respirators 

- when replacing filters which 

have been in contact with normal room or environmental air.

Nuaire would always recommend a site specific risk assessment by a 
competent person to determine if any additional PPE is required. 

2.0 INTRODUCTION

The ECO3-AE wall mounted range of units are designed to offer 
improved sound levels and an aesthetically pleasing installation by 
housing a Mechanical Ventilation with Heat Recovery unit (MVHR) 
inside an acoustically lined enclosure.

The MVHR unit is fitted with two independent fans. Each fan has full 
speed control for background and boost ventilation rates. To recover 
heat from the extract air the heat exchanger block is utilised. The heat 
exchanger can recover up to 95% of the normally wasted heat.

If the MVHR unit has integral automatic HX bypass (AB models 
only),

 the bypass damper shall open automatically via a wax actuator 

allowing the air to bypass the heat exchanger to deliver fresh filtered air 
during the warmer months.

Airflow Through unit (Standard Unit)

Airflow Through OH unit (Opposite Hand Unit)

Transport Fixings

3.0  MECHANICAL INSTALLATION

Installation must be carried out by competent personnel in accordance 
with the appropriate authority and conforming to all statutory 
governing regulations. All mains wiring must be in accordance with the 
current I.E.E. Regulations, or the appropriate standards. Ensure that the 
mains supply (Voltage, Frequency and Phase) complies with the rating 
label. 

Allow a minimum of 360m in front of the MRXBOXAB-ECO3.

The fan must be installed indoors, on a suitable wall away from direct 
sources of frost, heat and water spray or moisture generation. For a 
vibration-free result the unit must be mounted to a solid wall.

The unit must remain switched on at all times to maintain 
ventilation within the dwelling. Turning the unit off will cause long 
term damage to the unit and building fabric.

3.1 Transport Fixings

To prevent damage during transportation the product is shipped with 
securing fixings, these can be found front and centre of the enclosure 
top panel (Figure 3). These must be removed before use, failure to do so 
will result in excessive vibration and noise. The screws removed can be 
discarded and replaced with rubber caps provided.

Intake air 

from outside

Extract air 

from house

to house

Supply air 

Exhaust air 

from house

to outside

Extract air 

from house

Intake air 

Exhaust air 

from outside

from house

to outside

Supply air 

to house

Intake air 

from outside

Extract air 

from house

to house

Supply air 

Exhaust air 

from house

to outside

Extract air 

from house

Intake air 

Exhaust air 

from outside

from house

to outside

Supply air 

to house

Spigot fixing plate

Transportation fixings

3.2 Wall Mounting

The unit is designed for wall mounting on a solid wall only, a 
gypsum block/plasterboard wall will not suffice. 

Examples of suitable installation are shown overleaf. The wall brackets 
supplied should be secured to the wall using suitable fixings (supplied 
by others) as per the dimensions given in figure 4. The head of the 
chosen fixing should protrude no more than 8mm from the wall 
bracket. The enclosure assembly can then be lifted using suitable 
equipment and moved into position so it is sitting directly on the wall 
brackets (ensuring the rear panel of the enclosure is not in contact 
with the wall bracket fixings). The enclosure can be secured to the wall 
brackets using the 4x M8 fixings supplied.

No part of enclosure should be in contact with the building structure, 
the only components that should be in contact are the wall mounting 
brackets.

Care must be taken to ensure the unit is installed true in all 3 

dimensions. Failure to do so may result in overflow from the 

internal condensation drip tray.

Содержание MRXBOX-ECO3-AE

Страница 1: ...lations This unit must be earthed Ducting must be securely fixed with screws to the spigot to prevent access to live parts Duct runs terminating close to the fan must be adequately protected by suitab...

Страница 2: ...warmer months 1 2 3 Airflow Through unit Standard Unit Airflow Through OH unit Opposite Hand Unit Transport Fixings 3 0 MECHANICAL INSTALLATION Installation must be carried out by competent personnel...

Страница 3: ...ceiling but as a minimum should be a least 2m high Fix the mounting bracket to the wall Figure 3 and use the wall mounted bracket to mount the unit on Figure 5 25 25 704 crs 9 1 dia 30 94 94 33 3 3 C...

Страница 4: ...all other bedrooms This should be used as the default value If a greater level of occupancy is expected add 4 l s per occupant Any air intake terminal must be installed in accordance with the appropr...

Страница 5: ...sture levels are likely to occur Therefore it is advisable that if the installation and building works are complete the unit is left running If the building works are not complete please close the air...

Страница 6: ...sulated Insulated supply duct Top of ceiling void Air supply to bedrooms in ceilings via Air Valve mounted unit Nuaire wall MVHR DRAIN Condensate drain uninsulated drain pipe with min 5o fall running...

Страница 7: ...Ecosmart Device Connector 4 1 Electrical Information Voltage 240V 1ph 50Hz Consumption 1 2 Amp This unit must be earthed The cable from the mains power supply should be connected to a fixed wiring ins...

Страница 8: ...ed on to solely boost the unit Additional switch should be used local to the wet rooms Section 4 2 Humidity adjustment AB unit only Speed 2 Speed 1 Speed 2 Speed 1 18 19 Unit Control On Front Panel St...

Страница 9: ...uired The serial number will be found on the identification plate attached to the unit casing Telephone 02920 858 400 aftersales nuaire co uk 6 3 Annually Thoroughly inspect the unit and its component...

Страница 10: ...10 05 08 21 Document Number 671823 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOX AB ECO3 AE Installation Manual NOTES...

Страница 11: ...11 05 08 21 Document Number 671823 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOX AB ECO3 AE Installation Manual NOTES...

Страница 12: ...12 05 08 21 Document Number 671823 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOX AB ECO3 AE Installation Manual NOTES...

Отзывы: