04. 08. 21. Document Number  671793

Nuaire | 

Western Industrial Estate 

Caerphilly 

CF83 1NA 

|

 

nuaire.co.uk

DRI-ECO-RH

Installation Manual

2.1 Binding Unit To Sensor

2.1.1 Unit Binding Mode

Where a Humidity sensor is present, it must first be bound to the fan 
unit before it can work. In order to bind the sensor(s) the fan must be 
in binding mode. The steps required to enter binding mode are shown 
below.

Ensure the fan unit is powered on. 

Unit will enter the start-up sequence for 2 minutes when first 
powered on. Press the down button on the ceiling diffuser control 
panel once, to exit the start-up sequence.

Press and hold the both the UP and DOWN buttons for 20-30 
seconds then release. A single horizontal bar on the display flashes. 

Press "down" to enter binding mode (binding mode lasts for 5 
minutes).The unit will now display a flashing ‘b’ to indicate it has 
entered binding mode.

A solid “P” indicates purge, a solid “b” indicates boost, and a 
flashing “b” indicates binding mode. 

 

DOWN

UP

DOWN

UP

Drimaster Diffuser Control

2.1.2 Binding Sensor

Putting the unit into binding mode (Section 2.1) before powering the 
sensors will automatically bind the sensors to the unit. However if they 
do not bind follow the below steps.

Put the unit into binding mode.

Power up sensors (insert batteries for humidity, mains for CO2).

Tap indented button then hold until left hand LED flashes red/
green (ignore red/blue and continue to hold). Release button 
whilst flashing.

Tap indented button again, whilst red/green LED is still flashing.

Close binding window on fan control panel by holding both “up” 
and “down” for 5 seconds and release.

Check sensor has bound by tapping indented button and look for 
left hand LED to go green. If it displays red, repeat from step 1.

2.2 RF Frequency

RF enabled DRI-ECO devices operate at a frequency of 868.3 MHz.

3.0 CONTROLS

3.1 Sensor Setpoint

The sensors will automatically trigger the fan to increase speed once 
the sensor set point has been exceeded. To change the sensor set point, 
press and hold the indent button until the status indication LED flashes 
BLUE/RED then release, the green LED’s illuminate to show the current 
sensor set point. Press the button to cycle through all allowed values, 
and press and hold to confirm choice. If the button is not operated for 
10 seconds the set point currently selected is stored.

Boost (Sensor) - 

If a sensor set point has been exceeded, the unit will 

enter boost mode and a solid ‘b’ will be shown in the display. Boost 
mode increases the speed setting by 1. If the unit is running at speed 
6, boost is ignored (i.e. A unit is running at speed 3. A boost signal is 
received from a sensor whereby the speed changes to 4. When the 
boost condition clears, the unit will revert to speed 3).

3.2 LED Indicators

The sensors and switches include an LED which illuminates when a 
button is pressed. A green light shows that communication between 
the sensor or switch and the fan unit is taking place. A red light shows 
that no communication is taking place and binding may be required.

4.0 MAINTENANCE

It is important that maintenance checks are recorded and that the 
schedule is always adhered to, in all cases, the previous report should 
be referred to.

4.1 Routine Maintenance

This sensor can be cleaned with a dry brush or dry cloth. Any other 
maintenance or cleaning should be carried out by properly qualified 
personnel.

Ensure the unit does not come into contact with any kind of liquid 
or solvent. If this should occur, contact a qualified technician before 
reassembling the fan.

5.0 WARRANTY

The

 7

 

year warranty starts from the day of delivery and includes parts 

and labour for the first year. The remaining period covers replacement 
parts only.

This warranty is void if the equipment is modified without 
authorisation, is incorrectly applied, misused, disassembled, or not 
installed, commissioned and maintained in accordance with the details 
contained in this manual and general good practice.

The product warranty applies to the UK mainland and in accordance 
with Clause 14 of our Conditions of Sale. Customers purchasing from 
outside of the UK should contact Nuaire International Sales office for 
further details.

Failure to maintain the unit as recommended will invalidate the 
warranty.