Installation Manual

5.3 Wiring Connections

5.3.1 Mains Connections

Mains cables should be suitably sized and terminated at terminals 
shown on the appropriate diagram.

5.3.2 Control Connections

NET - 

4 IDC plug-in connectors are provided for the connection of 

compatible sensors, manual controls and for linking the fans together 
under a common control. If more than 4 connections are required, 
the junction box (product code ES-JB) should be used (see data cable 
installation). 

23 

Control Connections

5.3.3 Switched Live (SL) Terminal

A signal of 100-230V a.c. will activate the fan from either its off 
state or trickle state (see setting to work-trickle switch). When the 
SL is disconnected the fan will over-run (see setting to work-timer 
adjustment). 

Do not take this signal from an isolating transformer. 

24 

Switched Live Terminal

Mains Connection
Pre-wired
230V 50Hz  1Phase

Remove link if Switched Live signal, 
an enabler or BMS signal is connected

Terminals or PCB

N E L SL

5.3.4 Damper Connections

OP -

 230V 50Hz 1A max supply to open the damper

CL -

 230V 50Hz 1A max supply to close the damper

N -

 Neutral supply to damper

RET - 

230V ac return signal from the damper limit switch indicates the 

damper has reached its operating position. If the return signal is not 
present, the fan will wait for 1 minute before starting. 

If a damper is 

not fitted, connect a link wire from OP to RET. This will cancel the 
delay. 
 

25 

Drive Open / Drive Close Damper Connection

All wiring is 1PH 230V 50Hz

A fan starting delay 
of 1 minute is 
imposed to the 
enable the damper 
to open.
To override the 
delay fit a link here.

230V

motor

OP

CL

N

RET

2

S4

S6

1

 
 

 
 

26 

Drive Open / Spring Close Damper Connection

All wiring is 1PH 230V 50Hz

A fan starting delay 
of 1 minute is 
imposed to the 
enable the damper 
to open.
To override the 
delay fit a link here.

A fan starting delay 
of 1 minute is 
imposed to the 
enable the damper 
to open.
To override the 
delay fit a link here.

OP

White

Brown

Blue

CL

N

RET

230V

motor

5.3.5 Volt Free Relay Contacts

27 

Volt Free Relay Contacts

RUN

FAULT

Run Signal

Fault Signal

5.3.6 Data Cable Installation

A 4-core SELV data cable is used to connect devices such as sensors to 
the fan and for interconnecting multiple fan units. 

For good EMC engineering practice, any sensor or low voltage data 
cables should not be placed within 50mm of mains cables or placed 
on the same cable tray or conduit as mains cables.

The maximum cable run between any two devices is 300m when it 
is installed in accordance with the instructions. The total data cable 
length used in any system must be less than 1000m. Keep the number 
of cable joints to a minimum to ensure the best data transmission 
efficiency between d 50m or less for ES-LCD.

5.3.7 Maximum Number Of Devices

The maximum number of devices (including fans) that can be 
connected together via the data cable is 32, irrespective of their  
functions.

Содержание AV55-MSS

Страница 1: ...l not play with the appliance Cleaning and user maintenance shall not be carried out by children 1 1 Symbols GENERAL WARNING Signifies a general warning regarding hazard specified by supplementary information ELECTRIC SHOCK This unit must be completely electrically isolated before any panels are removed Check mains supply and control connections ROTATING PARTS This unit contains fast moving rotati...

Страница 2: ...sembly positioned in series for optimum performance Units incorporate fully detachable top or bottom panels for maintenance and inspection purposes AVS 1 units have a loose control module for surface mounting up to 1 metre away from main unit AVS 8 and 9 units incorporate split access panels 2 1 Code Description 1 2 3 4 AV S CP 1 1 Range Aire Volve 2 Fan Type S Single Fan 3 Constant Pressure CP Co...

Страница 3: ...mounting feet supplied with access panel positioned for underside access Figure 2 3 4 5 Vertically Wall Mounted Rigid Units Utilising the Aire Volve Vertical Hanging Bracket kit that includes wall hanging brackets and hinges Figures 5 and 6 The unit case has captive M8 nuts which can be used after removing the M8 plugging screws Units should always be positioned with sufficient space to allow the ...

Страница 4: ...talled NAV 2 5 Floor Mounted Application 4 7 Dimensions mm Weights kg 4 7 1 AVS Units 12 AVS Dimensions A C D B B1 A1 Unit Code A A1 Bracket Centre Points B B1 Bracket Centre Points C D Weight kg AVS1 580 344 535 576 246 200 27 AVS2 615 380 535 646 281 200 24 AVS3 745 510 672 713 329 250 43 AVS4 788 553 672 713 373 315 47 AVS4L 914 678 818 860 391 315 67 AVS5 914 678 818 860 428 315 66 AVS6 1087 8...

Страница 5: ...3 AVS7 MSS Standard 1000 1013 575 41 AVS7 MSL Large 1500 1013 575 98 AVS8 AVS8 MSM Mini 500 1237 615 51 AVS8 MSS Standard 1000 1237 615 83 AVS8 MSL Large 1500 1237 615 114 AVS9 AVS9 MSM Mini 500 1237 615 51 AVS9 MSS Standard 1000 1237 615 92 AVS9 MSL Large 1500 1237 615 125 4 8 Unit Access Unit can be installed inverted for ease of access to control e g control opposite side If inverted it will re...

Страница 6: ...ncer Floor Mounted Unit And Inlet Silencer 17 Silencer Alignment Brackets 18 Installed AVS Silencer 4 10 AVSCP Constant Pressure Range Ecosmart constant pressure extract fans are supplied to control the static pressure at the fan inlet This set up is suitable for the majority of applications However when ancillaries with high pressure losses are fitted to the fan s inlet side the low pressure tapp...

Страница 7: ... Ecosmart devices Min Max SL run on Trickle 0 1 Link wire see note Test Connection ES CO2 BMS Input Signal 0V 0 10V Ecosmart Pwr Standby Fan 1 Heating Fan 2 Cooling Fault TX RX Frost N L SL DP CL N RET Heat Demand Run Fault N L1 L3 L2 L3 L2 L1 N 400V 3ph 50Hz Supply Local isolator by others E 21 AVS9 Wiring Diagram 5 1 3 Control Module Volt Free Contact RUN signal 0 5A inductive 5A resistive Volt ...

Страница 8: ... minute before starting If a damper is not fitted connect a link wire from OP to RET This will cancel the delay 25 Drive Open Drive Close Damper Connection All wiring is 1PH 230V 50Hz A fan starting delay of 1 minute is imposed to the enable the damper to open To override the delay fit a link here 230V motor OP CL N RET 2 S4 S6 1 26 Drive Open Spring Close Damper Connection All wiring is 1PH 230V ...

Страница 9: ...cosmart products and will have indicators for functions that are not available in this particular fan However these indicators will not be illuminated A Commissioning Procedure document Document No 671153 is available on request from Nuaire 29 Commissioning Panel Details LED indicators Max Min Trickle Test 1 0 Pwr Standby Fan 1 Fan 2 Heating Cooling Fault Frost Tx Rx MIN Minimum speed adjustment M...

Страница 10: ...Annually Thoroughly inspect the unit and its components for corrosion acting immediately to treat restore any damaged areas All electrical terminals within the unit should be tightened Check all earth connections Check control dampers blades Check operation of damper actuators and linkages and adjust as necessary 8 0 WARRANTY The 5 year warranty starts from the day of delivery and includes parts a...

Страница 11: ...11 24 02 22 Document Number 671572 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk AVS Installation Manual NOTES ...

Страница 12: ...12 24 02 22 Document Number 671572 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk AVS Installation Manual NOTES ...

Отзывы: