Fig. 1  ESX*-X  Plantroom/Roof mounted in line unit.

Fig. 2  ESX*-R  roof mounted end inlet, side discharge unit.

Introduction

The Nuaire ESX Belt Drive range consists of the 

following units:

ESX-X  (Duct Mounted, Plantroom/Roof) in line unit

ESX-R  (Roof Mounted, end inlet) side discharge unit* 

ESX-B  (Roof Mounted bottom inlet) side discharge unit*

* larger size units have end discharge.

Units are rectangular in section. The casing is manufactured

from heavy gauge ‘Aluzinc’ aluminium-zinc coated mild steel.

A full size internally lined access panel is fitted to the top

face and this panel is fully detachable for inspection purposes.

The motor plate and frames are supported on the base by

resilient mountings allowing the fan unit to be operated

without the need for separate anti vibration fan case 

mountings. The units incorporate an independent motor with

high efficiency, forward curved centrifugal impeller running

in a metal scroll.  Taper locked pulleys and wedge drive belts

are employed. The motor is manufactured to BS5000 and

suitable for three phase supply.

Airflow and failure monitors are standard as is Class F

insulation. Suitable for operation in ambient temperatures

up to 40

o

C. 

Handling

Handle the units carefully to avoid damage and distortion.

Eyebolts are provided on some units for lifting purposes. 

If mechanical aids are used to lift the unit, spreaders should

be employed and positioned so as to prevent the slings,

webbing etc. making contact with the casing. 

Fig. 3  Bottom inlet units

Fig. 4  Bottom / End inlet units. Large sizes

XTRACTOR - 

3 phase Belt Drive

 

Roof & Plantroom Single Fans

Installation and 
Maintenance

 

Manual

 

1

11. 05. 17. Leaflet Number 671177

A

B

Removable 
top panel

Opposed
outlet
grilles

F

E

Control module
located internally

Commissioning
box

Bottom inlet

C

Louvred
end outlet

Bottom rectangular inlet spigot
Code: ESX*-B

F

E

B

A

C

F

E

End inlet rectangular spigot
Code: ESX*-R

Commissioning
box

A

50mm

B

F

C

E  

Rectangular spigots 
size ESX 20-26)

Circular spigots 
size ESX 11-19)

D dia

Removable top
panel

Commissioning box

ESX-X

ESX-R

ESX-B/R 

Larger units 

ESX-B

Unit

A

B

C

D dia

E

F

ESX 11-X to ESX 12-X

974

974

622

400

-

-

ESX 13-X to ESX 14-X

1233

1233

701

500

-

-

ESX 15-X to ESX 19-X

1430

1190

796

630

-

-

ESX 20-X to ESX 26-X

2030

1466

1183

-

1200

700

Unit

A

B

C

D dia

ESX 11-R to ESX 12-R

974

974

622

400

ESX 13-R to ESX 14-R

1233

1233

701

500

ESX 15-R to ESX 19-R

1430

1190

796

630

A

B

Removable 
top panel

Opposed 
outlet grilles

External 
commissioning box.

D dia

Control module
located internally

C

Unit

A

B

C

E

F

ESX 20-B to ESX 26-B

2030

1466

1183

1200

700

ESX 20-R to ESX 26-R

2030

1466

1183

1200

700

Table 3.   Dimensions (mm)

For unit weights see table 7

Unit

A

B

C

E

F

ESX 11-B to ESX 12-B

974

974

622 

457

229

ESX 13-B to ESX 14-B

1233

1233

701

762

304 

ESX 15-B to ESX 19-B

1430

1190

796

889

381

Table 4.   Dimensions (mm)

For unit weights see table 7

Table 2.   Dimensions (mm)

For unit weights see table 7

Table 1.   Dimensions (mm)

For unit weights see table 7

The EMC Directive 
2014/30/EU 
The Low Voltage 
directive 
2014/35/EU

Nuaire: A Trading Division of Polypipe Limited  

Western Industrial Estate

 

Caerphilly  United Kingdom  CF83 1NA  

T: 029 2088 5911  F: 029 2088 7033  E: [email protected]  W: www.nuaire.co.uk

Содержание ECOSMART XTRACTOR

Страница 1: ...d inlet units Large sizes XTRACTOR 3 phase Belt Drive Roof Plantroom Single Fans Installation and Maintenance Manual 1 11 05 17 Leaflet Number 671177 A B Removable top panel Opposed outlet grilles F E...

Страница 2: ...installation Ensure that the Fan unit and any specified controls are fitted securely according to the instructions Switch on the mains supply Push the test button to run each fan and check that they...

Страница 3: ...ype B RCD should be used trip limit 300mA Otherwise nuisance tripping will occur Because the run and start currents depend upon the duty and associated ductwork of an individual unit the values quoted...

Страница 4: ...Data Cable installation A 4 core SELV data cable is used to connect devices such as sensors to the fan and for interconnecting multiple fan units Do not run data cable in the same conduit as the mains...

Страница 5: ...NET The fan will now adjust it s speed according to temperature To obtain manual control connect a link across L to SL enabling signal and connect a user control in one of the sockets labelled NET Se...

Страница 6: ...ry metre of span length see fig 12 The force required to deflect the V belt should be from 0 5kg to 0 8kg 3 Tighten the pinch bolts General Cleaning and Inspection Clean and inspect the exterior of th...

Страница 7: ...by the equipment panels or by fixed installation detail eg ducting then guarding to the appropriate standard must be fitted 5 2 The electrical installation of the equipment must comply with the requi...