The unit must remain switched on at all times to maintain
ventilation within the dwelling. Turning the unit off will
cause long term damage to the unit and building fabric.

This appliance is not intended for use by persons 
(including children) with reduced physical, sensory or
mental capabilities, or lack of experience and knowledge,
unless they have been given supervision or instruction
concerning the use of the appliance by a person for their
safety. Children should be supervised so that they do not
play with the appliance.

MRXBOX95B-LP1

Mechanical Ventilation Unit with Heat Recovery 

& Summer Bypass for Ceiling Void Mounting

Installation and Maintenance

1.0 Introduction

MRXBOX95B-LP1 ceiling void mounted unit is designed to 
provide mechanical supply and extract ventilation with heat
recovery and incorporates summer bypass.

The unit is fitted with two independent fans. Each fan has full

speed control for background and boost ventilation rates. 

To recover heat from the extract air the heat exchanger block 

is utilised. The heat exchanger can recover up to 80% of the 

normally wasted heat.

The bypass damper opens automatically via a wax actuator when

the outside air reaches 20°C, when the outer air temperature

returns below this level the unit returns to its original state.

Outside air supplied through the bypass is still being filtered, 

so the air quality is optimal, irrespective of the bypass setting

(open or closed).

The unit is fitted with a frost protection mode, in the event of the

fresh air temperature dropping below -5 Deg C the supply fan will

switch off. The unit will then automatically switch back on when

the temperature raises back above -5 Deg C.

2.0 Installation

Installation must be carried out by competent personnel in

accordance with the appropriate authority and conforming 

to all statutory governing regulations. All mains wiring must 

be in accordance with the current I.E.E. Regulations, or the

appropriate standards. Ensure that the mains supply (Voltage,

Frequency and Phase) complies with the rating label. 

Please note a clear working space is required around the

installed unit to allow the cover to be removed and provide 

sufficient access for maintenance such as filter change.

The fan must be installed indoors, in a suitable ceiling void

away from direct sources of frost, heat, water spray or 

moisture generation. For a vibration-free result the unit must

be mounted to a solid surface in the void.

The unit is designed for ceiling mounting only (Horizontal 

surface).

1. The unit is supplied with a steel mounting bracket.

2. Position & secure the steel bracket to the ceiling using 

appropriate fixings (supplied by others), ensuring that the  

two outer fixing holes on the unit are accessible.

Note: The mounting bracket should be on the same side as the
condensate take off.

3. The unit can now be offered into position & located into the 

mounting bracket.

4. Using appropriate fixings (supplied by others), fix the unit to 

the ceiling. It is recommended that the unit is fixed through 

three holes on the non-bracket side and the two outer holes on

the bracket side.

Nuaire Limited

Western Industrial Estate  Caerphilly  United Kingdom  CF83 1NA  

T: 029 2085 8400  F: 029 2085 8444  E: [email protected]  W: www.nuaire.co.uk

1

24. 06. 13. Leaflet Number 671582

Spigot 1.

Spigot 4.

Spigot 3. 

Spigot 2.

Figure 1. Airflow through unit.

Spigots 1 to 4

1.

Intake air (Fresh Air from outside).

2. Supply Air (Supply in to house).

3. Extract Air (Warm air from house).

4. Exhaust Air (Waste air to outside).

The EMC Directive 
2004/108/EC  
The Low Voltage 
Directive 
2006/95/EC

Figure 2. Installing the unit using appropriate fixing bolts.

204 x 60mm 
ducting in 
ceiling void.

Side view of unit 
mounted in the ceiling void.

Air valve 
in ceiling.

Figure 3. Typical side view example of a unit mounted in a ceiling
void using 204 x 60mm rectangular ducting and air valves.

Steel mounting bracket

Note: The unit must be installed in an upright position as 
shown for the condensate drain and for compliance with safety
regulations relating to IP protection for water drip ingress.

Содержание MRXBOX95B-LP1

Страница 1: ...the appropriate standards Ensure that the mains supply Voltage Frequency and Phase complies with the rating label Please note a clear working space is required around the installed unit to allow the c...

Страница 2: ...uld be adjustable valve types not supplied External grilles to have a minimum free area of 12 250 sq mm 2 3 Ducting Before commencing ducting installation reference should be made to building regulati...

Страница 3: ...the whole dwelling ventilation supply rate from Table 2 0 04 x gross internal volume of the dwelling heated space m3 Step 2 Calculate the whole dwelling extract ventilation rate by summing the individ...

Страница 4: ...n ceilings Exhaust air from kitchen bathroom to outside via air brick Part no PVC505NS Supply and extract ducts from external air bricks to the unit needs to be insulated Minimum 300mm Top of ceiling...

Страница 5: ...rey Green yellow Unit serving kitchen and bathroom Unit serving kitchen and two bathrooms Figure 8 Figure 9 For good EMC engineering practice any sensor cables or switched live cables should not be pl...

Страница 6: ...nt further adjustment 6 Once commissioned the home owner tenant should be informed that the unit should not be adjusted as it will have a detrimental effect on the indoor air quality and could result...

Страница 7: ...nge speed This is normal and will have no adverse effect on the fan The speed will return to normal once the interference has subsided 5 0 INSTALLATION REQUIREMENTS In addition to the particular requi...

Страница 8: ...ings assessed under The Building Regulations 2010 specifically SAP 2009 and Approved Documents L and F Completion of this document is therefore only required for dwellings assessed by SAP 2005 Custome...

Страница 9: ...r to overcome particular obstructions If flexible ducting has been used has it been pulled taut to minimise system resistance Has the number of duct bends been minimised to ensure adequate air flow an...

Страница 10: ...y unit been fixed to a stable element of the building fabric e g wall or floor using manufacturer recommended supplied fixing brackets Has the condensation drain been fitted and the pipe insulated Hav...

Страница 11: ...or N A Has the rating label been verified to establish suitability for the installation strategy and whether an earth is required e g voltage class I or II product status Has a local isolator been pro...

Страница 12: ...tion grilles been locked where possible to minimise unapproved occupant adjustment Figure 3 Ensure all external and internal windows and doors are closed Set fan speed using manufacturer data table Se...

Страница 13: ...e customer been advised that opening windows is not recommended during normal use in order to ensure the energy efficient operation and performance of the balanced system Has the customer been advised...

Отзывы: