Installation and Maintenance   

TWINFAN CONTROL

4

Operating the Twinfan Mains Control

Pressing any of the panel buttons will be accompanied by an 
audible confirmation tone. The button functions are listed below.

Duty Share

(This button appears on CT-A models only).
Pressing this button will enable or disable the duty sharing feature.
When the Duty Share light is on, duty sharing is selected.

Fail

There are two ‘FAIL’ indicators, one under each Fan button. The
fail indicators show which fan has failed. In the event of a failure,
an audible alarm will also sound for 15 seconds. If the internal
configuration switches have been selected for a continuous audible
alarm, the alarm will continue until the fault is rectified.

Power

Pressing this button switches the unit ON or OFF. When
switched ON the associated light will show GREEN. When the
unit is switched OFF the light will show RED.
An AMBER light will indicate the unit is switched ON but there
is no 230v signal  connected to the SL terminal inside the case.

WARNING
Switching the unit OFF on the front panel Power button
does not  isolate the fan or the control.

Figure 7. 
Twinfan Control buttons

Power

Fail

Fail

Duty
Share

Fan 2

Fan 1

Explanation of the button functions.

Fan 1 / Fan 2

Pressing either button selects that fan to run. If there is a fan 
failure, the fail indicator will remain illuminated even after the fail-
ure has been rectified and the control must be reset (by pressing
the fan button to restart the fan.

Connections

to fan

Supply

230V ac.  50Hz

N   L   L   SL   L   FL   L1  L2   N       H   BL  RD  BK  Y    RUN    FAULT

  SUPPLY    SWITCHED     FAN            FAN UNIT                    ICP                 RR          RF               

              LIVE        LIVE

Main terminal connections

Figure 8. 
Connections to Control.

Run on Timer adjustment

A Run On facility is provided so that when the 230V ac signal 
is disconnected from the SL terminals the fans can continue to

run on for a period of up to 60 minutes.  The run on time is 

set using a rotating screw (See fig. 9).

When the 230V ac signal is disconnected, the power lamp on 
the front of the unit will illuminate AMBER to  indicate there
is no SL signal.

Figure 9. 
Run on  adjustment

  BL RD BK  Y    RUN    FAULT

  ICP                                     RR                   RF               

Run On
rotary 
adjustment
0-60 mins
(clockwise)

Содержание CT-A

Страница 1: ...ary cable access NOTE It is the responsibility of the installer to seal the cable entries and to maintain the IP rating of the unit Select a suitable surface mounting position and fix the main cas ing to it using the four case mounting holes provided fig 2 ISOLATE THE ELECTRICAL SUPPLY and make your main electrical supply and fan unit connections to the terminals inside as shown in fig 8 FEATURES ...

Страница 2: ...o Control Single Phase application Three Phase application N L L SL L FL L1 L2 N H BL RD BK Y RUN FAULT Connection for speed control Link must be removed when using a speed control 1 phase fans only L1 L2 N H QUIETWIN FAN Single phase 230v MAINS CONTROL 230V 1 phase supply NOTE supply to fan is via the control Link Link NET CT AVI Audible Visual Indicator connection 230V Switched Live Connection t...

Страница 3: ...Link NET CT AVI Audible Visual Indicator connection QUIETWIN FAN Three phase 230V Switched Live Connection twinfan operates when live remove link when used Volt Free Contacts Rated 230V 5A for run indication if required Volt Free Contacts Rated 230V 5A for fail indication if required L1 L2 N H CONNECTION BOX IN FAN 4 core Earth Cable 230V 1ph 50Hz supply Three Phase fan units 1ph power for control...

Страница 4: ... the SL terminal inside the case WARNING Switching the unit OFF on the front panel Power button does not isolate the fan or the control Figure 7 Twinfan Control buttons Power Fail Fail Duty Share Fan 2 Fan 1 Explanation of the button functions Fan 1 Fan 2 Pressing either button selects that fan to run If there is a fan failure the fail indicator will remain illuminated even after the fail ure has ...

Страница 5: ...witch off 4 Do not reset this particular switch retain as set by factory Figure 13 Function switches L SL P I R sensor or Light Switch BL RD BK Y RUN FAULT ICP RR RF A B C D A volt free relay is included to provide status if any fan is running Maximum load is 5amp 230V ac When a fan is running A B are connected When a fan has failed C D are connected Figure 11 Remote Run Remote Fail connections Re...

Страница 6: ...mensions of equipment and the right is reserved to make such changes without prior notice Western Industrial Estate Caerphilly Mid Glam CF83 1XH United Kingdom Telephone 029 2088 5911 Facsimile 029 2088 7033 Email info nuaire co uk www nuaire co uk Leaflet No 670912 GP168 Installation and Maintenance TWINFAN CONTROL 5 ...

Отзывы: