NuAire CT-A Скачать руководство пользователя страница 1

CONTENTS                                                 Page

Maintenance
Introduction.
Installing the control unit.
Applications and wiring diagrams            
Operating the twinfan  mains control.
Terminal connections
Run on Timer adjustment.
Switched Live connections.               
Remote Run / Remote Fail connections.
Connecting a Speed Control.
Resetting Function switches.
Certification

Installation 
and Maintenance

Mains ‘C’

Twin Fan Control
CT-A

(auto duty share)

CT-M

(manual duty share)

NuAire Limited
Western Industrial EstateCaerphilly, 
CF83 1XH  United Kingdom
Telephone  029- 20 88 5911
Facsimile No. 029 2088 7033
Email: info @ nuaire. co.uk
www.nuaire.co.uk

Leaflet No. 670912
JULY  2001

1

Maintenance

The control requires no maintenance other than cleaning.
Disconnect supply and clean with a damp cloth. Do not spray
any cleaning fluids onto the control

Introduction

This control has been designed specifically to suit NuAire
Quietwin Twinfan Extract units.
Two versions of the control are available.
1)   Manual Duty Sharing  (CT-M model).
2)   Automatic Duty Sharing  (CT-A model).
Both models provide automatic change over from a failed fan to
the standby fan.  A list of unit features is shown opposite.
A general view of  the unit with overall dimensions is shown in
fig. 1.

Installing the control unit

Carefully remove the case cover (4 screws).  Drill the main case
to allow the necessary cable access. 

NOTE:
It is the responsibility of the installer to ‘seal’ the cable
entries and to maintain the IP rating of the unit.

Select a suitable surface mounting position and fix the main cas-
ing to it using the four case mounting holes  provided. (fig 2).

ISOLATE THE ELECTRICAL SUPPLY

and make your

main electrical supply and fan unit connections to the terminals
inside as shown in fig. 8.

FEATURES

IP 65 (Protection).

Remote Fail (volt free contacts).

Remote Run (volt free contacts).

Switched Live operation. 

Adjustable run on 0-60 min.

Audible failure indication.

Visual failure indication.

Auto Duty Share (CT-A only. 12 hr intervals).

Microsave compatible.

Automatic Changeover on failure.

Failure detection of fan by Hall Effect sensors. 

IMPORTANT

The installation must be carried out by qualified personnel in
accordance with the appropriate authority and conforming to all
statutory and governing regulations eg. IEE, CIBSE, COHSE etc

.
.
.
.
.
.
.
.
.
.
.

Case mounting holes

Cover fixings

Figure 1. Unit overall dimensions (mm)

Figure 2. Fixing holes

1
1
1
2
4
4
4
5
5
5
5
6

Controls Application Service (CAS) 

A team of Engineers and technicians is available to provide
pre and post order support.
We are on hand to provide help and advice from the most
basic use of any NuAire equipment to the more complex
applications, maximising on the versatility of our  control
products.

Telephone: 

029 2085 8585

Facsimile:   

029 2085 8586

The EMC directive: 89/336/EEC
with modification 92/31/EEC
The low voltage directive 73/23/EEC

200

80

150

Содержание CT-A

Страница 1: ...ary cable access NOTE It is the responsibility of the installer to seal the cable entries and to maintain the IP rating of the unit Select a suitable surface mounting position and fix the main cas ing to it using the four case mounting holes provided fig 2 ISOLATE THE ELECTRICAL SUPPLY and make your main electrical supply and fan unit connections to the terminals inside as shown in fig 8 FEATURES ...

Страница 2: ...o Control Single Phase application Three Phase application N L L SL L FL L1 L2 N H BL RD BK Y RUN FAULT Connection for speed control Link must be removed when using a speed control 1 phase fans only L1 L2 N H QUIETWIN FAN Single phase 230v MAINS CONTROL 230V 1 phase supply NOTE supply to fan is via the control Link Link NET CT AVI Audible Visual Indicator connection 230V Switched Live Connection t...

Страница 3: ...Link NET CT AVI Audible Visual Indicator connection QUIETWIN FAN Three phase 230V Switched Live Connection twinfan operates when live remove link when used Volt Free Contacts Rated 230V 5A for run indication if required Volt Free Contacts Rated 230V 5A for fail indication if required L1 L2 N H CONNECTION BOX IN FAN 4 core Earth Cable 230V 1ph 50Hz supply Three Phase fan units 1ph power for control...

Страница 4: ... the SL terminal inside the case WARNING Switching the unit OFF on the front panel Power button does not isolate the fan or the control Figure 7 Twinfan Control buttons Power Fail Fail Duty Share Fan 2 Fan 1 Explanation of the button functions Fan 1 Fan 2 Pressing either button selects that fan to run If there is a fan failure the fail indicator will remain illuminated even after the fail ure has ...

Страница 5: ...witch off 4 Do not reset this particular switch retain as set by factory Figure 13 Function switches L SL P I R sensor or Light Switch BL RD BK Y RUN FAULT ICP RR RF A B C D A volt free relay is included to provide status if any fan is running Maximum load is 5amp 230V ac When a fan is running A B are connected When a fan has failed C D are connected Figure 11 Remote Run Remote Fail connections Re...

Страница 6: ...mensions of equipment and the right is reserved to make such changes without prior notice Western Industrial Estate Caerphilly Mid Glam CF83 1XH United Kingdom Telephone 029 2088 5911 Facsimile 029 2088 7033 Email info nuaire co uk www nuaire co uk Leaflet No 670912 GP168 Installation and Maintenance TWINFAN CONTROL 5 ...

Отзывы: