Installation and Maintenance
ES-TC Timeclock - Extra Low Voltage User Controls
03. 07. 15. Leaflet Number 671162
2
Pressing the centre button selects
the next operating mode
Off On Auto Time
15:54
Pressing the centre button selects
the next operating mode
Pressing the centre button selects
the next operating mode and brings us
back to
Option will flash
to show state of
timer
Automatic mode
has been selected
B
Off On Auto Time
15:54
Manual OFF mode
is selected
Off On Auto Time
15:54
Manual ON mode
is selected
When you are finished, fix the
chosen Time by pressing the
centre button to exit
programming mode or
press to continue to program
other settings
Increase or decrease by
pressing either button.
Hold button down to run quickly
through hours. Shorter presses
set minutes
Press the button to see the
Time setting
Pressing the buttons together
will display the set clock option
Off On Auto Time
10:04
Set clock
Time
15:54
Screen is set to Auto mode
(See basic operating instructions)
Off On Auto Time
15:54
Operating the control
Follow the instructions to set the time/weekday etc and
program your chosen on/off times etc.
On the fascia a Green LED indicates unit is working.
If the ‘STATUS’ LED shows Red it indicates a fault in the
system.
The ES-TC provides a signal to operate the Ecosmart fans
linked via the ‘NET’ connections. If the ES-TC is in the ‘OFF’
position, this will override other enabling devices such as
ES-PIR.
Note: The switched live signal operates independently from
other enablers. Individual fans can be switched ‘ON’ via the
switched live even if the ES-TC is in the ‘OFF’ position.
The ES-TC can pre-set the operating signal to ‘TRICKLE’ or
‘BOOST’ (see setting ‘ON’ level). However, if another device
is connected which can set the fan speed (eg. CO2 sensor or
User control etc.) the ES-TC setting will be ignored.
Basic Operating Functions
Setting the Time