ZEF004410502 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Specifications & Instruction Manual 

 

 

ABSOCODER CONVERTER FOR CC-Link Ver. 1.10 

VE-2CC 

VM-2CC 

 

 

 

 

 

 

Applicable sensor: VRE-P028 

VRE-P062 

MRE-32SP062 

MRE-G

SP062 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Содержание VE-2CC

Страница 1: ...ZEF004410502 Specifications Instruction Manual ABSOCODER CONVERTER FOR CC Link Ver 1 10 VE 2CC VM 2CC Applicable sensor VRE P028 VRE P062 MRE 32SP062 MRE G SP062...

Страница 2: ......

Страница 3: ...not exposed to direct sunlight Be sure to consult with NSD when the controller is stored for long periods Do not hold the cable or shaft of ABSOCODER sensor during transport otherwise it will cause i...

Страница 4: ...s at the upper right of this manual s cover page Document No Date Revision Description ZEF004410500 20 Mar 2008 1st Edition Japanese document ZEF004410206 ZEF004410501 3 Mar 2014 2nd Edition Japanese...

Страница 5: ...Precautions 13 6 WIRING 14 6 1 Connection between Converter and ABSOCODER Sensor 14 6 2 Power Supply Connection 14 6 3 CC Link Connection 15 7 NOMENCLATURE and FUNCTION 16 7 1 Part Identification and...

Страница 6: ...VM 2CC 1 Absolute position detection An absolute position detection format ensures accurate position detection even if a power interruption condition occurs An origin returning operation is not requi...

Страница 7: ...Shaft shape flat flange mount type MRE G SP062FBC Total number of turns 64 128 160 256 320 Shaft shape key way flange mount type Extension sensor cable 4P S 0102 Standard cable cable length m 4P RBT 0...

Страница 8: ...helf type within enclosure Outside dimension mm 45 W 160 H 115 D Refer to dimensions for details Mass Approx 0 7kg 2 Performance Specification Items Specifications Converter model VE 2CC VM 2CC Applic...

Страница 9: ...own 4 h forward back 2 h conforms to JIS D 1601 standard Shock resistance 4 9 x 10 3 m s 2 500G 0 5 ms up down forward back X 3 times each conforms to JIS C 5026 standard Protection rating IP40 confor...

Страница 10: ...h forward back 2 h conforms to JIS D 1601 standard Shock resistance 4 9 x 10 3 m s 2 500G 0 5 ms up down forward back X 3 times each conforms to JIS C 5026 standard Protection rating IP52f conforms to...

Страница 11: ...6 4 DIMENSIONS 4 1 Converter VE 2CC VM 2CC Units mm...

Страница 12: ...7 4 2 ABSOCODER Sensor 1 VRE P028 Units mm...

Страница 13: ...8 2 VRE P062 Units mm...

Страница 14: ...9 Units mm...

Страница 15: ...10 3 MRE 32SP062 MRE G SP062 Units mm...

Страница 16: ...11 Units mm...

Страница 17: ...12 4 3 Extension Sensor Cable 3P S 0102 L 3P RBT 0102 L 4P S 0102 L 4P RBT 0102 L Units mm...

Страница 18: ...hips 7 Do not install in areas where flammable and or corrosive gases are present 8 Avoid areas where splashing water oil or chemicals are likely to occur 9 Avoid areas where vibration and shocks are...

Страница 19: ...than 75 mm 6 2 Power Supply Connection The power supply should be connected as described below 1 Power Supply The rush current is 10A rush time of 20ms so select the power supply after due considerati...

Страница 20: ...CC Link Both sides of the unit of CC Link must be connected with the terminal resistor Connect the terminating resistance between DA to DB Wiring method Power Supply CPU CC Link master I O I O PLC VE...

Страница 21: ...n SW settings of NODE and BR have an error SW setting is changed during the power supply is ON and then LED blinks SD Lights ON when sending the data RD Lights ON when receiving the data RUN Lights ON...

Страница 22: ...esponse but CRC errors are found in receiving the refresh data CRC errors are found in the data address to the station Link is not started No data address exists to the station The data is not receive...

Страница 23: ...data which is detected by the ABSOCODER It is communicated by using the remote register RWr Remote register RWr Device No Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0 RWr0 L D7 D6 D5 D4 D3 D2 D1 D0 RWr0 H...

Страница 24: ...ERROR RESET Device No RY0F RY0E RY0D RY0C RY0B RY0A RY09 RY08 Signal name PRESET Remote input RX Device No RX0F RX0E RX0D RX0C RX0B RX0A RX09 RX08 Signal name 0 0 0 0 0 0 0 PRESET ANSWER Signal expla...

Страница 25: ...scan is needed more than one time after writing the current position setting data PRD0 to PRD23 Link scan time is changed according to the communication speed number of connecting units and station t...

Страница 26: ...CC VM 2CC is set at 1 and 2 This is a program example when setting the current position for the station No 1 of VE 2CC VM 2CC For more details refer to the user s manual of the master unit Readout the...

Страница 27: ...verter has a malfunction ME Memory error Error 1 Normal 0 A memory error has occurred At power ON The position data is indefinite state RUN LED is OFF ERROR RESET RY00 ON If the error is not cleared t...

Страница 28: ...converter VE 2CC VM 2CC Connect with external device Connect ABSOCODER sensor and dedicated cable for CC Link Switch setting Set the station No and communication speed setting switch Test run Check th...

Страница 29: ...rent the data link will not be available Rotation direction setting switch of ABSOCODER Sets the increased rotation direction of the current position value Factory setting all OFF Note DIP switch 2 to...

Страница 30: ...ate normally if ABSOCODER is replaced VE 2CC VM 2CC has a malfunction Contact your NSD representative Is the communication cable connector disconnected Check the connection of the cable Refer to 7 3 L...

Страница 31: ...e causes are as follows Sensor cables are severed The internal circuit of VE 2CC VM 2CC has a malfunction ABSOCODER has a malfunction Contact your NSD representative VE 2CC VM 2CC has a malfunction Co...

Страница 32: ...KU NAGOYA JAPAN 460 8302 Distributor NSD Trading Corporation 3 31 23 OSU NAKA KU NAGOYA JAPAN 460 8302 Phone 81 52 261 2352 Facsimile 81 52 252 0522 URL www nsdcorp com E mail foreign nsdcorp com Copy...