Installation and Maintenance

AXUS Swift Circular Long Cased Axial Flow Fans

4.4 Control Connections

4.4.1 Mains Connections

Mains cables should be suitably sized and terminated at terminals 
shown on the appropriate diagram.

4.4.2 Control Connections

4.4.3 Switched Live (SL) terminal at the PCB

4.4.4 Damper Connections

OP - 

230V 50Hz 1A max supply to open the damper. 

CL - 

230V 50Hz 1A max supply to close the damper. 

N - 

Neutral supply to damper. 

RET - 

230V ac return signal from the damper limit switch indicates the 

damper has reached its operating position. If the return signal is not 
present, the fan will wait for 1 minute before starting.

Note: If a damper is not fitted, connect a link wire from OP to RET. This 
will cancel the delay.

4.4.5 Volt Free Relay Contacts

4.4.6 Data Cable Installation

A 4-core SELV data cable is used to connect devices.

Do not run data cable in the same conduit as the mains cables and 
ensure there is a 50mm separation between the data cable and other 
cables. The maximum cable run between any two devices is 300m 
when it is installed in accordance with the instructions.

Please note that the total data cable length used in any system must 
be less than 1000m. Keep the number of cable joints to a minimum to 
ensure the best data transmission efficiency between devices.

4.4.7 Maximum Number Of Devices

The maximum number of devices (including fans) that can be 
connected together via the cable is 32, irrespective of their functions.

4.4.8 Other Low Voltage Cables e.g. BMS Signal

Follow the basic principle (as per section 4.4.6). Keep the cable run as 
short as possible, maximum cable length of 50m. If the cable is longer 
than 12m, Nuaire recommend using screened cable with the screening 
grounded at one end only (preferably at the inverter end).

4.4.9 Other Low Voltage Cables e.g. BMS Signal

Follow the basic principle (as per section 4.4.6). Keep the cable run as 
short as possible, maximum cable length of 50m. If the cable is longer 
than 12m, Nuaire recommend using screened cable with the screening 
grounded at one end only (preferably at the inverter end).

4.4.10 BMS Input Signals

The BMS connection is made with a plug-in connector 
via the socket (see fig. 11).

To ensure the connection is made only by suitably 
qualified and authorised personnel the plug is not 
supplied.

It is available from R S Components,  
Part No. 403-875 or Farnell, Part No. 963-021.

The system’s response to a 0-10V dc BMS signal is given in the 
following table.

Note: 
The BMS signal will override any sensors and user control connected in 
the system. The voltage tolerance is +/- 125mV and is measured at the 
fans terminal.

IMPORTANT

Reversal of the BMS connection will damage the 

control.

Mains Connection
230V 50Hz 1 phase

N E

L

SL

Remove link if switched live signal,
an enabler or BMS signal is connected. 

All wiring is 1Ph 230V 50Hz

230V 

motor

S4

2

S6

1

RET

OP       CL         N       

All wiring is 1Ph 230V 50Hz

230V 

motor

RET

N       

CL        

OP      

White      

Brown      

Blue     

A fan starting
delay of 1 minute
is imposed to 
enable the damper
to open.
To override the 
delay, fit a link here  

A fan starting
delay of 1 minute
is imposed to 
enable the damper
to open.
To override the 
delay, fit a link here  

Fault Signal

FAULT

Run Signal

RUN

0V

0 -

 10

V

BMS

Figure 6. ‘Net’ 
connection 
for Ecosmart 
devices.

Figure 7.  

Net -

 The 4 IDC plug-in connectors are provided for the connection of 

compatible sensors, manual controls and for linking the fans together 
under a common control. If more than 4 connections are required, 
the junction box (product code ES-JB) should be used (data cable 
installation).

A signal of 100-230V a.c. will activate the fan from either its off state 
or trickle state (see setting to work-trickle switch). When the SL is 
disconnected the fan will over-run for 1 – 60 minutes (see fig. 12).

Do not take this signal from an isolating transformer.

Figure 8. Drive 
Open / Spring close.

Figure 9. Drive 
Open / Drive Close

Figure 10.  

Note that the volt free contacts are not fused. If these are used to 
power any external equipment, the installer must provide adequate 
fusing or other protections. 
These contacts are rated at 5A resistive, 0.5A inductive.

Run connections - 

These contacts are closed when the fan is running.

Fault connections -

 No fault = the contacts are closed.

 

   

Fault = the contacts are opened.

Figure 11.  

Содержание AXUS SWIFT Series

Страница 1: ...lso be referred to before handling and installation Any damages or deviations should be immediately reported to the seller supplier agent quoting the order and product details from the product rating...

Страница 2: ...35 C up to 85 relative humidity The controller must be fitted to a vertical vibration free wall with appropriate fasteners and for ease of installation the cover should be removed and the casing separ...

Страница 3: ...L Control SPCON 460V 3 phase 60Hz supply 380V 3 phase 60Hz supply 400V 3 phase 50Hz supply L1 L2 L3 STAR L1 U1 L2 V1 L3 W1 Link W2 U2 V2 U1 V1 W1 W2 U2 V2 L1 L2 L3 400V 3 phase 50Hz supply 380V 3 phas...

Страница 4: ...kle Test 1 0 Pwr Standby Fan 1 Fan 2 Heating Cooling Fault Frost Tx Rx Ecosmart Earth DAMPER FAULT RUN E L3 N L2 L1 E N L1 L2 L3 Mains supply connections 400V 50Hz 3ph Neutral via local isolator 1 3 5...

Страница 5: ...creened cable with the screening grounded at one end only preferably at the inverter end 4 4 10 BMS Input Signals The BMS connection is made with a plug in connector via the socket see fig 11 To ensur...

Страница 6: ...sired airflow Remove the link wire if not required fig 7 5 3 2 Setting The Minimum Trickle Airflow Rate Nomial 20 Repeat the same procedure as for maximum airflow above but without the link wire betwe...

Страница 7: ...UK mainland and in accordance with Clause 14 of our Conditions of Sale Customers purchasing from outside of the UK should contact Nuaire International Sales office for further details 9 0 After Sales...

Отзывы: