09. 04. 15. Leaflet Number 671683

2.1 Condensate Drain

1.

The condensate must be discharged under a water

level in a U-trap drainpipe or an alternative drain method 

which acts as an airlock.  

2. This condensate discharge connection is suitable for 21.5mm

dia. overflow pipe. 

Solvent cement should be used to make the joint. 

3. If using a U-trap please ensure the U-trap has been filled to 

a suitable level of water to avoid any air locks.

4. If the condensation pipe is fitted in an unheated space the 

pipe should be in insulated to prevent freezing. 

Nuaire recommend MVHR-DRAIN be used as the primary

condensate take-off. (see figure 5b and 5C.

2.2 Extract/input areas

The unit is designed to extract air from all wet rooms 

e.g. bathroom, kitchen, en-suite, utility room (with sink). 

WC’s do not need to be ventilated if openable windows 

are fitted.

Supply air should be to all habitable rooms e.g. bedrooms and

lounge. Extract / input grilles should be adjustable valve types

(not supplied).

External grilles to have a minimum free area of 12,250 sq mm.

2.3 Ducting

Before commencing ducting installation reference should be

made to building regulations document “Domestic ventilation

compliance guide”. This document supports ADF2010 and

details installation, testing and commissioning of all ventilation

systems.

It is recommended that rigid ducting be used it all times. 

Flexible ducting has a very high resistance and it is impossible

to calculate how much resistance will be on a system if used.

If used the flexible ducting must be kept to a minimum and

should always be pulled taut. A maximum of 500mm should 

be used on each leg.

To prevent condensation on the outside of the outside air inlet

duct and the air outlet duct from the MRXBOX95-WM2, these

ducts should be insulated. 

Ducting must be installed in such a way that resistance to 

airflow is minimised. Bends should be kept to a minimum.

A minimum distance of 200mm between the appliance and 

any bends in ductwork is recommended.

Ideally 150mm diameter or 204 x 60mm rectangular ducting

should be used. (Refer to dwelling design drawing, figure 7a

and 7b on page 4 for further information).

Ducting joints must be sealed with silicone type sealant and

shall be adequately and reliably fixed to the appliance.

2.4 Ventilation flow rates

Table 1.

ADF2006 / 2010  – Extract ventilation rates

Room

Min high rate

Min low rate

Kitchen

13 l/s

Utility room

8 l/s

Bathroom

8 l/s

Sanitary 

accommodation

6 l/s

Table 2.

Whole dwelling ventilation rates

Number of bedrooms in dwelling

1

2

3

4

5

Whole

13

17

21

25

29

dwelling 

ventilation 

rate l/s

1, 2

Notes:

1,

In addition, the minimum ventilation rate be should be not

less than 0.3 l/s per m

2

of internal floor area. 

(This includes all floors, e.g. for a two-story building add the

ground and first floor areas).

2,

This is based on two occupants in the main bedroom and

a single occupant in all other bedrooms. This should be used

as the default value. If a greater level of occupancy is

expected add 4 l/s per occupant.

Installation and Maintenance

MRXBOX95AB-WM2 Mechanical Ventilation with Heat Recovery and Summer Bypass

Any air intake terminal MUST be installed in accordance with the

appropriate regulation. 

As a guide, the BS5440 series of British Standards deals with

this issue and currently states that an air intake must be at a

minimum distance of 300mm from a gas boiler balanced flue.

Installers are advised to be aware of the requirements of this

standard when installing ‘through the wall’ supply air ducting.

Similarly, supply and extract air grilles should be at least

300mm apart.

Figure 5a. Wet option.

Condensate pipe 

connection to unit and 

a typical example of 

a “U” trap drainpipe.

Figure 5b. MVHR-DRAIN option. 

Condensate drain, uninsulated drain 

pipe with 10o fall running to SVP.

5

Drop

Collar

Total extract rate should

be at least the whole

dwelling ventilation rate

given in table 2.

To SVP 

“T” piece 

MVHR Drain 

To unit 

To CONTRAP 

Figure 5c. 

IMPORTANT: When using a “T” Piece to connect the

CONTRAP drainage and the MVHR drain pipework the MVHR

drain must always be fitted before the “T” Piece to prevent 

condensate from feeding back into the MVHR system. 

Содержание MRXBOX95AB-WM2QA11665

Страница 1: ...ing the warmer months 2 0 Installation Installation must be carried out by competent personnel in accordance with the appropriate authority and conforming to all statutory governing regulations All ma...

Страница 2: ...nded Ideally 150mm diameter or 204 x 60mm rectangular ducting should be used Refer to dwelling design drawing figure 7a and 7b on page 4 for further information Ducting joints must be sealed with sili...

Страница 3: ...boost should be at least the greater of step 1 and step 2 Note that the maximum individual room extract rate should be at least those given in table 1 for minimum high rate n the minimum air supply ra...

Страница 4: ...Minimum 300mm Air supply to lounge via Air Valve Part no VS125 in ceilings Extract air from kitchen bathroom via Air Valve Part no VS125 in ceilings Air supply to bedrooms via Air Valve Part no VS125...

Страница 5: ...0Hz Room lights Light switches Double Pole N L 3 Pole isolator 3 Pole isolator Kitchen switch Kitchen switch Blue Brown Black Optional summer boost switch Supply cord from unit Green yellow Blue Brown...

Страница 6: ...cked in place to prevent further adjustment 6 Once commissioned the home owner tenant should be informed that the unit should not be adjusted as it will have a detrimental effect on the indoor air qua...

Страница 7: ...ated before carrying out any work Note The supply cable must be replaced by an electrically competent person When ordering spare parts please quote the serial number of the unit and the ARC number of...

Страница 8: ...have no adverse effect on the fan The speed will return to normal once the interference has subsided 5 0 INSTALLATION REQUIREMENTS In addition to the particular requirements given for the individual...

Страница 9: ...ings assessed under The Building Regulations 2010 specifically SAP 2009 and Approved Documents L and F Completion of this document is therefore only required for dwellings assessed by SAP 2005 Custome...

Страница 10: ...r to overcome particular obstructions If flexible ducting has been used has it been pulled taut to minimise system resistance Has the number of duct bends been minimised to ensure adequate air flow an...

Страница 11: ...y unit been fixed to a stable element of the building fabric e g wall or floor using manufacturer recommended supplied fixing brackets Has the condensation drain been fitted and the pipe insulated Hav...

Страница 12: ...or N A Has the rating label been verified to establish suitability for the installation strategy and whether an earth is required e g voltage class I or II product status Has a local isolator been pro...

Страница 13: ...tion grilles been locked where possible to minimise unapproved occupant adjustment Figure 3 Ensure all external and internal windows and doors are closed Set fan speed using manufacturer data table Se...

Страница 14: ...e customer been advised that opening windows is not recommended during normal use in order to ensure the energy efficient operation and performance of the balanced system Has the customer been advised...

Отзывы: