CBHF1-SM DIP SWITCH CONFIGURATION
Through the set of 8 dipswitches it is possible to change the charging curve (15 charging curves are available for
Wet and Gel batteries and it is possible to customize the charging profile under the specifications of battery
manufacturers), the battery voltage (12V or 24V) and the charging current (4A or 8A or 10A or 12A). The set of 8
dip switch is easy to find (is located under the front label of the charger, lifting the corner on the bottom-left) without
opening the charger.
D
IP
1 D
IP
2 D
IP
3 D
IP
4 for the selection of the CHARGING CURVE
D
IP
1 D
IP
2 D
IP
3 D
IP
4 C
HARGING
C
URVE
ON ON ON ON
0 -
Curve for charging DRYFIT TRACTION BLOCK (traction gel batteries).
OFF
ON ON ON
1 - Curve for charging TRACTION Lead-Acid (wet) batteries.
SETTING FOR NSS 2392111 - BATTERY, WET 12V, 115 AMP/HR
ON OFF ON ON
2 -
Curve for charging SEALED LEAD-ACID batteries.
OFF OFF ON ON
3 -
Curve for charging Sealed Lead-acid and GEL batteries from Trojan and
other manufacturers.
ON ON OFF ON
4 -
Curve for charging TRACTION Lead-Acid (wet) batteries w/float charge.
OFF ON OFF ON
5 -
Curve for charging SEALED LEAD-ACID batteries w/float charge.
ON OFF OFF ON
6 -
Curve for charging Sealed Lead-acid batteries and GEL batteries from
Trojan and other manufacturers w/float charge.
OFF OFF OFF ON
7 -
Curve for charging large capacity DRYFIT PzV (A800) GEL batteries.
ON ON ON OFF
8 -
Curve for charging GNB Sealed Lead-Acid batteries.
OFF ON ON OFF
9 -
Curve for charging Lead-Acid start-up batteries.
ON OFF ON OFF
10 -
Curve for charging DRYSAFE HAGEN batteries.
OFF OFF ON OFF
11 -
Curve for charging dryfit traction block batteries from Sonnenschein, DEKA
and other manufacturers.
ON ON OFF OFF
12 -
Curve for charging Lead-Acid starting batteries with stop.
OFF ON OFF OFF
13 -
Curve for charging Lead-Acid starting batteries with stop.
ON OFF OFF OFF
14
OFF OFF OFF OFF
15
D
IP
5 D
IP
6 D
IP
7 for the selection of the CURRENT
D
IP
8 for the selection of the battery voltage
D
IP
5 D
IP
6 D
IP
7 CURRENT
ON ON ON
4A
OFF ON ON
8A
ON OFF ON
10A
OFF OFF ON
12A
D
IP
8 VOLTS
O
N
12
O
FF
24
PROBLEMS
SOLUTIONS AND CHECKS
The battery charger does not switch on
Check that the plug is connected to the supply mains and
that the circuit breaker is efficient.
The charging cycle does not start and the message
‘bat’ is displayed.
Check the connection to the battery and the polarity.
The yellow indicator (4) will not light up even 15 hours
from the starting of the charging cycle, and the display
shows E03.
Check the battery for possible faulty components.
The message E01 is displayed
This means that the maximum voltage admissible by the
battery has been exceeded. The charging is interrupted.
If the battery charger is provided with a safety
thermostat and the message E02 is displayed.
This means that the maximum temperature has been
exceeded. The charging is interrupted.
The message SCt is displayed
This means that the total safety timer has interrupted the
charging.
The message Srt is displayed
This signals a possible internal short circuit.
ON