Installation Manual

1.0 SAFETY INFORMATION

• 

The provision of the electrical supply and the connection of the unit to the mains must be 
carried out by a qualified electrician.

• 

Isolate from power supply before removing any covers. During installation / maintenance ensure 
all covers are fitted before switching on the mains supply. 

• 

All-pole disconnection from the mains as shown in the wiring diagram must be incorporated 
within the fixed wiring and shall have a minimum contact separation of 3mm in accordance with 
latest edition of the wiring regulations.

• 

This unit must be earthed.

• 

Ducting must be securely fixed with screws to the spigot to prevent access to live parts. Duct 
runs terminating close to the fan must be adequately protected by suitable guards.

• 

If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or 
similarly qualified persons in order to avoid a hazard.

• 

Precautions must be taken to avoid the back-flow of gases into the room from the open flue of 
gas or other fuel-burning appliances.

• 

This appliance should not be used by children or persons with reduced physical, sensory or 
mental capabilities or lack of experience and knowledge, unless they have been given supervision 
or instruction concerning the safe use of the appliance by a person responsible for their safety. 
Children shall not play with the appliance. Cleaning and user maintenance shall not be carried 
out by children.

1.1 Hazard Symbols

  

REFER TO INSTRUCTION MANUAL

 

 

 

Read and understand the installation and maintenance manual before installing,    

 

 

operating or maintaining this product.

Содержание MRXBOX-ECO3-AE

Страница 1: ...lations This unit must be earthed Ducting must be securely fixed with screws to the spigot to prevent access to live parts Duct runs terminating close to the fan must be adequately protected by suitab...

Страница 2: ...warmer months 1 2 3 Airflow Through unit Standard Unit Airflow Through OH unit Opposite Hand Unit Transport Fixings 3 0 MECHANICAL INSTALLATION Installation must be carried out by competent personnel...

Страница 3: ...ceiling but as a minimum should be a least 2m high Fix the mounting bracket to the wall Figure 3 and use the wall mounted bracket to mount the unit on Figure 5 25 25 704 crs 9 1 dia 30 94 94 33 3 3 C...

Страница 4: ...all other bedrooms This should be used as the default value If a greater level of occupancy is expected add 4 l s per occupant Any air intake terminal must be installed in accordance with the appropr...

Страница 5: ...sture levels are likely to occur Therefore it is advisable that if the installation and building works are complete the unit is left running If the building works are not complete please close the air...

Страница 6: ...sulated Insulated supply duct Top of ceiling void Air supply to bedrooms in ceilings via Air Valve mounted unit Nuaire wall MVHR DRAIN Condensate drain uninsulated drain pipe with min 5o fall running...

Страница 7: ...Ecosmart Device Connector 4 1 Electrical Information Voltage 240V 1ph 50Hz Consumption 1 2 Amp This unit must be earthed The cable from the mains power supply should be connected to a fixed wiring ins...

Страница 8: ...ed on to solely boost the unit Additional switch should be used local to the wet rooms Section 4 2 Humidity adjustment AB unit only Speed 2 Speed 1 Speed 2 Speed 1 18 19 Unit Control On Front Panel St...

Страница 9: ...uired The serial number will be found on the identification plate attached to the unit casing Telephone 02920 858 400 aftersales nuaire co uk 6 3 Annually Thoroughly inspect the unit and its component...

Страница 10: ...10 05 08 21 Document Number 671823 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOX AB ECO3 AE Installation Manual NOTES...

Страница 11: ...11 05 08 21 Document Number 671823 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOX AB ECO3 AE Installation Manual NOTES...

Страница 12: ...12 05 08 21 Document Number 671823 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOX AB ECO3 AE Installation Manual NOTES...