NuAire ECOSMART TWINFAN Series Скачать руководство пользователя страница 4

For good EMC engineering practice, any sensor cables 

or switched live cables should not be 

placed within 50mm of other cables or on the same 

metal cable tray as other cables.

4

16. 06. 15. Leaflet Number 671142

Installation and Maintenance

ECOSMART Direct Drive Roof Mounted Twinfans

Connections continued.

NOTE: A Commissioning Procedure document (leaflet No.

671154) is available on request from the Nuaire Technical

Library Tel: 02920 885911.

2.0 Using the Test button 

(see fig. 6).

The test button allows the individual blowers within the unit to

be checked for its operation. If the fan is running already, press

the button once to stop the fan, press again to switch on the

standby fan, press again to stop and so on. 

Note that the fan will return to normal operation after 

30 seconds.

3.0 LED Indication 

(see fig. 6).

PWR

GREEN: Power on & OK. RED:Too much power 

is taken by peripherals or there is a short circuit in 

the net cable. Check the cable and use a junction 

box (ES-JB) to connect some of the peripherals.

Standby

LED on when fan is not running.

Fan 1

GREEN: Fan 1 is running, RED: Fan 1 faulty.

Fan 2

GREEN: Fan 2 is running, RED: Fan 2 faulty.

Heating*

Not applicable. See note.

Cooling*

Not applicable. See note.

Fault

LED on when a fault is present on unit.

Frost*

Not applicable. See note.

Tx

LED on when the controller is transmitting data.

Rx

LED on when the controller is receiving data.

* Note that the control panel is common to all the Ecosmart

products and will have indicators for functions that are not

available in this particular fan. However these indicators

will not be illuminated.

4.0 BMS input signals

The systems response to a 0-10V dc BMS signal is given in the 

following table. Note the BMS signal will override any sensors

and user control connected in the system. 

The voltage tolerance is +/_ 125mV and is measured at the

fans terminal.

Ventilation mode

Cooling mode*

Heating mode*

Local control

0.00

-

-

OFF/trickle

0.25

-

-

Speed 1

0.50

0.75

1.00

Speed 2

1.50

1.75

2.00

Speed 3

2.50

2.75

3.00

Speed 4

3.50

3.75

4.00

Speed 5

4.50

4.75

5.00

Speed 6

5.50

5.75

6.00

Speed 7

6.50

6.75

7.00

Speed 8

7.50

7.75

8.00

Speed 9

8.50

8.75

9.00

Speed 10

9.50

9.75

10.00

* Only available on relevant unit

5.0 Setting the airflow

Setting the maximum air flow

i) Ensure the power supply is switched off and that a link wire

is connected from the supply L to the SL terminal. Unplug all

items connected to the ‘Net‘ connectors.

ii) Switch on the power supply.

Note: Ensure unit cover is securely attached. 

iii) Wait for the fan to complete its self-test operation.

iv) Remove the cover of the units external commissioning box.

Measure the airflow using standard commissioning instruments

at a suitable point in the ductwork. If adjustment is required,

rotate the pot marked ‘MAX’ to obtain the desired airflow.

Setting the minimum trickle airflow (nominally 40%)

i) Repeat the same procedure as for maximum airflow above

but without the link wire between supply L and SL terminal.

Ensure the trickle switch is in the ‘ON’ position. The adjustment

must be made on the pot marked ‘Min’.

ii) Note that the minimum setting (nominally 40%) must be

below the maximum setting, otherwise minimum setting will 

be automatically set to be the same as the maximum.

After setting the airflows, re-connect all the items disconnected

previously. Ensure that the cover over the mains terminals is

replaced and that the cover of the controls enclosure is 

securely fastened.

Table 6.

Fig. 6  External Commissioning Box details.

Содержание ECOSMART TWINFAN Series

Страница 1: ...uent removal of fan and motor assemblies etc Whether internally or externally mounted the method of fixing to the roof is the responsibility of the installer All units have a bottom skirt to allow for...

Страница 2: ...h The fan casings have an inside skirt depth of 60mm or in the case of the largest size units only 50mm It is recommended that the units are mounted upon a suitable curb or upstand which has a minimum...

Страница 3: ...e total data cable length used in any system must be less than 1000m Keep the number of cable joints to a minimum to ensure the best data transmission efficiency between devices e Maximum number of de...

Страница 4: ...10V dc BMS signal is given in the following table Note the BMS signal will override any sensors and user control connected in the system The voltage tolerance is _ 125mV and is measured at the fans te...

Страница 5: ...freely Refit the assemblies to the unit see Replacement of Parts then replace the access cover If Nuaire controls and or remote indicators are fitted remove the cover and carefully clean out the inte...

Страница 6: ...Where access to any part of equipment which moves or can become electrically live are not prevented by the equipment panels or by fixed installation detail eg ducting then guarding to the appropriate...

Страница 7: ...7 16 06 15 Leaflet Number 671142 Notes Installation and Maintenance ECOSMART Direct Drive Roof Mounted Twinfans...

Страница 8: ...Number 671142 Installation and Maintenance ECOSMART Direct Drive Roof Mounted Twinfans Western Industrial Estate Caerphilly United Kingdom CF83 1NA T 029 2085 8400 F 029 2085 8400 E info nuaire co uk...

Отзывы: