9.1 Via the soffit through a grille and ducting supplied by others
Any air intake terminal MUST be installed in accordance
with the appropriate regulation.
As a guide, the BS5440 series of British Standards
deals with this issue and currently states that an air
intake must be at a minimum distance of 300mm from a
gas boiler balanced flue. Installers are advised to be
aware of the requirements of this standard when
installing ‘through the wall’ supply air ducting.
Similarly, supply and extract air grilles should be
at least 300mm apart.
150mm dia. insulated ducting
connected to unit spigot using
dynotie connector.
150mm dia. pipe
(Part No. PVC130-6WH.
Insulated duct formed over pipe
and sealed with dynotie connector.
199 x 215 x 20mm
white plastic wall grille
(Part No. PVC604WH.
Installation and Maintenance
Drimaster365 Low Energy Positive Input Ventilation Unit
9.2 Via a wall grille and ducting supplied by others
Circular duct connector
(Part No. RDC150).
150mm dia. insulated
ducting connected
to unit spigot using
dynotie connector.
5
11. 06. 15. Leaflet Number 671429
Figure 12.
Figure 13.