Fig. 1 ESX*-X Plantroom/Roof mounted in line unit.
Fig. 2 ESX*-R roof mounted end inlet, side discharge unit.
Introduction
The Nuaire ESX Belt Drive range consists of the
following units:
ESX-X (Duct Mounted, Plantroom/Roof) in line unit
ESX-R (Roof Mounted, end inlet) side discharge unit*
ESX-B (Roof Mounted bottom inlet) side discharge unit*
* larger size units have end discharge.
Units are rectangular in section. The casing is manufactured
from heavy gauge ‘Aluzinc’ aluminium-zinc coated mild steel.
A full size internally lined access panel is fitted to the top
face and this panel is fully detachable for inspection purposes.
The motor plate and frames are supported on the base by
resilient mountings allowing the fan unit to be operated
without the need for separate anti vibration fan case
mountings. The units incorporate an independent motor with
high efficiency, forward curved centrifugal impeller running
in a metal scroll. Taper locked pulleys and wedge drive belts
are employed. The motor is manufactured to BS5000 and
suitable for three phase supply.
Airflow and failure monitors are standard as is Class F
insulation. Suitable for operation in ambient temperatures
up to 40
o
C.
Handling
Handle the units carefully to avoid damage and distortion.
Eyebolts are provided on some units for lifting purposes.
If mechanical aids are used to lift the unit, spreaders should
be employed and positioned so as to prevent the slings,
webbing etc. making contact with the casing.
Fig. 3 Bottom inlet units
Fig. 4 Bottom / End inlet units. Large sizes
XTRACTOR -
3 phase Belt Drive
Roof & Plantroom Single Fans
Installation and
Maintenance
Manual
1
11. 05. 17. Leaflet Number 671177
A
B
Removable
top panel
Opposed
outlet
grilles
F
E
Control module
located internally
Commissioning
box
Bottom inlet
C
Louvred
end outlet
Bottom rectangular inlet spigot
Code: ESX*-B
F
E
B
A
C
F
E
End inlet rectangular spigot
Code: ESX*-R
Commissioning
box
A
50mm
B
F
C
E
Rectangular spigots
size ESX 20-26)
Circular spigots
size ESX 11-19)
D dia
Removable top
panel
Commissioning box
ESX-X
ESX-R
ESX-B/R
Larger units
ESX-B
Unit
A
B
C
D dia
E
F
ESX 11-X to ESX 12-X
974
974
622
400
-
-
ESX 13-X to ESX 14-X
1233
1233
701
500
-
-
ESX 15-X to ESX 19-X
1430
1190
796
630
-
-
ESX 20-X to ESX 26-X
2030
1466
1183
-
1200
700
Unit
A
B
C
D dia
ESX 11-R to ESX 12-R
974
974
622
400
ESX 13-R to ESX 14-R
1233
1233
701
500
ESX 15-R to ESX 19-R
1430
1190
796
630
A
B
Removable
top panel
Opposed
outlet grilles
External
commissioning box.
D dia
Control module
located internally
C
Unit
A
B
C
E
F
ESX 20-B to ESX 26-B
2030
1466
1183
1200
700
ESX 20-R to ESX 26-R
2030
1466
1183
1200
700
Table 3. Dimensions (mm)
For unit weights see table 7
Unit
A
B
C
E
F
ESX 11-B to ESX 12-B
974
974
622
457
229
ESX 13-B to ESX 14-B
1233
1233
701
762
304
ESX 15-B to ESX 19-B
1430
1190
796
889
381
Table 4. Dimensions (mm)
For unit weights see table 7
Table 2. Dimensions (mm)
For unit weights see table 7
Table 1. Dimensions (mm)
For unit weights see table 7
The EMC Directive
2014/30/EU
The Low Voltage
directive
2014/35/EU