background image

 

192211A

 

Rated Voltage:

 

 

 

208VAC (150V to ground max) 

Class

-

A

 

Operating Voltage Range:

   

85% to 110% of rated

 

Current:

 

 

 

 

Up to 60 Amps or Device Rating

 

Horsepower:

  

 

 

Up to 20HP 3Ø/7.5HP 1Ø

 

Frequency:

   

 

 

60 Hz.

 

Trip Level:

   

 

 

5mA +/

-

 1mA

 

Response Time:

 

 

 

25ms max at 

500Ω 

fault

 

Power up:

 

 

 

 

Auto: Output is on immediately upon power up

 

 

 

 

 

 

Manual: Output is off immediately upon power up

 

Display:                                         Illuminated TEST/RESET pushbuttons, triple indication of 

 

 

 

 

 

 

Protecting & Power

-

out versus Fault

 

Enclosure:

   

 

 

High impact polycarbonate, 8x10x4inch, NEMA 4X

 

Operational Temperature:

   

-

35

° 

C to 50

° 

C (

-

31

° 

F to 122

° 

F)

 

Connections:

  

 

 

1 inch

-

trade, Various UL Listed category DWTT Liquid Tight, 

 

 

 

 

 

 

Hubbell P100NGYA (stocked)

 

Short Circuit:

  

 

 

10KA (panel tested), higher with appropriate fusing

 

Dielectric Withstand:

 

 

1500 VRMS across contact, 4000V to enclosure

 

Voltage Surge Withstand:

   

4000V/2000A 20

-

times per IEC 61000

-

4

-

5

 

Agency:

 

 

 

 

Listed to UL943 (KCXS.E205630)

 

  

 

IMPORTANT NOTE:

 

*Manual configuration should be specified when automatic power up would create an unsafe condition after resto-

ration of circuit power.

 

**Ground connection is done external to device enclosure.

 

TEST PROCEDURE:  

After the installation has been completed, apply line side power at the branch 

circuit breaker or fused disconnect.  Within a few seconds the GFCI shall close its contacts showing 
a GREEN illuminated RESET button, and YELLOW illuminated OUTPUT POWER light at the top 
left; (RESET must first be pressed for manual models).  After 10sec (self tests have completed), 
press the TEST button, now only the TEST button shall be illuminated RED.  If this test procedure 
does not respond exactly as described, power down installation, and contact the technical support 
provided.  

Always consult qualified electricians.

 

Technical Support: +1(440) 205

-

9188 

or 

[email protected]

 

Testing Procedure

 

Specifications

 

Decision Table

 

PGFS 

-

 8 6 1 0 8

 

Product type (default)

 

Permanent Ground Fault Splice

 

Voltage

   

(8) 208 VAC 3Ø

 

 

Ampacity

 

(3) 30 Amps

 

(6) 60 Amps

 

 

Power Up Type

 

(0) Manual

 

(1) Automatic

 

 

Fault Output 

 

(0) None

 

 

Designator

 

(8) 60amp Enclosure UL Listed 

 

1

 

2

 

3

 

4

 

5

 

6

 

7

 

Optional customized, 
listed at end with 

 

hyphen

 

(

-

XXX) OEM or Custom 

Coding  (X = number/
letter)

 