Nuaire Group MRXBOX95B-LP1 Скачать руководство пользователя страница 3

2.5 Air permeability and 
infiltration

Is the uncontrolled exchange of air between inside and outside

through cracks, porosity and other unintentional openings in

the building. ADF2006 gives an allowance for this in both multi

and single storey buildings, however ADF2010 has an

allowance for multi storey only. Additionally ADF2010  only

applies this allowance for dwellings leakier than 5 m

3

/(h.m

2

) at

50Pa. (See below).

2.6 ADF 2006 Ventilation 
calculations
Continuous supply and extract

Step 1: 

Determine the whole building ventilation rate 

from Table

2.

Allow for infiltration by subtracting from this value:

for multi-storey dwellings: 0.04 x gross internal volume of 

the dwelling heated space (m

3

);

for single-storey dwellings: 0.06 x gross internal volume of 

the dwelling heated space (m

3

).

Step 2: 

Calculate the whole dwelling air extract rate at 

maximum operation by summing the individual room rates for

‘minimum high rate’ 

from Table 1.

(For sanitary accommmodation only, as an alternative, the

purge ventilation provisions given in ADF 2006 can be used

where security is not an issue. In this case ‘minimum high

extract rate’ for the sanitary accommodation should be omitted

from the step 2 calculation).

Step 3: 

The required airflow rates are as follows:

the maximum extract rate (e.g. boost) should be at least 

the greater of step 1 and step 2. Note that the maximum 

individual room extract rate should be at least those given 

in table 1

. for minimum high rate.

the minimum air supply rate should be at least the whole 

building ventilation rate found in step 1.

2.7 ADF 2010 Ventilation 
calculations
Design of MVHR systems

The MVHR system has been sized for the winter period.

Additional ventilation may be required during the warmer

months and it has been assumed that the provisions for purge

ventilation (e.g. openable windows) could be used.

Step 1:

For any design air permeability, determine the whole

dwelling ventilation supply rate 

from Table 2.

As an alternative where the design air permeability is intended

to be leakier than (>) 5m

3

/(h.m

2

) 50 Pa, allow for infiltration

for all dwelling types by subtracting from the whole dwelling

ventilation supply rate 

from Table 2

; 0.04 x gross internal 

volume of the dwelling heated space (m

3

).

Step 2:

Calculate the whole dwelling extract ventilation rate by

summing the individual room rates for ‘minimum high rate’ 

from

Table 1.

(For sanitary accommmodation only, as an alternative, the

purge ventilation provisions given in ADF 2010 can be used

where security is not an issue. In this case ‘minimum high

extract rate’ for the sanitary accommodation should be omitted

from the step 2 calculation).

Step 3: 

The required airflow rates are as follows:

the maximum whole dwelling extract ventilation rate 

(e.g. boost) should be at least the greater of step 1 and 

step 2. 

Note that the maximum individual room extract rate should 

be at least those given

in table 1.

for minimum high rate.

the minimum air supply rate should be at least the whole 

building ventilation rate found in step 1.

For Scotland refer to BRE Digest 398.

3

24. 06. 13. Leaflet Number 671582

Installation and Maintenance

MRXBOX95B-LP1 Mechanical Ventilation with Heat Recovery & Summer Bypass

Any air intake terminal MUST be installed in accordance with the

appropriate regulation. 

As a guide, the BS5440 series of British Standards deals with

this issue and currently states that an air intake must be at a

minimum distance of 300mm from a gas boiler balanced flue.

Installers are advised to be aware of the requirements of this

standard when installing ‘through the wall’ supply air ducting.

Similarly, supply and extract air grilles should be at least

300mm apart.

Pre Commissioning MRXBOX95
MVHR Units

MRXBOX95 units are designed to ventilate the whole

dwelling and must not be used during site construction 

or the clean-up period. Cement and plaster dust can be

abrasive and can affect fan performance and reliability. 

Please ensure that the filters are checked prior to 

commissioning to ensure there is no build-up of dust or

debris.

While the property is drying out, very high moisture levels

are likely to occur.  Therefore it is advisable that if the 

installation and building works are complete the unit is

left running. If the building works are not complete please

close the air valves or cover up the air valves to prevent

condensation forming in the ductwork and the

MRXBOX95 unit due to natural migration of warm air.  

Содержание MRXBOX95B-LP1

Страница 1: ...the appropriate standards Ensure that the mains supply Voltage Frequency and Phase complies with the rating label Please note a clear working space is required around the installed unit to allow the c...

Страница 2: ...uld be adjustable valve types not supplied External grilles to have a minimum free area of 12 250 sq mm 2 3 Ducting Before commencing ducting installation reference should be made to building regulati...

Страница 3: ...the whole dwelling ventilation supply rate from Table 2 0 04 x gross internal volume of the dwelling heated space m3 Step 2 Calculate the whole dwelling extract ventilation rate by summing the individ...

Страница 4: ...n ceilings Exhaust air from kitchen bathroom to outside via air brick Part no PVC505NS Supply and extract ducts from external air bricks to the unit needs to be insulated Minimum 300mm Top of ceiling...

Страница 5: ...rey Green yellow Unit serving kitchen and bathroom Unit serving kitchen and two bathrooms Figure 8 Figure 9 For good EMC engineering practice any sensor cables or switched live cables should not be pl...

Страница 6: ...nt further adjustment 6 Once commissioned the home owner tenant should be informed that the unit should not be adjusted as it will have a detrimental effect on the indoor air quality and could result...

Страница 7: ...nge speed This is normal and will have no adverse effect on the fan The speed will return to normal once the interference has subsided 5 0 INSTALLATION REQUIREMENTS In addition to the particular requi...

Страница 8: ...ings assessed under The Building Regulations 2010 specifically SAP 2009 and Approved Documents L and F Completion of this document is therefore only required for dwellings assessed by SAP 2005 Custome...

Страница 9: ...r to overcome particular obstructions If flexible ducting has been used has it been pulled taut to minimise system resistance Has the number of duct bends been minimised to ensure adequate air flow an...

Страница 10: ...y unit been fixed to a stable element of the building fabric e g wall or floor using manufacturer recommended supplied fixing brackets Has the condensation drain been fitted and the pipe insulated Hav...

Страница 11: ...or N A Has the rating label been verified to establish suitability for the installation strategy and whether an earth is required e g voltage class I or II product status Has a local isolator been pro...

Страница 12: ...tion grilles been locked where possible to minimise unapproved occupant adjustment Figure 3 Ensure all external and internal windows and doors are closed Set fan speed using manufacturer data table Se...

Страница 13: ...e customer been advised that opening windows is not recommended during normal use in order to ensure the energy efficient operation and performance of the balanced system Has the customer been advised...

Отзывы: