Nu-Way PO160 Скачать руководство пользователя страница 37

P Series Commissioning

Page D.2

IIIII

NDIVIDUAL

NDIVIDUAL

NDIVIDUAL

NDIVIDUAL

NDIVIDUAL

  S

  S

  S

  S

  S

ETTING

ETTING

ETTING

ETTING

ETTING

  R

  R

  R

  R

  R

ECORD

ECORD

ECORD

ECORD

ECORD

This manual contains commissioning sheets (Page

D.11) of essential information that should be

completed by the commissioning engineer with

individual details of the burner. These details

should be verified periodically and changed as

adjustments occur.

SSSSS

AFETY

AFETY

AFETY

AFETY

AFETY

IIt is essential that commissioning be undertaken

only by suitably qualified and experienced

personnel. In the case of P Series Burners,

commissioning engineers should be experienced

in commissioning forced draught, fully modulating

oil burners.
Nu-way can accept no responsibility for

consequential loss, damage or injury, which results

from a failure to follow the commissioning

instructions provided or from commissioning

procedures being undertaken by unqualified

personnel.

It is the commissioning engineer’s responsibility

to ensure that all settings are in accordance with

the appropriate local standards and applicable

codes of practice.

EEEEE

MERGENCY

MERGENCY

MERGENCY

MERGENCY

MERGENCY

  I

  I

  I

  I

  I

NSTRUCTIONS

NSTRUCTIONS

NSTRUCTIONS

NSTRUCTIONS

NSTRUCTIONS

P Series Burners are designed and constructed to

meet all applicable European Directives.
When used in accordance with the instructions

provided, P Series Burners are unlikely to produce

a hazardous condition. If, however, such a

condition should arise in connection with the

burner, the appliance or any instrument, machine

or service in the vicinity of the burner, the 

FUEL

AND ELECTRICITY SUPPLIES SHALL BE

ISOLATED IMMEDIATELY

 and they shall remain

isolated until the fault has been identified and

rectified.

IIIII

NSPECTION

NSPECTION

NSPECTION

NSPECTION

NSPECTION

Before commissioning is started it is important to:
-

Check that the electrical wiring is complete

and complies with all applicable Codes and

Standards.

-

Ensure that the fuses are fitted and are of the

correct ratings.

-

Check electrical earthing.

-

Verify that the oil pipework is correctly sized

and that it has been checked for leakage.

-

Check that the appropriate modulating

detector which is supplied loose with each

burner, is fitted correctly to the appliance.

(Technical Specification Pages C.2).

-

Make all personnel involved in the

commissioning aware of the location of the

emergency oil and electricity isolation points.

-

Check that the appliance's ventilation and

flueing arrangements are adequate.

-

Ensure that any warning notices appropriate

to the commissioning procedure are in

position.

-

Ensure that all necessary tools and test

equipment are available and ready for use.

Essential items include temperature

measuring instruments for measuring flue gas

and appliance water temperatures, and a

means of analysing the flue products for

carbon dioxide (CO

2

), oxygen (O

2

), carbon

monoxide (CO) and smoke.

-

Check that all relevant documentation is

available, including, where appropriate:
-

The agreed plant performance

specification.

-

Plant drawings and pipework layouts.

-

Electrical logic and wiring diagrams.

-

Certificates confirming satisfactory

completion of procedures such as

soundness testing, purging and

electrical safety tests.

-

Commissioning, operating, emergency

shutdown and maintenance

instructions for the plant.

-

Establish that the operation of plant other

than that being commissioned will not have

an adverse effect on the operation of the

plant to be commissioned, and similarly, that

the operation of the plant to be

commissioned will not have an adverse effect

on other plant.

-

Confirm that the operation of adjacent plant

and machinery will not constitute a hazard

to the personnel involved in commissioning.

-

Establish that the appliance is in an

appropriate and safe condition to be fired;

for example, that there is water in the boiler.

-

Set the appliance controls to call for heat.

Содержание PO160

Страница 1: ...Installation Maintenance Manual PO Series Automatic Oil Burner Fully Modulating Oil Burner Tel 44 0 1905 794331 Fax 44 0 1905 794017 Email info nu way co uk Web www nu way co uk ...

Страница 2: ...al Power Supply B 4 BURNER PACKAGING ASSEMBLY AND INSTALLATION B 4 Packaging For Transit B 4 Assembly And Installation B 4 Fitting To The Appliance B 4 Air Supply B 5 Combustion Chamber Conditions B 5 Electrical Power Supply B 5 TECHNICAL SPECIFICATION C 1 BURNER SPECIFICATION SHEET C 2 BURNER AND COMPONENT IDENTIFICATION C 3 BURNER OPERATION C 3 BURNER CONTROLS C 3 Modulating Unit C 3 Flame Monit...

Страница 3: ...NG SHEET OIL D 11 E OPERATION AND MAINTENANCE E 1 NORMAL OPERATION E 2 Automatic Modulation E 2 ROUTINE SAFETY CHECKS E 2 Combustion Air E 2 Flame Detector E 2 Combustion Air Pressure Switch E 2 ROUTINE MAINTENANCE E 2 Combustion Air Fan E 2 Burner Inner Assembly E 3 Oil Filters E 3 Oil Preheater E 3 FAULT FINDING E 3 Modulating System E 3 Incorrect Rotation of the Fan Motor E 3 Fan Motor Fails To...

Страница 4: ...P Series Burners are unlikely to produce a hazardous condition If however such a condition should arise in connection with the burner the appliance or any instrument machine or service in the vicinity of the burner the FUEL AND ELECTRICITY SUPPLIES SHALL BE ISOLATED IMMEDIATELY and they shall remain isolated until the fault has been identified and rectified E E E E EUROPEAN UROPEAN UROPEAN UROPEAN...

Страница 5: ...Page B 1 PO Series General Information GENERAL INFORMATION ...

Страница 6: ...wn on the Burner Specification Sheet on Page C 2 Technical Details Fuel The PO is available in two forms to use distillate or residual fuel oils Controls The control panel housed in a free standing or wall mounted cabinet is a purpose designed and robustly constructed unit that complies with relevant Standards and Codes of Practice and can be tailored to individual customer requirements Depending ...

Страница 7: ...The Table on Page B 7 shows the temperatures and pressures for Class D E F and G oils Oil Deliveries It is good practice to shut down boilers whilst the delivery of oil is made and allow 30 minutes for oil sediment to settle out before re starting the burners Ring Main System The oil from the tank must be supplied to the burner from a pumped ring main system A typical system is shown on Page B 8 T...

Страница 8: ...nsure that the appliance is in good condition Any doubt about the suitability of the appliance should be referred to the manufacturer To assemble the burner 1 Fit the burner head to the prepared appliance front plate 2 Ensure that the joint between the burner and the mounting flange is sealed effectively using the gasket provided The flame tube should not generally extend beyond the inner face of ...

Страница 9: ... Black L2 and Grey L3 and Blue N in three phase power circuits from 1 June 2006 Full details of the changes can be found in Amendment No 2 AMD 14905 to BS 7671 2001 which is a free download from the IEE website www iee org cablecolours They are also within the new version of BS7671 2001 Incorporating Amds 1 2 published on 31st March this new version of the Wiring Regulations can be identified by i...

Страница 10: ...e to the wiring diagrams provided in the instruction pack that is supplied with all P Series burners and to those wiring diagrams in the appliance manufacturer s instructions All external auxiliary control circuits should be connected with reference to the appropriate wiring diagram All systems and circuits should be checked to ensure that correctly rated fuses are used ...

Страница 11: ...PO Series General Information Page B 6 B B B B BURNER URNER URNER URNER URNER D D D D DESIGNA ESIGNA ESIGNA ESIGNA ESIGNATION TION TION TION TION C C C C CODE ODE ODE ODE ODE ...

Страница 12: ... ANDLING T T T T TEMPERA EMPERA EMPERA EMPERA EMPERATURES TURES TURES TURES TURES A A A A AND ND ND ND ND P P P P PRESSURES RESSURES RESSURES RESSURES RESSURES Fuel Class Viscosity Seconds Minimum From Tank Burner Inlet Atomising kg cm 2 psi D 35 0 35 to 0 70 5 to 10 E 200 16 16 82 960 30 43 110 1500 36 65 118 3500 50 82 132 4200 55 86 140 Fuel Handling Temperatures C Fuel Delivery Pressures Minim...

Страница 13: ...Series General Information Page B 8 T T T T TYPIC YPIC YPIC YPIC YPICAL AL AL AL AL P P P P PUMPED UMPED UMPED UMPED UMPED O O O O OIL IL IL IL IL R R R R RING ING ING ING ING M M M M MAIN AIN AIN AIN AIN ...

Страница 14: ...Page B 9 PO Series General Information ...

Страница 15: ...PO Series General Information Page B 10 AAD PFinal B_Gen PO B_Gen pmd 250504A ...

Страница 16: ...Page C 1 PO Series Technical Specification TECHNICAL SPECIFICATION ...

Страница 17: ...PO Series Technical Specification Page C 2 B B B B BURNER URNER URNER URNER URNER S S S S SPECIFIC PECIFIC PECIFIC PECIFIC PECIFICA A A A ATION TION TION TION TION S S S S SHEET HEET HEET HEET HEET ...

Страница 18: ...ulating unit Two adjustable cams are mounted on this shaft one of which is operating the burner air inlet control damper and is of the variable contour type the second cam is the modulating oil cam see illustrations on Page C 18 Oil System The Burner Oil Control System Drawings on pages C 10 11 show the burner hydraulic circuit Oil for combustion is drawn from the supply through a fixed displaceme...

Страница 19: ...and pressure given in the Table on Page B 8 Filter s are an integral part of the burner oil supply system The filter s should be checked regularly as failure to do so may result in a drop in oil pressure to the system Oil Control Train The oil control train consists of a high pressure fuel pump driven by the burner fan motor The oil nozzle throughput is controlled by a variable orifice regulator s...

Страница 20: ...r will then continue to its normal operating position i e it continues to supervise the control functions and is therefore able to shutdown the burner safely should this be necessary after driving to high fire the modulating controller will drive the burner towards the low flame position but depending on the temperature pressure will stop in any intermediate position between low and high flame the...

Страница 21: ...to the changed parameter Press and hold the PGM button down until the green set point figure changes to an AL the larger upper figures show the value Use the up down buttons to set the new value press the PGM button to enter the value and change to the next screen To cancel an entry press exit Scroll through the screens PGM button modifying any value found to be in error up down buttons At the las...

Страница 22: ... Control Damper Ignitor Terminal Box Assembly Oil Valve Assembly Burner Head Casing Transition Ductwork Combustion Air Fan Modulating Cam Unit Oil Lance Flame Tube Inner Assembly Access Plate Combustion Air Fan This diagram is for illustrative purposes only Actual components supplied may vary from those shown Please refer to the Burner Specification Sheet and the drawings elsewhere in this manual ...

Страница 23: ... u d o M 2 1 b x 4 s t u N g n i n i a t e R e t a l p k c a B 3 1 e n a V l o r t n o c r i A 4 1 t i n U r e p m a d r i A 5 1 y l b m e s s A k c o l B l a n i m r e T d n a r o t i n g I 6 1 s e l d n a H l a w a r d h t i W e t a l p k c a B 7 1 g n i s a C d a e H r e n r u B 8 1 d i o n e l o S f f o t u h S p i T e l z z o N 9 1 e c n a L l i O k c a B l l i p S 18 20 19 B B B B BURNER URN...

Страница 24: ...Page C 9 PO Series Technical Specification O O O O OIL IL IL IL IL P P P P PUMPS UMPS UMPS UMPS UMPS ...

Страница 25: ...re rated for 42kg cm 2 Pipework connections between the burner oil system and the separate pumping set are not supplied by Nu Way 3 Connections to the ring main on the air separator bottle air 1 BSP Spill Back Nozzle Tip Shut Off Solenoid Valve Solenoid Valve Pressure Guages Manifold Block Quick Release Couplings Flexible Connections Spill Control Valve Non Return Valve Feed To Burner Return from ...

Страница 26: ...ump Cold Filter Air Separator Return to Ring Main Optional Inlet from Ring Main Pressure Switch Lockshield Isolation Valve Hot Filter Thermo meter Burner Mounted Components Pumping Heating Set Components Notes 1 All interconnecting pipework must have a minimum bore of 19mm 3 4 and must be pressure rated for 42kg cm 2 Pipework connections between the burner oil system and the separate pumping set a...

Страница 27: ...PO Series Technical Specification Page C 12 D D D D DISTILL ISTILL ISTILL ISTILL ISTILLA A A A ATE TE TE TE TE O O O O OIL IL IL IL IL P P P P PUMPING UMPING UMPING UMPING UMPING S S S S SET ET ET ET ET ...

Страница 28: ...es Technical Specification R R R R RESIDU ESIDU ESIDU ESIDU ESIDUAL AL AL AL AL O O O O OIL IL IL IL IL P P P P PUMPING UMPING UMPING UMPING UMPING H H H H HEA EA EA EA EATING TING TING TING TING S S S S SET ET ET ET ET ...

Страница 29: ...ckout position Air Damper Closed proved by limit switch supplying voltage from terminal 11 to terminal 8 Fuel Valves closed proved by limit switch supplying voltage to terminal 12 Fuel pressure switch Limit Thermostat or Limit Pressure Switch all closed proved by continuity between terminals 4 and 5 Interruption to sequence whilst controller waits for the air damper to drive to open position prove...

Страница 30: ...Page C 15 PO Series Technical Specification B B B B BURNER URNER URNER URNER URNER H H H H HEAD EAD EAD EAD EAD ...

Страница 31: ...PO Series Technical Specification Page C 16 E E E E ELECTRODE LECTRODE LECTRODE LECTRODE LECTRODE S S S S SETTING ETTING ETTING ETTING ETTING D D D D DET ET ET ET ETAIL AIL AIL AIL AIL ...

Страница 32: ...MODUL ODUL ODUL ODUL ODULA A A A ATION TION TION TION TION C C C C CONTROLLER ONTROLLER ONTROLLER ONTROLLER ONTROLLER L L L L LANDIS ANDIS ANDIS ANDIS ANDIS AND AND AND AND AND S S S S ST T T T TAEF AEF AEF AEF AEFA A A A A RWF40 RWF40 RWF40 RWF40 RWF40 ...

Страница 33: ...ck Lever Servomotor Oil Spill Back Regulating Valve Oil Cam A Air Cam B Oil Cam Adjusting Screw Oil Cam Hub Rotation for High Flame Position Locking Screws Spill Pressure Reduce Increase Cam Disk Roller Adjustable Plunger Cam Follower Throw Oil Cam View On A Adjuster Locking Screws Profile Adjuster Profile Band Damper Drive Arm Cam Lever Roller Retaining Saddle Return Spring Air Cam View On B ...

Страница 34: ...Page C 19 PO Series Technical Specification ...

Страница 35: ...PO Series Technical Specification Page C 20 AAD PFinal C_Tech Po RWF40 C_Tech pmd 250504A ...

Страница 36: ...Page D 1 P Series Commissioning COMMISSIONING ...

Страница 37: ...t is important to Check that the electrical wiring is complete and complies with all applicable Codes and Standards Ensure that the fuses are fitted and are of the correct ratings Check electrical earthing Verify that the oil pipework is correctly sized and that it has been checked for leakage Check that the appropriate modulating detector which is supplied loose with each burner is fitted correct...

Страница 38: ...motor round to its start position and wait 6 Ensure that the flame detection system detects the presence of a simulated flame or where permissible an independent flame source Remove the flame detector from the burner expose the detector to a flame or simulated flame This should cause a lockout indicated by illumination of the corresponding indicator light on the control panel 7 Replace the flame d...

Страница 39: ...SSIONING THE THE THE THE THE B B B B BURNER URNER URNER URNER URNER Establish fuel supply to the burner Establish electrical supply to the control panel and switch the burner on If the burner sequence controller is at lockout press the re set button Warning From this point onwards the ignition sequence will be initiated and fuel will be admitted to the burner Care must be exercised NOTE HAND AUTO ...

Страница 40: ...terminal 20 and the wire that has been taken from terminal 20 4 Establish the electrical supply and switch on the burner Allow the burner to light and operate normally 5 Observe the reading on the micro ammeter at all firing levels A steady reading in excess of 7 microamps is satisfactory Lower readings may cause intermittent burner lock out and indicate a need for adjustment of the burner setting...

Страница 41: ... off manually c There is an electrical power failure In this event the burner will restart and run normally when power is restored No manual intervention is required d A failure in any of the safety functions monitored by the sequence controller On Completing Commissioning When commissioning has been completed satisfactorily the commissioning engineer shall prepare a report which shall contain the...

Страница 42: ...Page D 7 P Series Commissioning ...

Страница 43: ...e Where a choice of measurement units is shown delete those not applicable Flue Temp Ambient Temp Temp Difference Efficiency Heat input O2 CO2 CO Firing Rate Intermediate Positions Pressure at burner Oil rate Standing bar or psi Running bar or psi Commissioning Date Guarantee Expiry Date Fuel Oil Type Oil pressure upstream of pump Type Size Type Size Site Address The details below are to to be com...

Страница 44: ...Page D 9 P Series Commissioning AAD PFinal C_Tech Po RWF40 D_Comm pmd 250504A ...

Страница 45: ...P Series Page 10 ...

Страница 46: ...Page E 1 PO Series Operation And Maintenance E OPERATION AND MAINTENANCE ...

Страница 47: ...the electrical power supply to the burner Replace the PE cell Establish the electrical supply to the burner and switch on the burner Reset the lockout Combustion Air Pressure Switch 1 Check that the electrical supply to the control panel off and that the burner is off 2 Remove the air pressure switch cover 3 Fit a manometer or other approved pressure measuring instrument to the pressure switch so ...

Страница 48: ...OL BEFORE ATTEMPTING THESE TASKS In the case of the cold oil filter remove the plug from the sump and drain off any sludge and or water present at six weekly intervals The cleaning knob on this filter should be rotated daily If the filter fitted in the oil supply line has a disposable element this should be replaced at least once a year more frequently if this is dictated by the condition of the f...

Страница 49: ...ller to go to lockout If this occurs check that The glass envelope on the PE Cell is clean and correctly orientated it must face towards the flame The PE Cell and wiring are not faulty There is no carbon on the diffuser The nozzle is clear The flame detector current is adequate and stable The burner sequence controller is not faulty There is sufficient fuel under ignition conditions to enable the ...

Страница 50: ...Page E 5 PO Series Operation And Maintenance B B B B BURNER URNER URNER URNER URNER S S S S SERVICE ERVICE ERVICE ERVICE ERVICE R R R R RECORD ECORD ECORD ECORD ECORD ...

Страница 51: ...PO Series Operation And Maintenance Page E 6 ...

Страница 52: ...Page E 7 PO Series Operation And Maintenance ...

Страница 53: ...PO Series Operation And Maintenance Page E 8 N N N N NOTES OTES OTES OTES OTES ...

Страница 54: ...Page E 9 PO Series Operation And Maintenance N N N N NOTES OTES OTES OTES OTES ...

Страница 55: ...PO Series Operation And Maintenance Page E 10 N N N N NOTES OTES OTES OTES OTES ...

Страница 56: ...Enertech Limited P O Box 1 Vines Lane Droitwich Worcestershire WR9 8NA Tel 44 0 1905 794331 Fax 44 0 1905 794017 Email info nu way co uk Web www nu way co uk ...

Отзывы: